Plan Review Notes
Plan Review Notes For Permit 20060671
Permit Number 20060671
Review Stop E
Sequence Number 1
Notes
Date Text
2020-07-29 20:34:41ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. HOW IS THERE AN EXISTING SERVICE ON A NEW HOUSE? IS
 IT A REMODEL OR NEW HOUSE? FBC 107.2.1
  
 2. NO METER SHOWN ON RISER DIAGRAM FBC 107.2.1 NEC220
  
 3. NO WIRE SIZES SHOWN ON RISER DIAGRAM FBC 107.2.1
  
 4. ELEC NOTE #3 IS INCORRECT. CARBON MONOXIDE ALARMS
 ARE NOT REQURED IN ALL SLEEPING AREAS. SMOKE ALARMS ARE
 REQUIRED IN ALL SLEEPPING AREAS AND COMBO SMOKE/CARBON
 ALARMS ARE REQUIRED WITHIN 10? IMMEDIATELY OUTSIDE OF
 ALL SLEEPING AREAS. PROVIDE CORRECTION. FBC-R 314 &315
  
 5. NOTE 18 IS INCORRECT. SMOKE ALARMS MUST BE 36??
 INCHES AWAY FROM ANY A/C SUPPLYS? BATHROOM DOORS OR
 TIPS OF FAN BLADES. PROVIDE CORRECTION. NFPA 72
  
 6. PPROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC EC R404.1
  
 7. SHOW WIRE SIZES FOR GEC SYSTEM FBC 107.2.1
  
 8. 240 GENERATOR NOTE SHOWN ON PLAN. GENERATOR WILL
 REQUIRES SEPARATE PLAN AND PERMIT. PUT NOTE ON PLAN
 SAYING GENERATOR REQUIRES SEPARRATE PERMIT. FBC 107.2.1
 FBC 105.1
  
 9. BEDROOM ADJACENT TO KITCHEN NEEDS RECEPTACLE WITHIN
 6? OF DOOR NEC 210.52
  
 10. GARAGE DOOR RECEPTACLE MUST BE GFCI NEC 210.8
  
 11. $78,000 VALUE IS LOW FOR AMOUNT OF WORK SHOWN
  
 CITY ORDINANCE AND FBC 109.3 BUILDING PERMIT
 VALUATIONS. IF, IN THE OPINION OF THE BUILDING
 OFFICIAL, THE CLAIMED VALUATION OF BUILDING,
 ALTERATION, STRUCTURE, ELECTRICAL, GAS, MECHANICAL OR
 PLUMBING SYSTEMS APPEARS TO BE UNDERESTIMATED ON THE
 APPLICATION, THE PERMIT SHALL BE DENIED, UNLESS THE
 APPLICANT CAN SHOW DETAILED, QUANTITY ESTIMATES, AND/OR
 BONA FIDE SIGNED CONTRACTS (EXCLUDING LAND VALUE) TO
 MEET THE APPROVAL OF THE BUILDING OFFICIAL. FOR
 PERMITTING PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS
 SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 12. PLAN MUST BE SIGNED BY ELECTRICAL CONTRACTOR
 QUALIFIER OR DIGITALLY SIGNED BY DESIGN PROFESSIONAL .
 FS 471.003(2)(H); 471.025; WPB FBC 107.1
  
 13. NO DESCRIPTION OF WORK IS LISTED IN PERMIT
 APPLICATION FBC 107.2.1
  
 14. SQUARE FOOTAGE FOR HOUSE IN LOAD CALC IS 1360 BUT
 SQUARE FOOTAGE ON PERMIT APP SAY 1976.. PROVIIDE
 ACCURATE LOAD CALC TO INCLUDE ALL LOADS. NEC 220 FBC
 107.2.1
  
 15. RECEPTACLE REQURIED OUTSIDE ON FRONT OF HOME NEC
 210.52E1
  
 16. 200AMP PANEL NOT SHOWN ON PLAN ONLY METER AND SUB
 PANEL?? FBC 107.2.1
  
 17. PUT NOTE ON PLAN THAT LOW VOLTAGE WILL BE A
 SEPARATE PERMIT. FBC 105.1 107.2.1
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  