Plan Review Notes For Permit 20060619 |
Permit Number |
20060619 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2020-06-24 10:15:14 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | THE COMMENT WAS NOT ADDRESSED. THE HANDRAIL EXTENSION | | IS REQUIRED TO BE IN THE SAME DIRECTION AS THE STAIRS. | | FBC ACCESSIBILITY SECTION 505.10 | | 1) THE STAIR PLAN VIEW #5 OF THE 5TH LEVEL ON SHEET | | SD-01 DOES NOT APPEAR TO SHOW COMPLIANCE WITH FBC | | ACCESSIBILITY SECTION 505.10.2 FOR THE HANDRAIL | | EXTENSION AT THE TOP OF THE STAIRS. THE HANDRAIL IS | | REQUIRED TO EXTEND HORIZONTALLY FOR 12 INCHES BEGINNING | | DIRECTLY ABOVE THE FIRST RISER NOSING. THE DRAWING | | APPEARS TO SHOW THE HANDRAIL MAKING A 90 DEGREE TURN | | AND EXTENDING FOR 12" PERPENDICULAR TO THE STAIRS. |
|