2020-06-29 11:21:46 | 2017 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 20060784 |
| ADD: 4801 DREHER TRL. N. |
| CONT: GAST CONSTRUCTION |
| TEL: 561-281-1001 |
| E-MAIL: ASHLEY.YOKOTA@GASTCONSTTRUCTION GROUP.COM |
| |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 1ST REVIEW |
| DATE: MON. JUNE 29TH/ 2020 |
| ACTION: DENIED |
| |
| 1) 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATIVE CODE SECTION: |
| 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS AND |
| OR STRUCTURES. |
| 107.3.5.1 COMMERCIAL BUILDINGS |
| 107.3.5.1.1. BUILDING |
| MISSING CODE DATA: |
| SET BACK / SEPARATION (ASSUMED PROPERTY LINES) |
| FLOOD HAZARD AREAS, FLOOD ZONES, AND DESIGN FLOOD |
| ELEVATIONS |
| PROPOSED FLOOD ELEVATION CERTIFICATE FOR STRUCTURES IN |
| A SPECIFIC FLOOD HAZARD AREAS |
| OCCUPANCY GROUP |
| MINIMUM TYPE OF CONSTRUCTION |
| FIRE RESISTANCE SEPARATION |
| LIFE SAFETY PLANS SHALL DETERMINE AND SHALL INCLUDE THE |
| FOLLOWING: |
| OCCUPANT LOAD AND EGRESS CAPACITIES |
| GROSS OR NET |
| MEANS OF EGRESS EXIT ACCESS |
| EXIT |
| EXIT DISCHARGE |
| STRUCTURAL REQUIREMENTS SHALL INCLUDE: |
| DESIGN LOADS |
| WIND REQUIREMENTS |
| BUILDING ENVELOPE |
| STRUCTURAL CALCULATIONS/ IF REQUIRED. |
| FOUNDATION |
| FLOOD REQUIREMENTS IN ACCORDANCE WITH SECTION 1612 |
| WALL SYSTEMS/OR COLUMNS |
| ROOF SYSTEMS |
| |
| 2) SHEET LP-1 : |
| |
| 2A THE GRADING PLAN INDICATES THE FLOOR ELEVATION OF |
| THE EXISTING BUILDING AT 12.08 FEET. THE PLAN DOES NOT |
| INDICATE IF THIS ELEVATION IS IN NGVD OR NAVD88? THE |
| NEW PAVILION FINISH FLOOR ELEVATION IS NOT GIVEN. ) |
| BOTH BUILDINGS ARE IN AN AE FLOOD ZONE. |
| 2B) ARTICLE XVII ORDINANCES ARTICLE XVII FLOOD |
| PREVENTION & CONTROL. |
| FBC BUILDING 1612 AND CITY OF WPB CODE OF SECTION |
| 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD ZONE. A |
| FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED. PLEASE |
| REVIEW CITY ORDINANCE FOR THE CITY REQUIREMENTS REQUIRE |
| AN ADDITIONAL 6 INCHES/ (12 INCHES OF ELEVATION IF |
| PERMIT APPLICATION AFTER SEPT. 12/2016, |
| AFTER OCT. 11/ 2017 AN ADDITIONAL ONE FOOT OF FREE |
| BOARD WILL BE REQUIRED OR (2) FEET ABOVE BASE FLOOD. |
| AFTER OCT. 11/ 2017 THE BUILDING DEPARTMENT WILL HAVE |
| ADOPTED THE NEW FLOOD MAPS AND ALSO IN TOUGHS MAPS THE |
| NAVD 88 ELEVATIONS. YOU CAN GO TO THE WEBSITE: |
| WWW.NGS.NOAA.GOV/TOOLS/VERTCON/VERTCON.HTML FOR |
| CONVERSIONS. |
| 2C) DURING THE PERMITTING OF THIS STRUCTURE THERE WILL |
| BE REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES |
| REQUIRED: |
| (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE |
| PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR |
| HEIGHT. W. P. B. ADMINISTRATIVE CODE 107.3.5.1.1 |
| BUILDING MINIMUM PLAN REVIEW CRITERIA FOR COMMERCIAL |
| BUILDINGS. ( 8) FLOOD REQUIREMENTS ELEVATIONS, |
| ENCLOSURES, FLOOD DAMAGE-RESISTANT MATERIALS. |
| (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND |
| ELEVATION CERTIFICATE IS REQUIRED. W. P. B. |
| ADMINISTRATIVE CODE 110.3 REQUIRED INSPECTIONS 1.2 |
| FLOOR/ SLAB INSPECTION. IN FLOOD HAZARD AREAS, UPON |
| PLACEMENT OF THE LOWEST FLOOR, INCLUDING BASEMENT, AND |
| PRIOR TO FURTHER VERTICAL CONSTRUCTION, THE ELEVATION |
| CERTIFICATION, REQUIRED IN SECTION 1612.5, SHALL BE |
| SUBMITTED TO THE BUILDING OFFICIAL. |
| |
| (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY |
| OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE |
| CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR |
| ATTENDANTS A/C PADS OR OTHER SLABS FOR GENERATORS. |
| W. P. B. ADMINISTRATIVE CODE 110.3 REQUIRED INSPECTIONS |
| (6) FINAL INSPECTION. TO BE MADE AFTER THE BUILDING IS |
| COMPLETED AND READY FOR OCCUPANCY. 6.1. LOWEST FLOOR |
| ELEVATION. IN FLOOD HAZARD AREAS, AS PART OF THE FINAL |
| INSPECTION, A FINAL CERTIFICATION OF THE LOWEST FLOOR |
| ELEVATION SHALL BE SUBMITTED TO THE AUTHORITY HAVING |
| JURISDICTION. |
| |
| FEMA NEW FORM AVAILABLE JUNE 13/2016. |
| OMB NO. 1660-0008 |
| EXPIRATION DATE: NOV. 30/2018 |
| HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM |
| |
| 3) THE SUBMITTED SOILS REPORT FROM ALTERA IT WOULD SEAM |
| TO BE A PAPER COPY THAT WAS UPLOADED. FLORIDA |
| ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A SCANNED, |
| FACSIMILE, DIGITALLY CREATED OR COPIED IMAGE OF THE |
| LICENSEE?S SIGNATURE SHALL NOT BE USED ON DIGITALLY |
| SIGNED AND SEALED ENGINEERING PLANS, SPECIFICATIONS, |
| REPORTS OR OTHER DOCUMENTS. |
| |
| 4) THERE ARE NO STRUCTURAL SHEETS GIVING THE STRUCTURAL |
| DESIGN AND FABRICATION REQUIRED FOR THE PROPOSED |
| PAVILION. THE SUBMITTED FOREVER REDWOOD DRAWINGS 1-9 IT |
| APPEARS TO BE DIGITALLY SIGNED AND SEALED. THERE IS NO |
| DESIGNER OF RECORD FOR THE PAVILION. THE SUBMITTED 9 |
| SHEETS FROM FOREVER REDWOOD ARE MORE OF A SALES |
| BROCHURE OF THE PAVILION, THERE SHOULD BE ENGINEERED |
| DRAWINGS. SHEET 7 OF 9 STATES SEE STRUCTURAL DRAWINGS |
| FOR CONNECTIONS. |
| |
| 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1, ADMINISTRATION 107.2.1. |
| W.P.B. ADMINISTRATIVE CODE/2017 DRAWINGS & |
| SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM |
| OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, |
| WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE |
| TECHNICAL CODES. CONSTRUCTION DOCUMENTS SHALL BE |
| SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| DETERMINED BY THE BUILDING OFFICIAL. |
| |
| 5) THERE ARE 2 DIFFERENT ROOFING PRODUCT APPROVALS, |
| BOTH HAVE MULTIPLE SUB-SYSTEMS, DIFFEENT METAL ROOFING |
| STYLES, AND PRESSURES WITH VARIOUS ANCHOR SPACINGS |
| NOTHING HAS BEEN IDENTIFIED AS TO WHICH SUB-SYSTEM AND |
| ANCHOR SPACING WAS IDENTIFIED. |
| |
| 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY THE CODE, THE |
| CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND |
| DELINEATE THE TYPE OF ROOFING SYSTEM, MATERIALS, |
| VENTING, FASTENING REQUIREMENTS, FLASHING REQUIREMENTS |
| AND WIND RESISTANCE RATING THAT ARE REQUIRED TO BE |
| INSTALLED. PRODUCT EVALUATION AND INSTALLATION SHALL |
| INDICATE COMPLIANCE WITH THE WIND CRITERIA REQUIRED FOR |
| THE SPECIFIC SITE. |
| |
| 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED |
| DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE |
| MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS |
| AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |
| |
| PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| 19 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| 561-718-9724. |
| JAMES A. WITMER BN, PX, SFP, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |