Plan Review Notes For Permit 20060547 |
Permit Number |
20060547 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2020-07-20 14:25:28 | ROOFING | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected]. | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | AMENDMENTS | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | 1) NEW TARCO W-3 DOCUMENTS PROVIDED = ROOFING SYSTEM TO | | BE USED ON THE PROVIDED PRODUCT APPROVAL (W3 AS | | HIGHLITED) REQUIRES ADDITIONAL SIGNED AND SEALED | | ATTACHMENT DETAILS FROM AN ARCHITECT OR ENGINEER FOR | | ROOF WIND ZONES 2 AND 3 WHICH REQUIRE A HIGHER PRESSURE | | THAN THE MAXIMUM SHOWN ON THE PRODUCT APPROVAL (-60) - | | SEE NOTE NUMBER 4 ON THE PRODUCT APPROVAL. SIGNED AND | | SEALED DRAWINGS OR DOCUMENTS WILL NEED TO BE DIGITALLY | | SIGNED AND SEALED TO BE USED IN ELECTRONIC PLAN REVIEW. | | SHOW THE WIND DESIGN DATA USED PER 2017 FBC AND ASCE | | 7-10 - WIND SPEED - EXPOSURE - RISK CATEGORY - ETC. | | SEE FBC R301.1 |
|