Plan Review Notes For Permit 20060856 |
Permit Number |
20060856 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2020-08-27 10:42:18 | WINDOWS/DOORS | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected]. | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | AMENDMENTS | | 3RD REVIEW | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | 1) SIGNED AND SEALED WIND DESIGN PRESSURES PROVIDED ARE | | FOR A MEAN ROOF HEIGHT OF 15' - THE WIND DESIGN | | PRESSURES FOR THE WINDOWS ARE BASED ON THE BUILDING | | MEAN ROOF HEIGHT - BUILDING IS A 4 STORY BUILDING WHICH | | PUTS THE MEAN ROOF HEIGHT AT AROUND 40' - PLEASE | | PROVIDE SIGNED AND SEALED WIND DESIGN PRESSURES FOR THE | | BUILDING THAT THE WINDOWS/DOORS ARE BEING INSTALLED - | | THE BUILDING ADDRESS SHOULD APPEAR ON THE ENGINEERING | | TO VERIFY THE CORRECT BUILDING. | | |
|