Plan Review Notes
Plan Review Notes For Permit 20060761
Permit Number 20060761
Review Stop B
Sequence Number 1
Notes
Date Text
2020-07-14 12:07:131ST REVIEW FBC-2017 BUILDING
 PERMIT- 20060761
 7/21/2020
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE PLANS THAT WERE SUBMITTED ONLY HAVE A FEW
 DIMENSIONS ON THEM. SUBMIT DRAWINGS WITH ALL DIMENSIONS
 SPECIFIED ON THEM. FBC 107.2.1
  
 2) SPECIFY THE EXISTING OCCUPANCY TYPE FOR THIS SPACE
 ON THE PLANS. FBC 107.2.1
  
 3) VERIFY THAT THE TENANT SEPARATION WALLS ON EACH SIDE
 OF THE SPACE ARE 2 HOUR FIRE RESISTIVE RATED. FBC 706
  
 4) THE TYPE OF CONSTRUCTION FOR THIS BUILDING IS
 SPECIFIED AS TYPE V ON SHEET LS.100. SPECIFY IF IT IS
 TYPE V-A OR V-B CONSTRUCTION. BASED ON MY RESEARCH THIS
 SPACE IS LOCATED IN A 14,400 SQUARE FOOT WAREHOUSE
 BUILDING. IT IS LOCATED IN BUILDING #4 IN A GROUP OF
 OTHER WAREHOUSE BUILDINGS. THE ORIGINAL OCCUPANCY WAS
 BUSINESS AND WAREHOUSE. IT DOES NOT APPEAR THAT THIS
 BUILDING IS TYPE V CONSTRUCTION. PLEASE VERIFY THE
 CONSTRUCTION TYPE. FBC 601
  
 5) ONE SHEET LS.100 YOU HAVE INCLUDED THE CELLAR AND
 BAR SERVICE AREAS WITH THE F-2 OCCUPANCY. IT APPEARS
 THAT THE BAR SERVICE AREA AND POSSIBLY THE CELLAR AREA
 SHOULD BE INCLUDED WITH THE A2 OCCUPANCY. PLEASE
 CLARIFY THE INTENDED USE OF THE CELLAR. EXPLAIN WHY THE
 BAR SERVICE AREA AND THE CELLAR SHOULD NOT BE PART OF
 THE ASSEMBLY AREA.
  
 6) THE SECTION THAT ALLOWS ASSEMBLY AREAS WITH AN
 OCCUPANT LOAD OF LESS THAN 50 PERSONS TO BE CLASSIFIED
 AS A GROUP B OCCUPANCY DOES NOT ALLOW THE OCCUPANT LOAD
 FOR THE ASSEMBLY AREA TO BE RECALCULATED USING THE
 OCCUPANT LOAD FACTOR FOR A BUSINESS OCCUPANCY. THE
 NUMBER OF OCCUPANTS STAYS THE SAME AS CALCULATED FOR AN
 ASSEMBLY AREA. PLEASE CORRECT. FBC 1004 & FBC 303.1.1
 SMALL BUILDINGS AND TENANT SPACES A BUILDING OR TENANT
 SPACE USED FOR ASSEMBLY PURPOSES WITH AN OCCUPANT LOAD
 OF LESS THAN 50 PERSONS SHALL BE CLASSIFIED AS A GROUP
 B OCCUPANCY.
  
 7) ON SHEET LS.100 IT IS STATED THAT THE ASSEMBLY
 OCCUPANCY IS ACCESSORY TO THE F-2 OCCUPANCY. FBC
 508.2.3 STATES THAT AGGREGATE ACCESSORY OCCUPANCIES
 SHALL NOT OCCUPY MORE THAN 10 PERCENT OF THE FLOOR AREA
 OF THE STORY IN WHICH THEY ARE LOCATED. SINCE THE FLOOR
 AREA OF THE ASSEMBLY AREAS IS MORE THAN 10 PERCENT THIS
 CAN NOT BE AN ACCESSORY OR ANCILLARY OCCUPANCY. THIS IS
 A MIXED USE OCCUPANCY. YOU WILL NEED TO DETERMINE IF IT
 WILL BE A NON-SEPARATED OCCUPANCY OR A SEPARATED
 OCCUPANCY PER FBC508.3 OR 508.4.
  
 8) ON SHEET LS.100 UNDER EGRESS REQUIREMENTS THE NUMBER
 OF REQUIRED EXITS SPECIFIES FBC 2014 SECTION 1021.2(2).
 PLEASE CORRECT THIS TO REFERENCE THE 2017 FBC AND THE
 APPROPRIATE SECTION.
  
 FLORIDA ACCESSIBILITY COMMENTS : THIS IS A CHANGE OF
 OCCUPANCY AND IS TREATED AS NEW CONSTRUCTION FOR THE
 APPLICATION OF ACCESSIBILITY REQUIREMENTS. FBC EXISTING
 BUILDING 1006.1 GENERAL. ACCESSIBILITY IN PORTIONS OF
 BUILDINGS UNDERGOING A CHANGE OF OCCUPANCY
 CLASSIFICATION SHALL COMPLY WITH THE PROVISIONS OF THE
 FLORIDA BUILDING CODE, ACCESSIBILITY.
  
 9) SHOW ACCESSIBLE PARKING SPACES, ACCESSIBLE ROUTE TO
 ACCESSIBLE ENTRANCE AND THROUGH PRIMARY SERVICE AREA.
 FBC - ACCESSIBILITY 206 AND 208
  
 10) SHOW THAT BATHROOMS MEET ACCESSIBILITY
 REQUIREMENTS. 603 TOILET AND BATHING ROOMS. 603.1
 GENERAL. TOILET AND BATHING ROOMS SHALL COMPLY WITH 603
  
 11) SHOW ACCESSIBLE AREAS AT THE BARS. FBC -
 ACCESSIBILITY 226.1 GENERAL. WHERE DINING SURFACES ARE
 PROVIDED FOR THE CONSUMPTION OF FOOD OR DRINK, AT LEAST
 5 PERCENT OF THE SEATING SPACES AND STANDING SPACES AT
 THE DINING SURFACES SHALL COMPLY WITH 902. IN ADDITION,
 WHERE WORK SURFACES ARE PROVIDED FOR USE BY OTHER THAN
 EMPLOYEES, AT LEAST 5 PERCENT SHALL COMPLY WITH 902.
  
 12) SHOW ACCESSIBLE SEATING DISPERSED THROUGHOUT
 TASTING AREAS. FBC - A 226.2 DISPERSION. DINING
 SURFACES AND WORK SURFACES REQUIRED TO COMPLY WITH 902
 SHALL BE DISPERSED THROUGHOUT THE SPACE OR FACILITY
 CONTAINING DINING SURFACES AND WORK SURFACES.
  
 13) SHOW THAT THE SALES/SERVICE COUNTER COMPLIES WITH
 ACCESSIBILITY. FBC - A 904.4 SALES AND SERVICE
 COUNTERS. SALES COUNTERS AND SERVICE COUNTERS SHALL
 COMPLY WITH 904.4.1 OR 904.4.2. THE ACCESSIBLE PORTION
 OF THE COUNTER TOP SHALL EXTEND THE SAME DEPTH AS THE
 SALES OR SERVICE COUNTER TOP.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
  