Plan Review Notes For Permit 20060761 |
Permit Number |
20060761 |
|
Review Stop |
FIRE |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2021-07-30 14:50:51 | 1) SHEET LS .100 - THERE IS NO INDICATION OF WHETHER | | THIS IS A MIXED OR SEPARATED OCCUPANCY. | | | | THERE IS AN INDICATION THAT THE ASSEMBLY AREA IS | | ACCESSORY; HOWEVER, PER NFPA 101, IT DOES NOT APPEAR TO | | BE ACCESSORTY. | | | | PER NFPA 101 | | | | PER TABLE 6.1.14.4.1 (B) | | | | THE REQUIRED SEPARATION OF AN INDUSTRIAL GENERAL | | HAZARD/SPECIAL HAZARD AND MERCANTILE/ASSEMBLY IS 2 | | HOURS. | | | | IS THE FIRE CODE REQUIREMENT IS MORE | | RESTRICTIVE/STRINGENT THAN THE BUILDING CODE CITED, | | THEN THE FIRE CODE APPLIES. | | | | A 2 HOUR FIRE RATED SEPARATION IS REQUIRED. | | | | PLEASE REVIEW AND PROVIDE DETAILS AND FOR THE REQUIRED | | SEPARATION. | | | | | | | | 2) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|