Plan Review Notes
Plan Review Notes For Permit 20060671
Permit Number 20060671
Review Stop P
Sequence Number 1
Notes
Date Text
2020-07-27 15:26:211ST REVIEW FBC-2017 RES.
 PERMIT- 20060671
 7/27/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A3: SHOW THE DIMENSIONS OF THE SHOWER AND THE
 BATHTUB IN THE MASTER BATHROOM, AND THE DIMENSIONS OF
 THE SHOWER IN BATH 2- SECTION P2708.1 FBC RES.
  
 2) SHEET EP-1: THE PLUMBING RISER IS NOT CODE
 COMPLIANT.
 A) NO VENTS ARE SHOWN FOR THE MASTER BATH SHOWER AND
 TUB- SECTION P3101.2.1 FBC RES.
 B) THE MASTER BATH FIXTURES AND POWDER ROOM FIXTURES
 ARE NOT BEING PROPERLY VENTED- SEE SECTIONS P3108.1 &
 P3108.2.1 FBC RES. IN ORDER FOR THE TOILET TANK VENT TO
 SERVE AS THE DRY VENT FOR THE HORIZONTAL WET VENT
 SERVING THE TWO BATH GROUPS, IT MUST CONNECT
 HORIZONTALLY TO THE HORIZONTAL WET VENT- THE DRAWING
 SHOWS A VERTICAL CONNECTION. ADDITIONALLY, NOT MORE
 THAN ONE WET-VENTED FIXTURE DRAIN SHALL DISCHARGE
 UPSTREAM OF THE DRY-VENTED FIXTURE DRAIN CONNECTION-
 THE DRAWING SHOWS THREE BATH FIXTURES.
 C) ONLY THE FIXTURES WITHIN THE BATHROOM GROUPS SHALL
 CONNECT TO THE WET-VENTED HORIZONTAL BRANCH DRAIN. THE
 CLOTHES WASHING MACHINE FIXTURE DRAIN- P3108.1 SHALL
 DISCHARGE DOWNSTREAM OF THE HORIZONTAL WET VENT. PLEASE
 NOTE THAT THE 2? WASHING MACHINE DRAIN SHALL CONNECT TO
 A 3? FIXTURE BRANCH OR VERTICAL STACK- SECTION 406.2
 D) THE ISOMETRIC FOR BATH-2 SHOWS TWO FIXTURES
 DISCHARGING UPSTREAM OF THE DRY VENT AT THE LAVATORY-
 ONLY ONE FIXTURE IS ALLOWED TO DISCHARGE UPSTREAM-
 SECTION P3108.1.
  
 3) PROVIDE A WATER RISER DRAWING SHOWING THE WATER
 DISTRIBUTION PIPING RUNS INCLUDING THE TYPES AND SIZES
 OF PIPING, AND SHUT OFF VALVE LOCATIONS- SECTION
 107.3.5.3 WPB. PLEASE INCLUDE THE SUPPLY LINES TO THE
 DISHWASHER AND REFRIGERATOR ICE MAKER SHOWING THE
 REQUIRED BACKFLOW PREVENTERS AND WATER HAMMER
 ARRESTORS- SECTIONS P2717.1, P2902.1 P2903.5 FBC RES.
  
 4) PROVIDE A SHOWER PAN DETAIL- SECTIONS P2709.1 &
 P2709.2 FBC RES.
  
 5) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR:
 A) WATER HEATER- SECTION P2801.3 FBC RES.
 B) SHOWER AND BATHTUB VALVES- SECTIONS P2708.4 &
 P2713.3.
 C) IN-WALL TANK TOILET- SECTION P2712.1.
  
 6) PLEASE NOTE A SEPARATE PERMIT AND PLANS ARE REQUIRED
 FOR THE GAS PIPING INSTALLATIONS TO THE WATER HEATER,
 DRYER, AND RANGE- SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  