2020-06-22 16:17:26 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| |
| |
| 1) SHEET LS .100 - THERE IS NO INDICATION OF WHETHER |
| THIS IS A MIXED OR SEPARATED OCCUPANCY. |
| |
| THERE IS AN INDICATION THAT THE ASEMBLY AREA IS |
| ACCESSORY; HOWEVER, PER NFPA 101, IT DOES NOT APPEAR TO |
| BE ACCESSORTY. |
| |
| PER NFPA 101 |
| |
| 6.1 CLASSIFICATION OF OCCUPANCY. |
| 6.1.1 GENERAL. |
| 6.1.1.1 OCCUPANCY CLASSIFICATION. THE OCCUPANCY OF A |
| BUILDING OR |
| STRUCTURE, OR PORTION OF A BUILDING OR STRUCTURE, SHALL |
| BE CLASSIFIED IN |
| ACCORDANCE WITH 6.1.2 THROUGH 6.1.13. OCCUPANCY |
| CLASSIFICATION SHALL BE |
| SUBJECT TO THE RULING OF THE AUTHORITY HAVING |
| JURISDICTION WHERE THERE IS A |
| QUESTION OF PROPER CLASSIFICATION IN ANY INDIVIDUAL |
| CASE. |
| |
| 6.1.14 MULTIPLE OCCUPANCIES. |
| 6.1.14.1 GENERAL. |
| 6.1.14.1.1 MULTIPLE OCCUPANCIES SHALL COMPLY WITH THE |
| REQUIREMENTS OF |
| 6.1.14.1 AND ONE OF THE FOLLOWING: |
| (1) MIXED OCCUPANCIES ? 6.1.14.3 |
| (2) SEPARATED OCCUPANCIES ? 6.1.14.4 |
| |
| 6.1.14.1.2 WHERE EXIT ACCESS FROM AN OCCUPANCY |
| TRAVERSES ANOTHER |
| OCCUPANCY, THE MULTIPLE OCCUPANCY SHALL BE TREATED AS A |
| MIXED |
| OCCUPANCY. |
| 6.1.14.1.3* WHERE INCIDENTAL TO ANOTHER OCCUPANCY, |
| AREAS USED AS |
| FOLLOWS SHALL BE PERMITTED TO BE CONSIDERED PART OF THE |
| PREDOMINANT |
| OCCUPANCY AND SHALL BE SUBJECT TO THE PROVISIONS OF THE |
| CODE THAT APPLY |
| TO THE PREDOMINANT OCCUPANCY: |
| (1) MERCANTILE, BUSINESS, INDUSTRIAL, OR STORAGE USE |
| (2) *NONRESIDENTIAL USE WITH AN OCCUPANT LOAD FEWER |
| THAN THAT |
| ESTABLISHED BY SECTION 6.1 FOR THE OCCUPANCY THRESHOLD |
| (3) PORTIONS OF BUILDINGS USED AS ACCESSORY OFFICES OR |
| FOR CUSTOMARY |
| NON-HAZARDOUS USES NECESSARY FOR TRANSACTING THE |
| PRINCIPAL |
| BUSINESS IN STORAGE AND INDUSTRIAL OCCUPANCIES NEED NOT |
| BE |
| SEPARATED FROM THE PRINCIPAL USE. |
| (4) INDUSTRIAL OCCUPANCIES PRODUCING, USING, OR STORING |
| LOW HAZARD |
| PRODUCTS IN ACCORDANCE WITH SUBDIVISION 6.2.2 NEED NOT |
| BE |
| SEPARATED BY FIRE-RESISTANT CONSTRUCTION FROM THE |
| OCCUPANCIES TO |
| WHICH THEY ARE ACCESSORY. |
| 6.1.14.1.3.1 INCIDENTAL USE AREAS SHALL BE SEPARATED AS |
| REQUIRED BY TABLE |
| 508.2.5 OF THE FLORIDA BUILDING CODE WHERE TABLE |
| 508.2.5 PERMITS AN |
| AUTOMATIC FIRE-EXTINGUISHING SYSTEM WITHOUT A FIRE |
| BARRIER, THE INCIDENTAL |
| USE AREA SHALL BE SEPARATED BY CONSTRUCTION CAPABLE OF |
| RESISTING THE |
| PASSAGE OF SMOKE. |
| 6.1.14.1.4 THE FOLLOWING ACCESSORY OCCUPANCIES SHALL |
| NOT BE REQUIRED TO |
| BE SEPARATED FROM THE PRIMARY OCCUPANCY AS REQUIRED IN |
| 6.1.14.4: |
| (1) A KITCHEN IN AN ASSEMBLY OCCUPANCY DOES NOT |
| CONSTITUTE A MIXED |
| OCCUPANCY. |
| (2) ACCESSORY USES IN INDUSTRIAL AND STORAGE |
| OCCUPANCIES AS OTHERWISE |
| PROVIDED IN 6.1.14.1.3(1) |
| (3) ROOMS OR SPACES USED FOR CUSTOMARY STORAGE OF |
| NON-HAZARDOUS |
| MATERIALS IN ASSEMBLY, BUSINESS, EDUCATIONAL, |
| INDUSTRIAL, |
| MERCANTILE, HOTEL AND DORMITORY, AND APARTMENT |
| OCCUPANCIES WHICH |
| IN AGGREGATE DO NOT EXCEED 10% OF THE MAJOR FLOOR AREA |
| IN WHICH |
| THEY ARE LOCATED. PROTECTION FROM HAZARDS SHALL BE AS |
| OTHERWISE |
| PROVIDED IN THE SPECIFIC OCCUPANCY CHAPTER |
| |
| |
| 6.2.1.3* FOR THE PURPOSE OF THIS CODE, WHERE DIFFERENT |
| DEGREES OF |
