Date |
Text |
2020-07-27 15:26:21 | 1ST REVIEW FBC-2017 RES. |
| PERMIT- 20060671 |
| 7/27/2020 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET A3: SHOW THE DIMENSIONS OF THE SHOWER AND THE |
| BATHTUB IN THE MASTER BATHROOM, AND THE DIMENSIONS OF |
| THE SHOWER IN BATH 2- SECTION P2708.1 FBC RES. |
| |
| 2) SHEET EP-1: THE PLUMBING RISER IS NOT CODE |
| COMPLIANT. |
| A) NO VENTS ARE SHOWN FOR THE MASTER BATH SHOWER AND |
| TUB- SECTION P3101.2.1 FBC RES. |
| B) THE MASTER BATH FIXTURES AND POWDER ROOM FIXTURES |
| ARE NOT BEING PROPERLY VENTED- SEE SECTIONS P3108.1 & |
| P3108.2.1 FBC RES. IN ORDER FOR THE TOILET TANK VENT TO |
| SERVE AS THE DRY VENT FOR THE HORIZONTAL WET VENT |
| SERVING THE TWO BATH GROUPS, IT MUST CONNECT |
| HORIZONTALLY TO THE HORIZONTAL WET VENT- THE DRAWING |
| SHOWS A VERTICAL CONNECTION. ADDITIONALLY, NOT MORE |
| THAN ONE WET-VENTED FIXTURE DRAIN SHALL DISCHARGE |
| UPSTREAM OF THE DRY-VENTED FIXTURE DRAIN CONNECTION- |
| THE DRAWING SHOWS THREE BATH FIXTURES. |
| C) ONLY THE FIXTURES WITHIN THE BATHROOM GROUPS SHALL |
| CONNECT TO THE WET-VENTED HORIZONTAL BRANCH DRAIN. THE |
| CLOTHES WASHING MACHINE FIXTURE DRAIN- P3108.1 SHALL |
| DISCHARGE DOWNSTREAM OF THE HORIZONTAL WET VENT. PLEASE |
| NOTE THAT THE 2? WASHING MACHINE DRAIN SHALL CONNECT TO |
| A 3? FIXTURE BRANCH OR VERTICAL STACK- SECTION 406.2 |
| D) THE ISOMETRIC FOR BATH-2 SHOWS TWO FIXTURES |
| DISCHARGING UPSTREAM OF THE DRY VENT AT THE LAVATORY- |
| ONLY ONE FIXTURE IS ALLOWED TO DISCHARGE UPSTREAM- |
| SECTION P3108.1. |
| |
| 3) PROVIDE A WATER RISER DRAWING SHOWING THE WATER |
| DISTRIBUTION PIPING RUNS INCLUDING THE TYPES AND SIZES |
| OF PIPING, AND SHUT OFF VALVE LOCATIONS- SECTION |
| 107.3.5.3 WPB. PLEASE INCLUDE THE SUPPLY LINES TO THE |
| DISHWASHER AND REFRIGERATOR ICE MAKER SHOWING THE |
| REQUIRED BACKFLOW PREVENTERS AND WATER HAMMER |
| ARRESTORS- SECTIONS P2717.1, P2902.1 P2903.5 FBC RES. |
| |
| 4) PROVIDE A SHOWER PAN DETAIL- SECTIONS P2709.1 & |
| P2709.2 FBC RES. |
| |
| 5) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR: |
| A) WATER HEATER- SECTION P2801.3 FBC RES. |
| B) SHOWER AND BATHTUB VALVES- SECTIONS P2708.4 & |
| P2713.3. |
| C) IN-WALL TANK TOILET- SECTION P2712.1. |
| |
| 6) PLEASE NOTE A SEPARATE PERMIT AND PLANS ARE REQUIRED |
| FOR THE GAS PIPING INSTALLATIONS TO THE WATER HEATER, |
| DRYER, AND RANGE- SECTION 107.2.1 WPB. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL/PLUMBING PLANS EXAMINER |
| 401 CLEMATIS STREET |
| WEST PALM BEACH FL 33401 |
| 561-805-6719 |
| [email protected] |
| |