Plan Review Notes For Permit 20060558 |
Permit Number |
20060558 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-06-29 15:17:23 | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 | | 5TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION, | | PART VIII ELECTRICAL | | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | NFPA 70 2014 EDITION | | | | JAKE LEAHY BN, BU, PX | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | KITCHEN LAYOUT SHOWS PANEL NEXT TO THE REFRIGERATOR, IS | | PANEL FACING INTO THE KITCHEN? IF SO THIS IS A | | VIOLATION OF 110.26 | | | | E3405.1WORKING SPACE AND CLEARANCES. | | ACCESS AND WORKING SPACE SHALL BE PROVIDED AND | | MAINTAINED AROUND ALL ELECTRICAL EQUIPMENT TO PERMIT | | READY AND SAFE OPERATION AND MAINTENANCE OF SUCH | | EQUIPMENT IN ACCORDANCE WITH THIS SECTION AND FIGURE | | E3405.1. (110.26) 30" WIDE AND 36" DEEP | | | | |
|