2020-08-04 08:10:44 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| SERVICES/ BUILDING DIVISION |
| 2017 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 20060908 |
| ADD: 5520 GEORGIA AVE. |
| CONT: BADER?S GROUP LLC |
| TEL: 561-336-3891 |
| E-MAIL: [email protected] |
| |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 2ND REVIEW |
| DATE: TUES. AUGUST 04TH/ 2020 |
| ACTION: DENIED |
| ***NO RESPONSE LETTER. A TRANSMITTAL LETTER FROM THE |
| DESIGN PROFESSIONAL LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| 1) ON THE BUILDING PERMIT THE VALUE OF WORK STATED FOR |
| THE WORK TO BE ACCOMPLISHED UNDER THIS PERMIT IS |
| $10.000.00 DOLLARS OF VALUE. THE TOTAL VALUE OF THE |
| PROJECT IS $17,500.00 DOLLARS OF VALUE. THE VALUE OF |
| THIS PROJECT SEEMS LOW. |
| 109.3* BUILDING PERMIT VALUATION. |
| IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS |
| APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE |
| PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, |
| VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS |
| FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| CONGRESS. |
| |
| THIS MAIN BUILDING PERMIT WILL INCLUDE THE FEES FOR THE |
| MECHANICAL, ELECTRICAL, PLUMBING & ROOFING PERMITS. |
| WHEN THE GENERAL CONTRACTOR COMES IN FOR A BUILDING |
| PERMIT WITH THE SIGNED PERMIT APPLICATION FORM BY THE |
| QUALIFIER AND OWNER AND BRINGS IN THE LISTED |
| SUB-PERMITS M-E-P & ROOFING PERMITS SIGNED BY THE |
| QUALIFIER OF EACH COMPANY, THEIR INSURANCES AND |
| LICENSURE UP TO DATE, THE M-E-P AND ROOFING PERMITS ARE |
| FREE OF CHARGE. IF THE M-E-P & ROOFING PERMITS COME IN |
| LATER THERE WILL BE AN $80.00 ADMINISTRATIVE FEE FOR |
| EACH PERMIT. |
| |
| ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, RACK |
| STORAGE, EXHAUST HOODS, ANSUL SYSTEMS OR ALTERNATIVE |
| AUTOMATIC FIRE-EXTINGUISHING SYSTEMS, WALK IN COOLERS & |
| FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL |
| TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED |
| SUB-PERMITS, AWNING, SCREEN ENCLOSURES, CANOPY, FENCE, |
| LANDSCAPE, IRRIGATION, AUGER CAST PILE AND OR |
| FOUNDATION OR STRUCTURE ONLY PERMIT WILL BE SEPARATE |
| REVIEWS AND ASSOCIATED FEES WITH EACH PERMIT. |
| PLEASE PROVIDE AN ITEMIZED LIST AND SUBTRACT THESE LINE |
| ITEMS AND THEIR VALUE FROM THE OVERALL BUILDING VALUE |
| STATED ON THE PERMIT APPLICATION FOR THIS PROJECT. THE |
| REMAINING BALANCE WILL BE AFFECTIVELY THE VALUE OF THE |
| BUILDING YOU WILL BE PAYING FOR THIS PERMIT. THE |
| BUILDING DEPARTMENT DOES NOT WANT TO COLLECT TWICE FOR |
| THE VALUE OF THESE SUB-PERMITS NOT COVERED UNDER THE |
| PRIME OR MASTER PERMIT. |
| |
| 2) NO RESPONSE LETTER OR DESIGNATED ON PLANS. PHONE |
| CALLS CAN?T BE SUBSTANTIATED. DOES THE TENANT SPACE |
| HAVE A MEZZANINE OVER THE OFFICE SPACE, IF SO IT IS NOT |
| DECLARED IN THE SQUARE FOOTAGE OF THE TENANT SPACE? |
| 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED. |
| |
| 3-5) COMPLIED. |
| |
| 6) 2ND REQUEST. SUBMIT A COPY OF THE PRODUCT APPROVAL. |
| 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, |
| RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS |
| OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| APPROVALS: |
| (31)(A) EXTERIOR DOORS, |
| |
| 7) 2ND REQUEST. W. P. B. 107.3.4. PRODUCT APPROVALS. |
| THOSE PRODUCTS WHICH ARE REGULATED BY FLORIDA |
| ADMINISTRATIVE CODE RULE 61G20 SHALL BE REVIEWED AND |
| APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.. |
| |
| 8) 2ND REQUEST. THE RESTROOM ACCESSIBLE DETAIL IS FOUND |
| ON P-1 PLEASE NOTE THAT THE PLUMBING CONTRACTOR DOES |
| NOT INSTALL THE ACCESSIBLE GRAB BARS, PAPER HOLDERS, |
| AND MIRRORS IN THE RESTROOMS. THESE DETAILS SHOULD |
| ALWAYS BE ON THE ARCHITECTURAL SHEETS. 2017 |
| FBC-ACCESSIBILITY CODE SECTION 609.4 POSITION OF GRAB |
| BARS. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL |
| POSITION, 33 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE |
| THE FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING |
| SURFACE, NOT CENTERLINE. |
| |
| 8A) 2ND REQUEST. MISSING DETAIL FOR THE TOILET PAPER |
| DISPENSER LOCATION FOR SIDE WALL LOCATION. TOILET PAPER |
| DISPENSERS. 2017 ACCESSIBILITY CODE SECTION 604.7. |
| TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND |
| SHALL BE 7-9 INCHES MAXIMUM IN FRONT OF THE WATER |
| CLOSET MEASURED TO THE CENTER LINE OF THE DISPENSER. |
| THE OUTLET OF THE DISPENSER SHALL BE 15 INCHES MINIMUM |
| AND 48 INCHES MAXIMUM ABOVE THE FINISH FLOOR AND SHALL |
| NOT BE LOCATED BEHIND THE GRAB BARS. |
| |
| 8B) 2ND REQUEST. MIRROR LOCATION IS MEASURED AS SUCH: |
| 603.3 MIRRORS. 2017 FBC-ACCESSIBILITY CODE. MIRRORS |
| LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL BE |
| INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING |
| SURFACE 40 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR |
| GROUND. MIRRORS NOT LOCATED ABOVE LAVATORIES OR |
| COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE OF |
| THE REFLECTING SURFACE 35 INCHES MAXIMUM ABOVE THE |
| FINISH FLOOR OR GROUND. |
| |
| 8C) COMPLIED, REMOVED FROM PROJECT, BREAK ROOM SINK. |
| |
| 9) A TRANSMITTAL LETTER FROM THE DESIGN PROFESSIONAL |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH A |
| DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE SHEET |
| OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| ANTICIPATED COOPERATION. |
| |
| PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| 19 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| 561-718-9724. |
| JAMES A. WITMER BN, PX, SFP, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |