2020-07-29 09:39:01 | 2ND REVIEW FBC-2017 PLUMBING |
| PERMIT- 20060908 |
| 7/29/2020 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| COMMENTS LISTED BELOW FROM THE 1ST REVIEW HAVE NOT BEEN |
| COMPLETELY ADDRESSED. ADDITIONAL NOTES IN CAPITAL |
| LETTERS HAVE BEEN PLACED AT THE END OF EACH COMMENT FOR |
| FURTHER EXPLANATION OF THE PLAN DEFICENCIES. |
| |
| 4) SHEET P1: PROVIDE ENLARGED, DIMENSIONED TOILET ROOM |
| DRAWINGS INDICATING: |
| A) CLEAR FLOOR SPACE DIMENSIONS FOR THE WATER CLOSETS- |
| SECTION 604.3 FBC ACC. |
| B) CLEAR FLOOR SPACE DIMENSIONS FOR THE LAVATORIES- |
| SECTION 606.2 |
| C) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE WALLS |
| OR PARTITIONS- SECTION 604.2. |
| D) DIAMETERS OF THE TURNING CIRCLES- SECTION 304.3. |
| (THE TOILET 2 PLAN ON SHEET A1 SHOWS THE LAVATORY |
| CENTERED AT 2'0 OFF THE SIDE WALL. THE ELEVATION DETAIL |
| ON P1 SHOWS IT CENTERED AT 15". THE LOCATIONS OF THE |
| FIXTURES BETWEEN THE TWO DRAWINGS DO NOT MATCH AND THE |
| 30X48" DIMENSIONS FOR THE LAVATORY CLEAR FLOOR SPACE IS |
| NOT SHOWN.) |
| |
| 5) P1: MODIFY THE ACCESSIBLE ELEVATION DETAIL IN |
| ACCORDANCE WITH FIGURES 604.5.1 AND 604.5.2 FBC ACC. A) |
| THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG MINIMUM, |
| LOCATED 12 INCHES MAXIMUM FROM THE REAR WALL AND |
| EXTENDING 54 INCHES MINIMUM FROM THE REAR WALL. B) THE |
| REAR WALL GRAB BAR SHALL BE 36 INCHES LONG MINIMUM AND |
| EXTEND FROM THE CENTERLINE OF THE WATER CLOSET 12 |
| INCHES MINIMUM ON ONE SIDE AND 24 INCHES MINIMUM ON THE |
| OTHER SIDE. (THE REAR GRAB IS NOT CENTERED PROPERLY |
| OVER THE WATER CLOSET AS SHOWN IN FIGURE 604.5.2.) |
| |
| 6) P1: MODIFY THE ACCESSIBLE ELEVATION DETAIL TO SHOW: |
| A) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION |
| 306. (THE 29" MINIMUM KNEE CLEARANCE AND MINIMUM 12? |
| CLEARANCE SHOWN ARE NOT IN COMPLIANCE. PLEASE REFER TO |
| FIGURES 306.2 AND 306.3 FOR REQUIRED CLEARANCES. PLEASE |
| USE THOSE FIGURES AS THE MODEL FOR YOUR LAVATORY |
| ELEVATION DETAIL.) |
| B) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS- |
| SECTION 604.6. |
| C) LOCATIONS, CLEARANCES, AND MOUNTING HEIGHTS FOR |
| PAPER DISPENSERS- SECTION 604.7. (THE TOILET PAPER |
| DISPENSER SHALL INSTALLED 7" MINIMUM AND 9" MAXIMUM |
| MEASURED FROM THE FRONT OF THE WATER CLOSET TO THE |
| CENTERLINE OF THE DISPENSER.) |
| D) HEIGHTS OF THE MIRROR FROM THE FINISHED FLOOR TO THE |
| BOTTOM OF THE REFLECTIVE SURFACES- SECTION 603.3. (THE |
| HEIGHT OF THE MIRROR IS SHOWN TO THE FRAME AND NOT THE |
| REFLECTIVE SURFACE AS REQUIRED BY SECTION 603.3.) |
| |
| 8) P1: HOT WATER SHALL BE PROVIDED TO THE SERVICE SINK- |
| SECTION 607.1 FBC P. PLEASE NOTE THAT AN EQUIPMENT |
| SCHEDULE WILL BE REQUIRED FOR WATER HEATER |
| INSTALLATIONS. THE SCHEDULE SHALL INDICATE MAKE AND |
| MODEL, ELECTRICAL DATA, AND EFFICIENCY RATING. A |
| SEPARATE DETAIL WILL BE REQUIRED TO SHOW THE PLUMBING |
| PIPING CONNECTIONS, ETC.- SECTION C404.2 FBC EC AND |
| SECTION 107.2.1 WPB. (THE WATER HEATER DETAIL SHOWS A |
| THERMAL EXPANISON PRESSURE REDUCING VALVE ON THE HOT |
| WATER LINE. A THERMAL EXPANSION TANK AND A PRESSURE |
| REDUCING VALVE ARE TWO SEPARATE DEVICES AND EACH SHALL |
| BE LOCATED ON THE COLD WATER LINE. |
| PRESSURE REDUCING VALVES SHALL BE LOCATED ON THE WATER |
| SERVICE LINE UPSTREAM OF THE MAIN SHUT OFF VALVE. |
| THERMAL EXPANSIO DEVICES SHALL BE INSTALLED ON THE COLD |
| WATER SUPPLY PIPE AT A POINT THAT IS DOWNSTREAM OF ALL |
| CHECK VALVES, PRESSURE REDUCING VALVES AND BACKFLOW |
| PREVENTERS- SEE SECTIONS 604.8 AND 607.3 FBC P.) |
| PLEASE NOTE THE STIEBEL ELTRON 6 GALLON WATER HEATER TO |
| BE INSTALLED ATHE MOP SINK IS A POINT OF USE WATER |
| HEATER AND WILL NOT ADEQUATELY SUPPLY THE LAVATORY SINK |
| WHICH ALSO REQUIRES TEMPERED WATER AS NOTED IN COMMENT |
| #9 BELOW. |
| |
| 9) P1: TEMPERED WATER WILL BE PROVIDED TO THE LAVATORY- |
| SECTION 416.5 FBC P. PLEASE NOTE THAT TEMPERED WATER |
| SHALL BE SUPPLIED THROUGH A WATER TEMPERATURE LIMITING |
| DEVICE THAT CONFORMS TO ASSE 1070 AND SHALL LIMIT THE |
| TEMPERED WATER TO A MAXIMUM OF 110 DEGREES F. (THE |
| REQUIRED TEMPERATURE LIMITING DEVICE WAS NOT PROVIDED.) |
| |
| 11) P1: THE PLAN SHOWS A REFRIGERATOR WHICH TYPICALLY |
| HAS AN ICE MAKER. PLEASE SHOW THE LINE CONNECTION IN |
| THE WATER ISOMETRIC AND INDICATE A WATER HAMMER AND |
| BACKFLOW PREVENTER WILL BE INSTALLED PER SECTIONS 604.9 |
| AND 608.3 FBC P. (COMMENT NOT ADDRESSED. IF NO ICE |
| MAKER IS TO BE INSTALLED PLEASE NOTE IT ON THE PLANS.) |
| |
| 12) THE $10,000 PROJECT VALUE APPEARS TO BE LOW FOR THE |
| SCOPE OF WORK SHOWN ON THE PLANS. PLEASE PROVIDE A COPY |
| OF A SIGNED CONTRACT AND/OR ESTIMATES, INVOICES ETC. TO |
| VERIFY THE TOTAL VALUE OF THE PROJECT. PLEASE NOTE THAT |
| VALUE IS BASED ON LABOR, MATERIALS, EQUIPMENT, |
| APPLIANCES, FIXTURES, SITE WORK, DESIGN FEES, AND |
| OVERHEAD AND PROFIT- SECTION 109.3 WPB. (COMMENT NOT |
| ADDRESSED) |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. (RESPONSE LETTER NOT PROVIDED) |
| |