2021-08-27 14:40:36 | 2ND REVIEW FBC-2017 BUILDING |
| PERMIT- 20060761 |
| 8/27/2021 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) [NOT RESOLVED.] THE PLANS THAT WERE SUBMITTED ONLY |
| HAVE A FEW DIMENSIONS ON THEM. SUBMIT DRAWINGS WITH ALL |
| DIMENSIONS SPECIFIED ON THEM. FBC 107.2.1 |
| |
| 2) [NOT RESOLVED.] SPECIFY THE EXISTING OCCUPANCY TYPE |
| FOR THIS SPACE ON THE PLANS. FBC 107.2.1 |
| |
| 3) [THIS WILL BE A PROVISO TO BE VERIFIED BY THE FIELD |
| INSPECTOR.] VERIFY THAT THE TENANT SEPARATION WALLS ON |
| EACH SIDE OF THE SPACE ARE 2 HOUR FIRE RESISTIVE RATED. |
| FBC 706 |
| |
| 4) [NOT RESOLVED. THE CONSTRUCTION TYPE IS SPECIFIED AS |
| TYPE IV ON THE PLANS IN THE CITY'S RECORDS. THE PLANS |
| FOR THE BUILDING HAS NON-COMBUSTIBLE FLOORS, BEARING |
| WALLS, AND ROOF CONSTRUCTION. THE CONSTRUCTION TYPES IN |
| THE BUILDING CODES HAVE CHANGED SINCE THIS BUILDING WAS |
| CONSTRUCTED. BASED ON THE 2017 FBC THE CONSTRUCTION |
| TYPE FOR THIS BUILDING IS TYPE II-B. PLEASE CHANGE THE |
| CONSTRUCTION TYPE ON THE PLANS FROM V-B TO II-B.] THE |
| TYPE OF CONSTRUCTION FOR THIS BUILDING IS SPECIFIED AS |
| TYPE V ON SHEET LS.100. SPECIFY IF IT IS TYPE V-A OR |
| V-B CONSTRUCTION. BASED ON MY RESEARCH THIS SPACE IS |
| LOCATED IN A 14,400 SQUARE FOOT WAREHOUSE BUILDING. IT |
| IS LOCATED IN BUILDING #4 IN A GROUP OF OTHER WAREHOUSE |
| BUILDINGS. THE ORIGINAL OCCUPANCY WAS BUSINESS AND |
| WAREHOUSE. IT DOES NOT APPEAR THAT THIS BUILDING IS |
| TYPE V CONSTRUCTION. PLEASE VERIFY THE CONSTRUCTION |
| TYPE. FBC 601 |
| |
| 5) [RESOLVED.] ONE SHEET LS.100 YOU HAVE INCLUDED THE |
| CELLAR AND BAR SERVICE AREAS WITH THE F-2 OCCUPANCY. IT |
| APPEARS THAT THE BAR SERVICE AREA AND POSSIBLY THE |
| CELLAR AREA SHOULD BE INCLUDED WITH THE A2 OCCUPANCY. |
| PLEASE CLARIFY THE INTENDED USE OF THE CELLAR. EXPLAIN |
| WHY THE BAR SERVICE AREA AND THE CELLAR SHOULD NOT BE |
| PART OF THE ASSEMBLY AREA. |
| |
| 6) [RESOLVED.] THE SECTION THAT ALLOWS ASSEMBLY AREAS |
| WITH AN OCCUPANT LOAD OF LESS THAN 50 PERSONS TO BE |
| CLASSIFIED AS A GROUP B OCCUPANCY DOES NOT ALLOW THE |
| OCCUPANT LOAD FOR THE ASSEMBLY AREA TO BE RECALCULATED |
| USING THE OCCUPANT LOAD FACTOR FOR A BUSINESS |
| OCCUPANCY. THE NUMBER OF OCCUPANTS STAYS THE SAME AS |
| CALCULATED FOR AN ASSEMBLY AREA. PLEASE CORRECT. FBC |
| 1004 & FBC 303.1.1 SMALL BUILDINGS AND TENANT SPACES A |
| BUILDING OR TENANT SPACE USED FOR ASSEMBLY PURPOSES |
| WITH AN OCCUPANT LOAD OF LESS THAN 50 PERSONS SHALL BE |
| CLASSIFIED AS A GROUP B OCCUPANCY. |
| |
| 7) [NOT RESOLVED. THE RESPONSE LETTER STATES THAT THIS |
| IS A NON-SEPARATED MIXED USE OCCUPANCY. SPECIFY THIS ON |
| THE PLANS AND REMOVE THE STATEMENT ON SHEET ON SHEET |
| LS.100 THAT SPECIFIES THAT THE ASSEMBLY OCCUPANCY IS |
| ACCESSORY TO THE F-2 OCCUPANCY.] FBC 508.2.3 STATES |
| THAT AGGREGATE ACCESSORY OCCUPANCIES SHALL NOT OCCUPY |
| MORE THAN 10 PERCENT OF THE FLOOR AREA OF THE STORY IN |
| WHICH THEY ARE LOCATED. SINCE THE FLOOR AREA OF THE |
| ASSEMBLY AREAS IS MORE THAN 10 PERCENT THIS CAN NOT BE |
