2020-06-29 11:15:202017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20060703
 ADD: 1701 S. FLAGLER DR. # 506
 CONT: AOA CONSTRUCTION
 TEL: 561-660-3504
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. JUNE 29TH/ 2020
 ACTION: DENIED
  
 1) WIND CHART FROM ENGINEERING EXPRESS:
 1A) THE WIND CHART FORM ENGINEERING EXPRESS COULD NOT
 VERIFY THE DIGITAL SIGNATURE.
 61G15-23.005 PROCEDURES FOR SIGNING AND SEALING
 ELECTRONICALLY TRANSMITTED PLANS (DIGITAL SIGNATURES),
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
 FLORIDA ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A
 SCANNED, FACSIMILE, DIGITALLY CREATED OR COPIED IMAGE
 OF THE LICENSEE?S SIGNATURE SHALL NOT BE USED ON
 DIGITALLY SIGNED AND SEALED ENGINEERING PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 1B) THE SUBMITTED WIND CHART FROM ENGINEERING EXPRESS
 IS ONLY GOOD FOR BUILDINGS < (LESS THAN 60 FEET). THIS
 HIGHRISE IS APPROXIMATELY 230 FEET ABOVE GRADE. NOTE TO
 CONTRACTOR NEGATIVE PRESSURES FOR COMPONENTS AND
 CLADDING ARE ALWAYS TAKEN FROM THE MRH (MEAN ROOF
 HEIGHT). 2017 FBC-B TABLE 1609.7(2) ADJUSTMENT FACTORS
 FOR HEIGHT & EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR
 THE BUILDING.
 1C) ) THE SUBMITTED WIND CHART FROM ENGINEERING EXPRESS
 NEITHER ARE THE WALL ZONES IDENTIFIED ON THE SIDE
 ELEVATIONS AND ON THE PRESSURE CHARTS OPENING SIZES AND
 PRESSURES ARE NOT IDENTIFIED.
 2) THE SUBMITTED PRODUCT APPROVALS DIDN?T HAVE THE
 FOLLOWING INFORMATION IDENTIFIED. PLEASE IDENTIFY ON
 THE PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS.
 FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH
 INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM
 LOADS AND SPACING USED IN THE TESTS.
 3) PLEASE NOTE THE FOLLOWING 3 FILES WERE LOADED WRONG,
 FAILED TO OPEN:
 3.1) 1XFRVUM1.RJI
 3.2) JOOOE3PQP.WZH
 3.3) RBV4W5R5.PZN
 YOU MAY HAVE TO CONTACT THE PERMIT LIBRARIANS:
 LAURA MARCHANT 561-805-6658
 OR CAROLINA CARVAJAL 561-805-6690
  
 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  