| HAZARD OF CONTENTS EXIST IN DIFFERENT PARTS OF A |
| BUILDING OR STRUCTURE, |
| THE MOST HAZARDOUS SHALL GOVERN THE CLASSIFICATION, |
| UNLESS |
| HAZARDOUS AREAS ARE SEPARATED OR PROTECTED AS SPECIFIED |
| IN SECTION |
| 8.7 AND THE APPLICABLE SECTIONS OF CHAPTERS 11 THROUGH |
| 43. |
| |
| |
| PLEASE REVIEW AND PROVIDE DETAILS AND FOR THE REQUIRED |
| SEPARATION. |
| |
| |
| |
| 1A) SHEET A.100 - THE TASTING ROOM APPEARS TO BE MORE |
| OF A BAR THAN A ROOM IS MORE THAN INCIDENTAL TO THE |
| OCCUPANCY. |
| |
| PER NFPA 101, TABLE 6.1.14.4.1(B) A 2 HOUR SEPARATION |
| IS REQUIRED |
| |
| 6.2.1.3* FOR THE PURPOSE OF THIS CODE, WHERE DIFFERENT |
| DEGREES OF |
| HAZARD OF CONTENTS EXIST IN DIFFERENT PARTS OF A |
| BUILDING OR STRUCTURE, |
| THE MOST HAZARDOUS SHALL GOVERN THE CLASSIFICATION, |
| UNLESS |
| HAZARDOUS AREAS ARE SEPARATED OR PROTECTED AS SPECIFIED |
| IN SECTION |
| 8.7 AND THE APPLICABLE SECTIONS OF CHAPTERS 11 THROUGH |
| 43. |
| |
| PLEASE REVIEW AND CORRECT. |
| |
| |
| |
| |
| 2) SHEET S 7 OF 8 - FERMENTOR CO2 VENT SYSTEM - THERE |
| IS AN INDICATION OF A VENTING SYSTEM THAT INDICATES |
| GOING UNDER A BAY DOOR. |
| |
| THERE NEEDS TO BE A BETTER PLAN OF VENTING TO THE |
| OUTSIDE AND ONE THAT HELPS DISPERSE THE CO2 FROM |
| NEIGBORING BUSINESSES. |
| |
| |
| PLEASE PROVIDE DETAILS. |
| |
| |
| |
| 2A) THERE DOES NOT APPEAR TO AN INDICATION OF THE |
| VENTING MATERIAL AND HOW IT WILL BE SUPPORTED. |
| |
| PLEASE PROVIDE DETAILS. |
| |
| |
| |
| 2B) THERE DOES NOT APPEAR TO BE ANY CO2 DETECTION |
| DEVICES THROUGHOUT THE OCCUPANCY. |
| |
| AS A INDUSTRIAL THAT PRODUCES CO2 AS PART OF ITS |
| PROCESSES CO2 DETECTION IS REQUIRED FOR LIFE SAFETY |
| PURPOSES. INSTALLATION OF CO2 AND O2 ALARMS MAY BE |
| REQUIRED. |
| |
| PLEASE REVIEW AND CORECT. |
| |
| |
| |
| 2C) FOR CONFIRMATION PURPOSES, THERE DOES NOT APPEAR TO |
| BE ANY CO2 STORAGE BOTTLES/CONTAINORS WITHIN IN THE |
| OCCUPANCY THAT COULD BE USED DURING THE BREWING |
| PROCESS. |
| |
| PLEASE CONFIRM THAT CO2 STORAGE TANKS WILL NOT BE USED. |
| |
| |
| |
| |
| 3) ELECTRICAL DEVICES/EQUIPMENT - IN BREWERIES THERE |
| CAN BE COMBUSTIBLE DUST CREATED DUE TO SEVRAL PROCESSED |
| THAT MAY ACCULMULATE ON SURFACES AND IN THE AIR. |
| |
| IT IS IMPORTANT TO HAVE INTRINSICALY SAFE ELCTRICAL |
| DEVICES/EQUIPMENT IN THESE AREAS. |
| |
| PLEASE REVIEW AND PROVIDE PROPER ELECTRICAL EQUIPMENT. |
| |
| PER NFPA 654 |
| 6.5 ELECTRICAL EQUIPMENT. |
| 6.5.1 ALL ELECTRICAL EQUIPMENT AND INSTALLATIONS SHALL |
| COMPLY |
| WITH THE REQUIREMENTS OF NFPA 70, NATIONAL ELECTRICAL |
| CODE, OR |
| NFPA 496, STANDARD FOR PURGED AND PRESSURIZED |
| ENCLOSURES FOR ELECTRICAL |
| EQUIPMENT. |
| 6.5.2* IN LOCAL AREAS OF A PLANT WHERE A HAZARDOUS |
| QUANTITY OF |
| DUST ACCUMULATES OR IS SUSPENDED IN AIR, THE AREA SHALL |
| BE CLASSIFIED |
| AND ALL ELECTRICAL EQUIPMENT AND INSTALLATIONS IN THOSE |
| LOCAL AREAS SHALL COMPLY WITH ARTICLE 502 OR ARTICLE |
| 503 OF |
| NFPA 70, NATIONAL ELECTRICAL CODE, AS APPLICABLE. |
| |
| I. GENERAL |
| 502.1 SCOPE. ARTICLE 502 COVERS THE REQUIREMENTS FOR |
| ELECTRICAL |
| AND ELECTRONIC EQUIPMENT AND WIRING FOR ALL VOLTAGES |
| IN CLASS II, DIVISION 1 AND 2 LOCATIONS WHERE FIRE OR |
| EXPLOSION |
| HAZARDS MAY EXIST DUE TO COMBUSTIBLE DUST. |
| |
| |
| |
| 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |