2021-08-17 15:59:47 | 2ND REVIEW FBC-2020 MECHANICAL |
| PERMIT-20060761 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE |
| FBC M- FLORIDA MECHANICAL CODE |
| FBC EC- FLORIDA ENERGY CONSERVATION |
| FBC FG- FLORIDA FUEL GAS |
| FBC EX- FLORIDA EXISTING BUILDING CODE |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) PLEASE SHOW HOW THE VENTILATION FOR ALL SPACES OF |
| THIS TENANT SPACE WILL MEET FBC M 401.3 (VENTILATION |
| SHALL BE PROVIDED DURING THE PERIODS THAT THE ROOM OR |
| SPACE IS OCCUPIED.) |
| |
| 2) PLEASE PROVIDE MECHANICAL EQUIPMENT SIZING |
| CALCULATIONS BASED ON THE NATURAL VENTILATION OF THE |
| CHANGE OF USE OF THE SPACES. FBC EC C403.2.1 |
| |
| 3) PLEASE ADDRESS ALL OF THE COMMENTS FROM THE 1ST |
| CYCLE MECHANICAL REVIEW LISTED BELOW. |
| |
| |
| 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT-20060761 |
| |
| |
| |
| 2) PLEASE PROVIDE COMPLETE DRAWINGS OF THE EXISTING |
| MECHANICAL SYSTEM AND INCLUDE ANY NEW CHANGES. THIS |
| DRAWING MUST SHOW THE RATED WALLS USED AS SEPARATION |
| BETWEEN THE NEW OCCUPANCIES WITH DAMPERS IF ANY DUCT |
| WORK IS PENETRATING THESE RATED WALLS. FBC FS 107.2.1 |
| |
| 3) PLEASE PROVIDE VENTILATION CALCULATIONS FOR THIS NEW |
| PROJECT, FOR ALL AREAS. THE NATURAL VENTILATION |
| CALCULATIONS IN THIS PACKAGE WOULD NOT WORK AS THERE |
| SHOULD BE A RATED WALL BETWEEN THE F-2 AND B |
| OCCUPANCIES. FBC M 403 |
| |
| 4) PLEASE PROVIDE QUANTITIES OF INGREDIENTS STORED AT |
| THIS FACILITY. FBC FS 107.2.1 |
| |
| 5) PLEASE SHOW THE EXHAUST FOR THE MASH AREA. FBC FS |
| 107.2.1 |
| |
| 6) PLEASE PROVIDE A VENTING DETAIL FOR THE CO2 TO AN |
| APPROVED TERMINATION LOCATION. FBC FS 107.2.1 |
| |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| UPDATED. |
| |
| |