Plan Review Notes
Plan Review Notes For Permit 20060908
Permit Number 20060908
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2020-07-29 10:16:54THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 THE PREVIOUS COMMENT BELOW WAS NOT ADDRESSED AND
 REMAINS:
  
  
 1) SHEET A 1 - THE KEY NOTES OF THE NEW FLOOR PLAN
 INDICATES A # 2 AT THE NEW WALL AREA AS GYPSUM WLL WITH
 1/2" DRYWALL; HOWEVER, NOTE # 5 FOR THE EXISTING WALL
 INDICATES 1 HOUR RATED.
  
 THE NEW WALL IS REQUIRED TO BE 1 HOUR FIRE RATED, THE
 SAME AS EXISTING.
  
 PLEASE REVIEW AND CORRECT.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  