2020-06-19 07:28:2206/19/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. DOCUMENTATION THAT THE PROPOSED DEVICE IS LEAD-FREE.
 ON PAGE THREE IT SAYS ONLY THE TEST COCKS ARE LEAD FREE
 AS IT MUST SAY 300LF ON THE FIRST PAGE OR STATE .025
 LEAD FREE (SEE BELOW), THIS SPECS MAY NOT BE THE UPDATE
 VERSION OR THIS DEVICE MAY NOT BE APPROVED BY UTILITIES
 AS THE RUN THE CROSS CONNECTION PROGRAM IN WEST PALM
 BEACH.
  
 EXAMPLE
  
 LEAD PLUMBING LAW COMPLIANCE
  
 (CA H&S CODE ?116875, VSA ?2470H)
  
 *(0.25% MAX. WEIGHTED AVERAGE LEAD CONTENT)
  
 ? LEAD PLUMBING LAW CERTIFIED BY IAPMO R&T
  
 ? ANNEX G CERTIFIED BY NSF INTERNATIONAL
  