Date Text
2020-06-22 16:17:26THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) SHEET LS .100 - THERE IS NO INDICATION OF WHETHER
 THIS IS A MIXED OR SEPARATED OCCUPANCY.
  
 THERE IS AN INDICATION THAT THE ASEMBLY AREA IS
 ACCESSORY; HOWEVER, PER NFPA 101, IT DOES NOT APPEAR TO
 BE ACCESSORTY.
  
 PER NFPA 101
  
 6.1 CLASSIFICATION OF OCCUPANCY.
 6.1.1 GENERAL.
 6.1.1.1 OCCUPANCY CLASSIFICATION. THE OCCUPANCY OF A
 BUILDING OR
 STRUCTURE, OR PORTION OF A BUILDING OR STRUCTURE, SHALL
 BE CLASSIFIED IN
 ACCORDANCE WITH 6.1.2 THROUGH 6.1.13. OCCUPANCY
 CLASSIFICATION SHALL BE
 SUBJECT TO THE RULING OF THE AUTHORITY HAVING
 JURISDICTION WHERE THERE IS A
 QUESTION OF PROPER CLASSIFICATION IN ANY INDIVIDUAL
 CASE.
  
 6.1.14 MULTIPLE OCCUPANCIES.
 6.1.14.1 GENERAL.
 6.1.14.1.1 MULTIPLE OCCUPANCIES SHALL COMPLY WITH THE
 REQUIREMENTS OF
 6.1.14.1 AND ONE OF THE FOLLOWING:
 (1) MIXED OCCUPANCIES ? 6.1.14.3
 (2) SEPARATED OCCUPANCIES ? 6.1.14.4
  
 6.1.14.1.2 WHERE EXIT ACCESS FROM AN OCCUPANCY
 TRAVERSES ANOTHER
 OCCUPANCY, THE MULTIPLE OCCUPANCY SHALL BE TREATED AS A
 MIXED
 OCCUPANCY.
 6.1.14.1.3* WHERE INCIDENTAL TO ANOTHER OCCUPANCY,
 AREAS USED AS
 FOLLOWS SHALL BE PERMITTED TO BE CONSIDERED PART OF THE
 PREDOMINANT
 OCCUPANCY AND SHALL BE SUBJECT TO THE PROVISIONS OF THE
 CODE THAT APPLY
 TO THE PREDOMINANT OCCUPANCY:
 (1) MERCANTILE, BUSINESS, INDUSTRIAL, OR STORAGE USE
 (2) *NONRESIDENTIAL USE WITH AN OCCUPANT LOAD FEWER
 THAN THAT
 ESTABLISHED BY SECTION 6.1 FOR THE OCCUPANCY THRESHOLD
 (3) PORTIONS OF BUILDINGS USED AS ACCESSORY OFFICES OR
 FOR CUSTOMARY
 NON-HAZARDOUS USES NECESSARY FOR TRANSACTING THE
 PRINCIPAL
 BUSINESS IN STORAGE AND INDUSTRIAL OCCUPANCIES NEED NOT
 BE
 SEPARATED FROM THE PRINCIPAL USE.
 (4) INDUSTRIAL OCCUPANCIES PRODUCING, USING, OR STORING
 LOW HAZARD
 PRODUCTS IN ACCORDANCE WITH SUBDIVISION 6.2.2 NEED NOT
 BE
 SEPARATED BY FIRE-RESISTANT CONSTRUCTION FROM THE
 OCCUPANCIES TO
 WHICH THEY ARE ACCESSORY.
 6.1.14.1.3.1 INCIDENTAL USE AREAS SHALL BE SEPARATED AS
 REQUIRED BY TABLE
 508.2.5 OF THE FLORIDA BUILDING CODE WHERE TABLE
 508.2.5 PERMITS AN
 AUTOMATIC FIRE-EXTINGUISHING SYSTEM WITHOUT A FIRE
 BARRIER, THE INCIDENTAL
 USE AREA SHALL BE SEPARATED BY CONSTRUCTION CAPABLE OF
 RESISTING THE
 PASSAGE OF SMOKE.
 6.1.14.1.4 THE FOLLOWING ACCESSORY OCCUPANCIES SHALL
 NOT BE REQUIRED TO
 BE SEPARATED FROM THE PRIMARY OCCUPANCY AS REQUIRED IN
 6.1.14.4:
 (1) A KITCHEN IN AN ASSEMBLY OCCUPANCY DOES NOT
 CONSTITUTE A MIXED
 OCCUPANCY.
 (2) ACCESSORY USES IN INDUSTRIAL AND STORAGE
 OCCUPANCIES AS OTHERWISE
 PROVIDED IN 6.1.14.1.3(1)
 (3) ROOMS OR SPACES USED FOR CUSTOMARY STORAGE OF
 NON-HAZARDOUS
 MATERIALS IN ASSEMBLY, BUSINESS, EDUCATIONAL,
 INDUSTRIAL,
 MERCANTILE, HOTEL AND DORMITORY, AND APARTMENT
 OCCUPANCIES WHICH
 IN AGGREGATE DO NOT EXCEED 10% OF THE MAJOR FLOOR AREA
 IN WHICH
 THEY ARE LOCATED. PROTECTION FROM HAZARDS SHALL BE AS
 OTHERWISE
 PROVIDED IN THE SPECIFIC OCCUPANCY CHAPTER
  
  
 6.2.1.3* FOR THE PURPOSE OF THIS CODE, WHERE DIFFERENT
 DEGREES OF
 HAZARD OF CONTENTS EXIST IN DIFFERENT PARTS OF A
 BUILDING OR STRUCTURE,
 THE MOST HAZARDOUS SHALL GOVERN THE CLASSIFICATION,
 UNLESS
 HAZARDOUS AREAS ARE SEPARATED OR PROTECTED AS SPECIFIED
 IN SECTION
 8.7 AND THE APPLICABLE SECTIONS OF CHAPTERS 11 THROUGH
 43.
  
