2020-06-29 15:50:53PLAN REVIEW - FUEL GAS
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 RESIDENTIAL GENERATOR ? CHPT. 1 GAS
  
  
 1. A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE
 REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK.
 PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT
 SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE
 SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC.
 107.2.1.
  
 2. PROVIDE THE TOTAL BTU LOAD OF EXISTING GAS
 APPLIANCES - IF ANY. THE BTU LOAD OF THE PROPOSED GAS
 EQUIPMENT MUST BE ADDED INTO THE TOTAL BTU LOAD ON THE
 SYSTEM TO ENSURE THE EXISTING SYSTEM IS PROPERLY SIZED.
 IF UNDERSIZED, THE EXISTING SYSTEM MUST BE REDONE TO
 ENSURE A SAFE OPERATING SYSTEM. NOTE: IF THE EXISTING
 SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE SYSTEM
 PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE
 REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES.
 FGC SECS. 401.4, 401.8, 402.1, 402.2, 402.3 OR FBCR
 SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3.
  
 3. SUBMIT MANUFACTURERS SPECIFICATIONS AND INSTALLATION
 INSTRUCTIONS FOR ANY NEW PRESSURE REGULATORS.
 REGULATORS INSTALLED ON THE EXTERIOR OF THE BUILDING
 SHALL BE APPROVED FOR OUTDOOR INSTALLATION. IDENTIFY ON
 THE SPECIFICATION SHEETS WHICH MODEL REGULATOR IS BEING
 INSTALLED AND THE ORIFICE SIZE TO ENSURE THE REGULATOR
 CAN ACCOMMODATE THE BTU LOAD THROUGH THE REGULATOR.2017
 FGC SEC.410.1, 2017 FBC-RES. SEC. G2421.1.
  
 4. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE FOR THE NEW
 INSTALLATION PER 2017 FBC FUEL GAS RES SECS. G2413.4.1,
 G2413.4.2.
  
 5. SUBMIT A COPY OF THE APPLICABLE SIZING TABLES USED
 TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR ANOTHER STANDARD THAT WAS USED IN THE
 DESIGN OF THIS GAS SYSTEM.
  
 REFER TO THE 2017 FBC FUEL GAS RES. SEC. G2412.4,
 G2412.8, G2413.1, G2413.2, & G2413.3.
  
 6. PROVIDE MANUFACTURERS INSTALLATION INSTRUCTIONS.
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 7. PROVIDE A SITE PLAN - GENERATOR SHALL BE LOCATED
 THREE FEET FROM STRUCTURE.
 NFPA 37 ? 4.1.4
 EXHAUST GASES SHALL NOT BE LOCATED WITHIN 5 FEET OF ANY
 BUILDING OPENING OR COMBUSTIBLE CONSTRUCTION.
  
 8. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE FLEX
 CONNECTOR FOR THE GENERATOR. THE FLEX CONNECTOR SHALL
 BE APPROVED TO FLOW THE MAXIMUM BTU LOAD FOR THE
 GENERATOR. 2017 FBCR SEC. G2422.1 (8), 2017 FBC-FUEL
 GAS SEC. 411.1.3.2.
  
  
  
  