Plan Review Notes
Plan Review Notes For Permit 20060583
Permit Number 20060583
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2020-06-10 15:07:22THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS NO PROPSED SEATING PLAN INDICATED IN THE
 OPEN SPACES AND THE ROADWAYS.
  
 A SEATING PLAN IS REQUIRED FOR OCCUPANCY LOAD AND
 EGRESS WIDTHS.
  
  
  
 2) THERE IS AN INDICATION OF PROPOSED SEATING WITHIN
 THE ROADWAYS.
  
 FIRE DEPARTMENT VEHICLE ACCESS IS REQUIRED AND SHALL BE
 A MINIMUM OF 15' WIDE.
  
 SEATING CAN'T BE WITHIN APPROX. 50' OF AN INTERSECTION
 FOR FD VEHICLE TURNING RADIUS.
  
 PLEASE PROVIDE A PROPOSED PLAN WITHIN THE REQUIRMENTS
 OF ABOVE.
  
 ONCE INSTALLED, A FD VEHICLE WILL ASSIGNED TO NAVIGATE
 TO ENSURE PROPOER DIMENSIONS.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  