Plan Review Notes For Permit 20060615 |
Permit Number |
20060615 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-06-16 17:10:12 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE STAIR #1 AND # 2 PLAN VIEWS ON SHEET SD-01 DO | | NOT APPEAR TO SHOW COMPLIANCE WITH FBC ACCESSIBILITY | | SECTION 505.10.3 FOR THE HANDRAIL EXTENSION AT THE | | BOTTOM OF THE STAIRS. THE HANDRAIL IS REQUIRED TO | | EXTEND AT THE SLOPE OF THE STAIR FLIGHT FOR A | | HORIZONTAL DISTANCE EQUAL TO ONE TREAD DEPTH BEYOND THE | | LAST RISER NOSING. IT CAN THEN RETURN TO A GUARD, A | | WALL OR THE LANDING. THE DRAWING APPEARS TO SHOW THE | | HANDRAIL MAKING A 90 DEGREE TURN AND EXTENDING FOR 12" | | PERPENDICULAR TO THE STAIRS. |
|