| AN ACCESSORY OR ANCILLARY OCCUPANCY. THIS IS A MIXED |
| USE OCCUPANCY. YOU WILL NEED TO DETERMINE IF IT WILL BE |
| A NON-SEPARATED OCCUPANCY OR A SEPARATED OCCUPANCY PER |
| FBC508.3 OR 508.4. |
| |
| 8) [NOT RESOLVED. CHANGE THIS TO SPECIFY 2017 FBC |
| SECTION 1006.2.] ON SHEET LS.100 UNDER EGRESS |
| REQUIREMENTS THE NUMBER OF REQUIRED EXITS SPECIFIES FBC |
| 2014 SECTION 1021.2(2). PLEASE CORRECT THIS TO |
| REFERENCE THE 2017 FBC AND THE APPROPRIATE SECTION. |
| |
| FLORIDA ACCESSIBILITY COMMENTS : THIS IS A CHANGE OF |
| OCCUPANCY AND IS TREATED AS NEW CONSTRUCTION FOR THE |
| APPLICATION OF ACCESSIBILITY REQUIREMENTS. FBC EXISTING |
| BUILDING 1006.1 GENERAL. ACCESSIBILITY IN PORTIONS OF |
| BUILDINGS UNDERGOING A CHANGE OF OCCUPANCY |
| CLASSIFICATION SHALL COMPLY WITH THE PROVISIONS OF THE |
| FLORIDA BUILDING CODE, ACCESSIBILITY. |
| |
| 9) [ NOT RESOLVED. PROVIDE A COST BREAKDOWN TO SHOW HOW |
| THE 20% DISPROPORTIONATE COSTS WILL BE SPENT TOWARD |
| IMPROVING ACCESSIBILITY.] SHOW ACCESSIBLE PARKING |
| SPACES, ACCESSIBLE ROUTE TO ACCESSIBLE ENTRANCE AND |
| THROUGH PRIMARY SERVICE AREA. FBC - ACCESSIBILITY 206 |
| AND 208 |
| |
| 10) [NOT RESOLVED. PROVIDE DETAILED DRAWINGS, |
| ELEVATIONS, ETC. TO SHOW THAT THE BATHROOMS COMPLY WITH |
| ACCESSIBILITY.] SHOW THAT BATHROOMS MEET ACCESSIBILITY |
| REQUIREMENTS. 603 TOILET AND BATHING ROOMS. 603.1 |
| GENERAL. TOILET AND BATHING ROOMS SHALL COMPLY WITH 603 |
| |
| 11) [NOT RESOLVED. THE RESPONSE LETTER STATES THAT THE |
| BAR TOP WILL BE USED FOR BEVERAGE SERVICE AND THE FLOOR |
| PLAN SHOWS SEATING AT THE BAR TOP. THIS BAR IS NEW |
| CONSTRUCTION AND IT WILL HAVE TO COMPLY WITH |
| ACCESSIBILITY.] SHOW ACCESSIBLE AREAS AT THE BARS. FBC |
| - ACCESSIBILITY 226.1 GENERAL. WHERE DINING SURFACES |
| ARE PROVIDED FOR THE CONSUMPTION OF FOOD OR DRINK, AT |
| LEAST 5 PERCENT OF THE SEATING SPACES AND STANDING |
| SPACES AT THE DINING SURFACES SHALL COMPLY WITH 902. IN |
| ADDITION, WHERE WORK SURFACES ARE PROVIDED FOR USE BY |
| OTHER THAN EMPLOYEES, AT LEAST 5 PERCENT SHALL COMPLY |
| WITH 902. |
| |
| 12) [RESOLVED.] SHOW ACCESSIBLE SEATING DISPERSED |
| THROUGHOUT TASTING AREAS. FBC - A 226.2 DISPERSION. |
| DINING SURFACES AND WORK SURFACES REQUIRED TO COMPLY |
| WITH 902 SHALL BE DISPERSED THROUGHOUT THE SPACE OR |
| FACILITY CONTAINING DINING SURFACES AND WORK SURFACES. |
| |
| 13) [ NOT RESOLVED. THE BAR TOP WILL BE USED AS A |
| SERVICE COUNTER AND WILL HAVE TO COMPLY WITH FBC |
| ACCESSIBILITY.] SHOW THAT THE SALES/SERVICE COUNTER |
| COMPLIES WITH ACCESSIBILITY. FBC - A 904.4 SALES AND |
| SERVICE COUNTERS. SALES COUNTERS AND SERVICE COUNTERS |
| SHALL COMPLY WITH 904.4.1 OR 904.4.2. THE ACCESSIBLE |
| PORTION OF THE COUNTER TOP SHALL EXTEND THE SAME DEPTH |
| AS THE SALES OR SERVICE COUNTER TOP. |
| |
| 14) NEW COMMENT.THE TOTAL NUMBER OF OCCUPANTS IS |
| SPECIFIED AS 46.2 PERSONS ON SHEET LS.100. SINCE THERE |
| CAN NOT BE A FRACTION OF A PERSON, THE TOTAL NEEDS TO |
| BE ROUNDED UP TO THE NEXT HIGHER WHOLE NUMBER WHICH IS |
| 47 PERSONS. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |
| |