Plan Review Notes
Plan Review Notes For Permit 20060724
Permit Number 20060724
Review Stop G
Sequence Number 2
Notes
Date Text
2020-08-13 09:00:492ND REVIEW FBC-2017 MECHANICAL
 PERMIT-20060724
  
 CODES IN EFFECT:
  
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE INCLUDE THE GAS RISER DIAGRAM FOR THIS
 PROJECT. THIS RISER DIAGRAM SHOULD INCLUDE ANY EXISTING
 EQUIPMENT AND PIPING SIZES, BTU?S OF EXISTING EQUIPMENT
 ALONG WITH BTU?S OF THE NEW GENERATOR, LONGEST LENGTH
 TO THE MOST REMOTE APPLIANCE ON THE SYSTEM, SYSTEM
 OPERATING PRESSURE, ANY REGULATORS INSTALLED IN THE
 SYSTEM, SHUT OFF VALVES AT APPLIANCES, MUST ALSO
 INCLUDE THE PIPE MATERIAL AND SIZE WHERE THE CONNECTION
 IS MADE TO (TAP INTO) THE EXISTING GAS LINE.
  
 2) PLEASE SEE 1ST CYCLE REVIEWER COMMENTS ABOUT THE
 REGULATOR AND IDENTIFYING THE MODEL USE ON THE DOCUMENT
 SUBMITTED. PLEASE ALSO IDENTIFY THE INLET AND OUTLET
 PRESSURES OF THE SELECTED REGULATOR. FBC RES G2421.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  