2020-06-17 09:39:36PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE STAIR PLAN VIEW #5 OF THE 5TH LEVEL ON SHEET
 SD-01 DOES NOT APPEAR TO SHOW COMPLIANCE WITH FBC
 ACCESSIBILITY SECTION 505.10.2 FOR THE HANDRAIL
 EXTENSION AT THE TOP OF THE STAIRS. THE HANDRAIL IS
 REQUIRED TO EXTEND HORIZONTALLY FOR 12 INCHES BEGINNING
 DIRECTLY ABOVE THE FIRST RISER NOSING. THE DRAWING
 APPEARS TO SHOW THE HANDRAIL MAKING A 90 DEGREE TURN
 AND EXTENDING FOR 12" PERPENDICULAR TO THE STAIRS.