Plan Review Notes
Plan Review Notes For Permit 20060908
Permit Number 20060908
Review Stop P
Sequence Number 1
Notes
Date Text
2020-07-08 09:56:461ST REVIEW FBC-2017 PLUMBING
 PERMIT- 20060908
 7/8/2020
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A-1: THE PLANS APPEAR TO SHOW TWO SEPARATE
 OCCUPANCIES BEING CREATED- REVISE THE SCOPE OF WORK
 NOTES TO CLARIFY- SECTION 107.2.1 WPB.
  
 2) A-1: THE RESTROOM CALCULATIONS ARE NOT IN COMPLIANCE
 WITH SECTION 403.1.1 AND TABLE 403.3 FBC P. BECAUSE
 THERE ARE TWO SEPARATE OCCUPANCIES, CALCULATIONS ARE
 REQUIRED FOR EACH. THE FIXTURES SHALL BE PROVIDED FOR
 BOTH THE PUBLIC AND EMPLOYEE USE- SECTION 403.3.
 PROVIDE ON THE PLAN A TABLE INDICATING THE REQUIRED AND
 PROVIDED FIXTURES FOR THE STORAGE-1/BUSINESS OCCUPANCY,
 AND THE SEPARATED STORAGE-1 OCCUPANCY. BASED ON THE
 OCCUPANT LOADS INDICATED, AND ON SECTION 403.2
 (SEPARATE FACILITIES) IT APPEARS THE STOR-1/BUS
 OCCUPANCIES REQUIRES DRINKING FOUNTAINS; AND THE SECOND
 STOR-1 OCCUPANCY REQUIRES DRINKING FOUNTAINS AND A
 SERVICE SINK IN ORDER TO MEET COMPLIANCE.
  
 3) CONCERNING THE MISSING DRINKING FOUNTAINS, REFER TO
 SECTION 211.1.2 FBC ACC: NO FEWER THAN TWO DRINKING
 FOUNTAINS SHALL BE PROVIDED. ONE DRINKING FOUNTAIN
 SHALL COMPLY WITH SECTIONS 602.1- 602.6, AND ONE SHALL
 COMPLY WITH 602.7. SECTION 602.7 REQUIRES THAT SPOUT
 OUTLETS FOR STANDING PERSONS SHALL BE 38 INCHES MINIMUM
 AND 43 INCHES MAXIMUM FROM THE FINISHED FLOOR. REVISE
 THE PLANS TO SHOW COMPLIANCE AND PROVIDE THESE DETAILS:
 A) THE CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR
 FORWARD WHEELCHAIR APPROACH- SECTION 602.2. FBC ACC.
 B) KNEE AND TOE CLEARANCES- SECTION 306.
 C) SPOUT HEIGHT AND SPOUT LOCATION- SECTION 602.4 AND
 602.5.
  
 4) SHEET P1: PROVIDE ENLARGED, DIMENSIONED TOILET ROOM
 DRAWINGS INDICATING:
 A) CLEAR FLOOR SPACE DIMENSIONS FOR THE WATER CLOSETS-
 SECTION 604.3 FBC ACC.
 B) CLEAR FLOOR SPACE DIMENSIONS FOR THE LAVATORIES-
 SECTION 606.2
 C) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE WALLS
 OR PARTITIONS- SECTION 604.2.
 D) DIAMETERS OF THE TURNING CIRCLES- SECTION 304.3.
  
 5) P1: MODIFY THE ACCESSIBLE ELEVATION DETAIL IN
 ACCORDANCE WITH FIGURES 604.5.1 AND 604.5.2 FBC ACC. A)
 THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG MINIMUM,
 LOCATED 12 INCHES MAXIMUM FROM THE REAR WALL AND
 EXTENDING 54 INCHES MINIMUM FROM THE REAR WALL. B) THE
 REAR WALL GRAB BAR SHALL BE 36 INCHES LONG MINIMUM AND
 EXTEND FROM THE CENTERLINE OF THE WATER CLOSET 12
 INCHES MINIMUM ON ONE SIDE AND 24 INCHES MINIMUM ON THE
 OTHER SIDE.
  
 6) P1: MODIFY THE ACCESSIBLE ELEVATION DETAIL TO SHOW:
 A) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION
 306.
 B) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS-
 SECTION 604.6.
 C) LOCATIONS, CLEARANCES, AND MOUNTING HEIGHTS FOR
 PAPER DISPENSERS- SECTION 604.7
 D) HEIGHTS OF THE MIRROR FROM THE FINISHED FLOOR TO THE
 BOTTOM OF THE REFLECTIVE SURFACES- SECTION 603.3.
  
 7) P1: THE LOUNGE SINK SHALL BE ACCESSIBLE- SECTION
 606.1 FBC ACC. PROVIDE DETAILS INCLUDING:
 A) CLEAR FLOOR DIAGRAM AND DIMENSIONS FOR FORWARD OR
 SIDE APPROACH- SECTION 305.
 B) KNEE AND TOE CLEARANCES- SECTION 306.
 C) HEIGHT OF THE SINK RIM OR COUNTER SURFACE- SECTION
 606.3.
  
 8) P1: HOT WATER SHALL BE PROVIDED TO THE SERVICE SINK-
 SECTION 607.1 FBC P. PLEASE NOTE THAT AN EQUIPMENT
 SCHEDULE WILL BE REQUIRED FOR WATER HEATER
 INSTALLATIONS. THE SCHEDULE SHALL INDICATE MAKE AND
 MODEL, ELECTRICAL DATA, AND EFFICIENCY RATING. A
 SEPARATE DETAIL WILL BE REQUIRED TO SHOW THE PLUMBING
 PIPING CONNECTIONS, ETC.- SECTION C404.2 FBC EC AND
 SECTION 107.2.1 WPB.
  
 9) P1: TEMPERED WATER WILL BE PROVIDED TO THE LAVATORY-
 SECTION 416.5 FBC P. PLEASE NOTE THAT TEMPERED WATER
 SHALL BE SUPPLIED THROUGH A WATER TEMPERATURE LIMITING
 DEVICE THAT CONFORMS TO ASSE 1070 AND SHALL LIMIT THE
 TEMPERED WATER TO A MAXIMUM OF 110 DEGREES F.
  
 10) P1: PROVIDE PLUMBING FIXTURE AND DEVICE SCHEDULES-
 SECTION 107.2.1 WPB.
  
 11) P1: THE PLAN SHOWS A REFRIGERATOR WHICH TYPICALLY
 HAS AN ICE MAKER. PLEASE SHOW THE LINE CONNECTION IN
 THE WATER ISOMETRIC AND INDICATE A WATER HAMMER AND
 BACKFLOW PREVENTER WILL BE INSTALLED PER SECTIONS 604.9
 AND 608.3 FBC P.
  
 12) THE $10,000 PROJECT VALUE APPEARS TO BE LOW FOR THE
 SCOPE OF WORK SHOWN ON THE PLANS. PLEASE PROVIDE A COPY
 OF A SIGNED CONTRACT AND/OR ESTIMATES, INVOICES ETC. TO
 VERIFY THE TOTAL VALUE OF THE PROJECT. PLEASE NOTE THAT
 VALUE IS BASED ON LABOR, MATERIALS, EQUIPMENT,
 APPLIANCES, FIXTURES, SITE WORK, DESIGN FEES, AND
 OVERHEAD AND PROFIT- SECTION 109.3 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER