Plan Review Notes
Plan Review Notes For Permit 20060784
Permit Number 20060784
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2020-06-30 10:48:25THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE ARE INDICATIONS OF A CONCRETE SLAB AND RAMPS,
 HOWEVER, THERE IS NO DISCERNABLE GRADE INDICATION TO
 ENSURE A RAILING/GUARD IS REQUIRED.
  
 PER NFPA 101 CH 7
  
 7.2.5 RAMPS.
 7.2.5.1 GENERAL. EVERY RAMP USED AS A COMPONENT IN A
 MEANS OF
 EGRESS SHALL CONFORM TO THE GENERAL REQUIREMENTS OF
 SECTION 7.1
 AND TO THE SPECIAL REQUIREMENTS OF 7.2.5.
  
 7.2.5.5 GUARDS AND HANDRAILS.
 7.2.5.5.1 GUARDS COMPLYING WITH 7.2.2.4 SHALL BE
 PROVIDED FOR
 RAMPS, UNLESS OTHERWISE PROVIDED IN 7.2.5.5.4.
 7.2.5.5.2 HANDRAILS COMPLYING WITH 7.2.2.4 SHALL BE
 PROVIDED
 ALONG BOTH SIDES OF A RAMP RUN WITH A RISE GREATER THAN
 6 IN. (150
 MM), UNLESS OTHERWISE PROVIDED IN 7.2.5.5.4.
 7.2.5.5.3 THE HEIGHT OF HANDRAILS AND GUARDS SHALL BE
 MEASURED
 VERTICALLY TO THE TOP OF THE GUARD OR RAIL FROM THE
 WALKING SURFACE
 ADJACENT THERETO.
 7.2.5.5.4 THE REQUIREMENTS OF 7.2.5.5.1 AND 7.2.5.5.2
 SHALL NOT
 APPLY TO GUARDS AND HANDRAILS PROVIDED FOR RAMPED
 AISLES IN
 ASSEMBLY OCCUPANCIES AS OTHERWISE PROVIDED IN CHAPTERS
 12 AND
 13.
  
 7.2.5.7 SPECIAL PROVISIONS FOR OUTSIDE RAMPS.
 7.2.5.7.1* VISUAL PROTECTION. OUTSIDE RAMPS SHALL BE
 ARRANGED TO
 AVOID ANY IMPEDIMENTS TO THEIR USE BY PERSONS HAVING A
 FEAR OF
 HIGH PLACES. OUTSIDE RAMPS MORE THAN 36 FT (11 M) ABOVE
 THE
 FINISHED GROUND LEVEL SHALL BE PROVIDED WITH AN OPAQUE
 VISUAL
 OBSTRUCTION NOT LESS THAN 48 IN. (1220 MM) IN HEIGHT.
 7.2.5.7.2* WATER ACCUMULATION. OUTSIDE RAMPS AND
 LANDINGS
 SHALL BE DESIGNED TO MINIMIZE WATER ACCUMULATION ON
 THEIR
 SURFACES.
  
 PLEASE REVIEW AND PROVIDE DETAILS.
  
  
  
 2) ON SHEET 2 OF 9 OF THE FOREVER REWOOD SPEC SHEETS
 THERE ARE NO INDICATIONS OF CEILING FANS; HOWEVER,
 THERE ARE NO INDICATIONS OF ELECTRICAL WORK.
  
 ADDITIONALLY, THERE ARE NO INDICATIONS OF LIGHTING FOR
 THE PROPOSED.
  
 ANY ELECTICAL WORK WOULD REQUIRE PERMIITING AND PLAN
 SHEETS.
  
 PLEASE CORRECT OR PROVIDE A NOTE OF NO ELECTIC IS BEING
 PROPOSED.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  