  
 PLEASE REVIEW AND PROVIDE DETAILS AND FOR THE REQUIRED
 SEPARATION.
  
  
  
 1A) SHEET A.100 - THE TASTING ROOM APPEARS TO BE MORE
 OF A BAR THAN A ROOM IS MORE THAN INCIDENTAL TO THE
 OCCUPANCY.
  
 PER NFPA 101, TABLE 6.1.14.4.1(B) A 2 HOUR SEPARATION
 IS REQUIRED
  
 6.2.1.3* FOR THE PURPOSE OF THIS CODE, WHERE DIFFERENT
 DEGREES OF
 HAZARD OF CONTENTS EXIST IN DIFFERENT PARTS OF A
 BUILDING OR STRUCTURE,
 THE MOST HAZARDOUS SHALL GOVERN THE CLASSIFICATION,
 UNLESS
 HAZARDOUS AREAS ARE SEPARATED OR PROTECTED AS SPECIFIED
 IN SECTION
 8.7 AND THE APPLICABLE SECTIONS OF CHAPTERS 11 THROUGH
 43.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
  
 2) SHEET S 7 OF 8 - FERMENTOR CO2 VENT SYSTEM - THERE
 IS AN INDICATION OF A VENTING SYSTEM THAT INDICATES
 GOING UNDER A BAY DOOR.
  
 THERE NEEDS TO BE A BETTER PLAN OF VENTING TO THE
 OUTSIDE AND ONE THAT HELPS DISPERSE THE CO2 FROM
 NEIGBORING BUSINESSES.
  
  
 PLEASE PROVIDE DETAILS.
  
  
  
 2A) THERE DOES NOT APPEAR TO AN INDICATION OF THE
 VENTING MATERIAL AND HOW IT WILL BE SUPPORTED.
  
 PLEASE PROVIDE DETAILS.
  
  
  
 2B) THERE DOES NOT APPEAR TO BE ANY CO2 DETECTION
 DEVICES THROUGHOUT THE OCCUPANCY.
  
 AS A INDUSTRIAL THAT PRODUCES CO2 AS PART OF ITS
 PROCESSES CO2 DETECTION IS REQUIRED FOR LIFE SAFETY
 PURPOSES. INSTALLATION OF CO2 AND O2 ALARMS MAY BE
 REQUIRED.
  
 PLEASE REVIEW AND CORECT.
  
  
  
 2C) FOR CONFIRMATION PURPOSES, THERE DOES NOT APPEAR TO
 BE ANY CO2 STORAGE BOTTLES/CONTAINORS WITHIN IN THE
 OCCUPANCY THAT COULD BE USED DURING THE BREWING
 PROCESS.
  
 PLEASE CONFIRM THAT CO2 STORAGE TANKS WILL NOT BE USED.
  
  
  
  
 3) ELECTRICAL DEVICES/EQUIPMENT - IN BREWERIES THERE
 CAN BE COMBUSTIBLE DUST CREATED DUE TO SEVRAL PROCESSED
 THAT MAY ACCULMULATE ON SURFACES AND IN THE AIR.
  
 IT IS IMPORTANT TO HAVE INTRINSICALY SAFE ELCTRICAL
 DEVICES/EQUIPMENT IN THESE AREAS.
  
 PLEASE REVIEW AND PROVIDE PROPER ELECTRICAL EQUIPMENT.
  
 PER NFPA 654
 6.5 ELECTRICAL EQUIPMENT.
 6.5.1 ALL ELECTRICAL EQUIPMENT AND INSTALLATIONS SHALL
 COMPLY
 WITH THE REQUIREMENTS OF NFPA 70, NATIONAL ELECTRICAL
 CODE, OR
 NFPA 496, STANDARD FOR PURGED AND PRESSURIZED
 ENCLOSURES FOR ELECTRICAL
 EQUIPMENT.
 6.5.2* IN LOCAL AREAS OF A PLANT WHERE A HAZARDOUS
 QUANTITY OF
 DUST ACCUMULATES OR IS SUSPENDED IN AIR, THE AREA SHALL
 BE CLASSIFIED
 AND ALL ELECTRICAL EQUIPMENT AND INSTALLATIONS IN THOSE
 LOCAL AREAS SHALL COMPLY WITH ARTICLE 502 OR ARTICLE
 503 OF
 NFPA 70, NATIONAL ELECTRICAL CODE, AS APPLICABLE.
  
 I. GENERAL
 502.1 SCOPE. ARTICLE 502 COVERS THE REQUIREMENTS FOR
 ELECTRICAL
 AND ELECTRONIC EQUIPMENT AND WIRING FOR ALL VOLTAGES
 IN CLASS II, DIVISION 1 AND 2 LOCATIONS WHERE FIRE OR
 EXPLOSION
 HAZARDS MAY EXIST DUE TO COMBUSTIBLE DUST.
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  