Plan Review Notes
Plan Review Notes For Permit 20060908
Permit Number 20060908
Review Stop B
Sequence Number 2
Notes
Date Text
2020-08-04 08:10:44WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20060908
 ADD: 5520 GEORGIA AVE.
 CONT: BADER?S GROUP LLC
 TEL: 561-336-3891
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. AUGUST 04TH/ 2020
 ACTION: DENIED
 ***NO RESPONSE LETTER. A TRANSMITTAL LETTER FROM THE
 DESIGN PROFESSIONAL LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1) ON THE BUILDING PERMIT THE VALUE OF WORK STATED FOR
 THE WORK TO BE ACCOMPLISHED UNDER THIS PERMIT IS
 $10.000.00 DOLLARS OF VALUE. THE TOTAL VALUE OF THE
 PROJECT IS $17,500.00 DOLLARS OF VALUE. THE VALUE OF
 THIS PROJECT SEEMS LOW.
 109.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 THIS MAIN BUILDING PERMIT WILL INCLUDE THE FEES FOR THE
 MECHANICAL, ELECTRICAL, PLUMBING & ROOFING PERMITS.
 WHEN THE GENERAL CONTRACTOR COMES IN FOR A BUILDING
 PERMIT WITH THE SIGNED PERMIT APPLICATION FORM BY THE
 QUALIFIER AND OWNER AND BRINGS IN THE LISTED
 SUB-PERMITS M-E-P & ROOFING PERMITS SIGNED BY THE
 QUALIFIER OF EACH COMPANY, THEIR INSURANCES AND
 LICENSURE UP TO DATE, THE M-E-P AND ROOFING PERMITS ARE
 FREE OF CHARGE. IF THE M-E-P & ROOFING PERMITS COME IN
 LATER THERE WILL BE AN $80.00 ADMINISTRATIVE FEE FOR
 EACH PERMIT.
  
 ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, RACK
 STORAGE, EXHAUST HOODS, ANSUL SYSTEMS OR ALTERNATIVE
 AUTOMATIC FIRE-EXTINGUISHING SYSTEMS, WALK IN COOLERS &
 FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL
 TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED
 SUB-PERMITS, AWNING, SCREEN ENCLOSURES, CANOPY, FENCE,
 LANDSCAPE, IRRIGATION, AUGER CAST PILE AND OR
 FOUNDATION OR STRUCTURE ONLY PERMIT WILL BE SEPARATE
 REVIEWS AND ASSOCIATED FEES WITH EACH PERMIT.
 PLEASE PROVIDE AN ITEMIZED LIST AND SUBTRACT THESE LINE
 ITEMS AND THEIR VALUE FROM THE OVERALL BUILDING VALUE
 STATED ON THE PERMIT APPLICATION FOR THIS PROJECT. THE
 REMAINING BALANCE WILL BE AFFECTIVELY THE VALUE OF THE
 BUILDING YOU WILL BE PAYING FOR THIS PERMIT. THE
 BUILDING DEPARTMENT DOES NOT WANT TO COLLECT TWICE FOR
 THE VALUE OF THESE SUB-PERMITS NOT COVERED UNDER THE
 PRIME OR MASTER PERMIT.
  
 2) NO RESPONSE LETTER OR DESIGNATED ON PLANS. PHONE
 CALLS CAN?T BE SUBSTANTIATED. DOES THE TENANT SPACE
 HAVE A MEZZANINE OVER THE OFFICE SPACE, IF SO IT IS NOT
 DECLARED IN THE SQUARE FOOTAGE OF THE TENANT SPACE?
 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED.
  
 3-5) COMPLIED.
  
 6) 2ND REQUEST. SUBMIT A COPY OF THE PRODUCT APPROVAL.
 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS,
  
 7) 2ND REQUEST. W. P. B. 107.3.4. PRODUCT APPROVALS.
 THOSE PRODUCTS WHICH ARE REGULATED BY FLORIDA
 ADMINISTRATIVE CODE RULE 61G20 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 8) 2ND REQUEST. THE RESTROOM ACCESSIBLE DETAIL IS FOUND
 ON P-1 PLEASE NOTE THAT THE PLUMBING CONTRACTOR DOES
 NOT INSTALL THE ACCESSIBLE GRAB BARS, PAPER HOLDERS,
 AND MIRRORS IN THE RESTROOMS. THESE DETAILS SHOULD
 ALWAYS BE ON THE ARCHITECTURAL SHEETS. 2017
 FBC-ACCESSIBILITY CODE SECTION 609.4 POSITION OF GRAB
 BARS. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL
 POSITION, 33 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE
 THE FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING
 SURFACE, NOT CENTERLINE.
  
 8A) 2ND REQUEST. MISSING DETAIL FOR THE TOILET PAPER
 DISPENSER LOCATION FOR SIDE WALL LOCATION. TOILET PAPER
 DISPENSERS. 2017 ACCESSIBILITY CODE SECTION 604.7.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7-9 INCHES MAXIMUM IN FRONT OF THE WATER
 CLOSET MEASURED TO THE CENTER LINE OF THE DISPENSER.
 THE OUTLET OF THE DISPENSER SHALL BE 15 INCHES MINIMUM
 AND 48 INCHES MAXIMUM ABOVE THE FINISH FLOOR AND SHALL
 NOT BE LOCATED BEHIND THE GRAB BARS.
  
 8B) 2ND REQUEST. MIRROR LOCATION IS MEASURED AS SUCH:
 603.3 MIRRORS. 2017 FBC-ACCESSIBILITY CODE. MIRRORS
 LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL BE
 INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND. MIRRORS NOT LOCATED ABOVE LAVATORIES OR
 COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE OF
 THE REFLECTING SURFACE 35 INCHES MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND.
  
 8C) COMPLIED, REMOVED FROM PROJECT, BREAK ROOM SINK.
  
 9) A TRANSMITTAL LETTER FROM THE DESIGN PROFESSIONAL
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  