2020-08-04 09:57:22 | NOTE: |
| THIS REVIEW IS ONLY FOR THE SIGNATURE REVIEW. |
| CONTRACTOR NEEDS TO UPLOAD TO PROJECTDOX THE |
| INFORMATION REQUESTED BY THE PLANS EXAMINER FOR |
| BUILDING, ELECTRICAL AND GAS. |
| |
| SIGNATURE REVIEW COMMENTS: |
| 1-ENGINEER WHO SIGNED AND SEALED THE CONCRETE PAD |
| ENGINEERING IS NOT THE SAME ENGINEER WHO SIGNED/SEALED |
| THE ORIGINAL ENGINEERING SUBMITTED. SEC. 107.3 CITY |
| AMENDMENTS. |
| THERE ARE THERE TWO OPTIONS TO ADDRESS THIS ISSUE: |
| (1)SUBMIT ENGINEERING WITH ORIGINAL SEAL/SIGNATURE OF |
| THE ENGINEER WHO SIGNED THE ORIGINAL SUBMITTAL. OR |
| (2) UPLOAD TO PROJECTDOX NEW DOCUMENT SIGNED/SEALED BY |
| THE NEW ENGINEER FOR BUILDING REVIEW. |
| NOTE: IN ORDER TO EXPEDITE THE REVIEW PROCESS, IT IS |
| PREFERABLE TO DOWNLOAD THE NEW ENGINEERING WITH A |
| DIGITAL SIGNATURE. OTHERWISE, HARD COPY WITH ORIGINAL |
| SEAL/SIGNATURE IS REQUIRED. WE CAN USE THE ONE |
| SUBMITTED NOW IF IT MATCHES THE ONE THAT WAS DOWNLOADED |
| TO PROJECTDOX. |
| |
| 2- THE CONCRETE PAD ENGINEERING SUBMITTED DOESN'T MATCH |
| THE ORIGINAL ENGINEERING THAT WAS UPLOADED TO |
| PROJECTDOX. SEC. 107.3 CITY AMENDMENTS. |
| |
| PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| QUESTIONS REGARDING THESE COMMENTS, |