2020-07-29 20:34:41 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. HOW IS THERE AN EXISTING SERVICE ON A NEW HOUSE? IS |
| IT A REMODEL OR NEW HOUSE? FBC 107.2.1 |
| |
| 2. NO METER SHOWN ON RISER DIAGRAM FBC 107.2.1 NEC220 |
| |
| 3. NO WIRE SIZES SHOWN ON RISER DIAGRAM FBC 107.2.1 |
| |
| 4. ELEC NOTE #3 IS INCORRECT. CARBON MONOXIDE ALARMS |
| ARE NOT REQURED IN ALL SLEEPING AREAS. SMOKE ALARMS ARE |
| REQUIRED IN ALL SLEEPPING AREAS AND COMBO SMOKE/CARBON |
| ALARMS ARE REQUIRED WITHIN 10? IMMEDIATELY OUTSIDE OF |
| ALL SLEEPING AREAS. PROVIDE CORRECTION. FBC-R 314 &315 |
| |
| 5. NOTE 18 IS INCORRECT. SMOKE ALARMS MUST BE 36?? |
| INCHES AWAY FROM ANY A/C SUPPLYS? BATHROOM DOORS OR |
| TIPS OF FAN BLADES. PROVIDE CORRECTION. NFPA 72 |
| |
| 6. PPROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE |
| LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF |
| THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE. |
| FBC EC R404.1 |
| |
| 7. SHOW WIRE SIZES FOR GEC SYSTEM FBC 107.2.1 |
| |
| 8. 240 GENERATOR NOTE SHOWN ON PLAN. GENERATOR WILL |
| REQUIRES SEPARATE PLAN AND PERMIT. PUT NOTE ON PLAN |
| SAYING GENERATOR REQUIRES SEPARRATE PERMIT. FBC 107.2.1 |
| FBC 105.1 |
| |
| 9. BEDROOM ADJACENT TO KITCHEN NEEDS RECEPTACLE WITHIN |
| 6? OF DOOR NEC 210.52 |
| |
| 10. GARAGE DOOR RECEPTACLE MUST BE GFCI NEC 210.8 |
| |
| 11. $78,000 VALUE IS LOW FOR AMOUNT OF WORK SHOWN |
| |
| CITY ORDINANCE AND FBC 109.3 BUILDING PERMIT |
| VALUATIONS. IF, IN THE OPINION OF THE BUILDING |
| OFFICIAL, THE CLAIMED VALUATION OF BUILDING, |
| ALTERATION, STRUCTURE, ELECTRICAL, GAS, MECHANICAL OR |
| PLUMBING SYSTEMS APPEARS TO BE UNDERESTIMATED ON THE |
| APPLICATION, THE PERMIT SHALL BE DENIED, UNLESS THE |
| APPLICANT CAN SHOW DETAILED, QUANTITY ESTIMATES, AND/OR |
| BONA FIDE SIGNED CONTRACTS (EXCLUDING LAND VALUE) TO |
| MEET THE APPROVAL OF THE BUILDING OFFICIAL. FOR |
| PERMITTING PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS |
| SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, |
| ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, |
| RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, |
| MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY |
| LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST |
| PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS |
| SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY |
| INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT |
| VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. |
| |
| 12. PLAN MUST BE SIGNED BY ELECTRICAL CONTRACTOR |
| QUALIFIER OR DIGITALLY SIGNED BY DESIGN PROFESSIONAL . |
| FS 471.003(2)(H); 471.025; WPB FBC 107.1 |
| |
| 13. NO DESCRIPTION OF WORK IS LISTED IN PERMIT |
| APPLICATION FBC 107.2.1 |
| |
| 14. SQUARE FOOTAGE FOR HOUSE IN LOAD CALC IS 1360 BUT |
| SQUARE FOOTAGE ON PERMIT APP SAY 1976.. PROVIIDE |
| ACCURATE LOAD CALC TO INCLUDE ALL LOADS. NEC 220 FBC |
| 107.2.1 |
| |
| 15. RECEPTACLE REQURIED OUTSIDE ON FRONT OF HOME NEC |
| 210.52E1 |
| |
| 16. 200AMP PANEL NOT SHOWN ON PLAN ONLY METER AND SUB |
| PANEL?? FBC 107.2.1 |
| |
| 17. PUT NOTE ON PLAN THAT LOW VOLTAGE WILL BE A |
| SEPARATE PERMIT. FBC 105.1 107.2.1 |
| |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| CODES IN EFFECT: |
| |
| IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN |
| PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE |
| 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A |
| COMPLETED RESUBMITTAL FORM, VIA EMAIL TO |
| [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT |
| NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE |
| RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE: |
| |
| HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| UILDING-PERMIT-FORMS |
| |
| |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE 2017 6TH ED. |
| FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |