2020-07-01 13:00:24 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | NFPA 70 2014 EDITION | | | | JAKE LEAHY BN, BU, PX | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | | | 1) VALUE OF WORK IS LOW PLEASE SUBMIT A SIGNED CONTRACT | | FOR WORK INVOLVED. | | | | 2) PANEL SHOWN IN LAUNDRY DOES NOT MEET 110.26 FOR | | WRKING CLEARANCES. | | | | 3) MASTER BDRM NEED TO MOVE SD TO CLOSE TO BATHROOM | | DOOR. | | | | 4) SUBFEEDER PIPE TO PANEL IS IT METAL IF NOT EQUIPMENT | | GROUND IS REQUIRED 250.122 | | | | 5) OUTLET IS REQUIRED AT THE FRONT AND REAR OF EACH | | DWELLING UNIT 210.52(E)(1) | | | | 6) COUNTER SPACE RECEPTACLES LOOKS LIKE IT DOES NOT | | MEET THE REQUIREMENTS 210.52(A)(4) |
|