Plan Review Notes For Permit 20060547
Permit Number 20060547
Review Stop B
Sequence Number 3
Notes
Date Text
2020-07-20 14:25:28ROOFING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) NEW TARCO W-3 DOCUMENTS PROVIDED = ROOFING SYSTEM TO
 BE USED ON THE PROVIDED PRODUCT APPROVAL (W3 AS
 HIGHLITED) REQUIRES ADDITIONAL SIGNED AND SEALED
 ATTACHMENT DETAILS FROM AN ARCHITECT OR ENGINEER FOR
 ROOF WIND ZONES 2 AND 3 WHICH REQUIRE A HIGHER PRESSURE
 THAN THE MAXIMUM SHOWN ON THE PRODUCT APPROVAL (-60) -
 SEE NOTE NUMBER 4 ON THE PRODUCT APPROVAL. SIGNED AND
 SEALED DRAWINGS OR DOCUMENTS WILL NEED TO BE DIGITALLY
 SIGNED AND SEALED TO BE USED IN ELECTRONIC PLAN REVIEW.
 SHOW THE WIND DESIGN DATA USED PER 2017 FBC AND ASCE
 7-10 - WIND SPEED - EXPOSURE - RISK CATEGORY - ETC.
 SEE FBC R301.1