Plan Review Notes
Plan Review Notes For Permit 20060687
Permit Number 20060687
Review Stop P
Sequence Number 1
Notes
Date Text
2020-07-21 13:57:411ST REVIEW FBC-2017 RES. PLUMBING
 PERMIT- 20060687
 7/21/2020
  
 CODES IN EFFECT:
  
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE TOTAL DYNAMIC HEAD CALCULATIONS FOR THE
 MAXIMUM SYSTEM FLOW- SECTION R4501.7.3 FBC RES. THE
 MAXIMUM FLOW OF THE PUMP FROM ITS PUMP CURVE AND THE
 SIMPLIFIED TOTAL DYNAMIC HEAD CALCULATION IS NO LONGER
 ALLOWED TO BE USED IN DETERMINING MAXIMUM SYSTEM FLOW
 RATE PER ANSI/APSP/ICC 7- 2013 SECS. 4.4.9, 4.4.9.1.
 THE 2013 EDITION ADDRESSES FLOW RATE IN GALLONS PER
 MINUTE (GPM). IT REQUIRES THAT MAXIMUM SYSTEM FLOW RATE
 DOES NOT EXCEED THE LISTED MAXIMUM FLOW RATE OF THE
 SUCTION OUTLET FITTING ASSEMBLY (DRAIN COVER). THE TDH
 CALCULATIONS MUST INCLUDE ALL OF THE SYSTEM COMPONENTS
 INCLUDING SUCTION AND RETURN PIPING, FITTINGS, VALVES,
 HEATER, FILTER, AND CHLORINATOR.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  