2020-08-20 08:35:47 | WINDOWS/DOORS | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected]. | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | 1) NEED A COMPLETE (FRONT PAGES AND THE INSTALLATION | | INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE PRODUCT | | APPROVAL FOR THE WINDOWS, DOORS. | | 2) NEED SIGNED AND SEALED WIND DESIGN PRESSURES FROM AN | | ARCHITECT OR ENGINEER. FBC 1609 (BUILDING IS 4 STORIES) | | SHOW THE WIND DESIGN DATA USED ON THE WIND DESIGN | | PRESSURES. | | DRAWINGS/DOCUMENTS NEED TO BE DIGITALLY/ELECTRONICALLY | | SIGNED BY THE ENGINEER OR ARCHITECT TO BE USED IN | | ELECTRONIC PLAN REVIEW. | | | | FYI = ENGINEER CANNOT SELF-CERTIFY THE DIGITAL | | SIGNATURE | | 668.003(2) AND (3), F.S. | | (2) A PROFESSIONAL ENGINEER UTILIZING A DIGITAL | | SIGNATURE TO ELECTRONICALLY SIGN AND SEAL ENGINEERING | | PLANS, | | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS SHALL HAVE | | THEIR IDENTITY AUTHENTICATED BY A CERTIFICATION | | AUTHORITY. |
|