2020-07-14 13:14:44ROOFING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) NEW TARCO W-3 DOCUMENTS PROVIDED = ROOFING SYSTEM TO
 BE USED ON THE PROVIDED PRODUCT APPROVAL REQUIRES
 ADDITIONAL SIGNED AND SEALED ATTACHMENT DETAILS FROM AN
 ARCHITECT OR ENGINEER FOR ROOF WIND ZONES 2 AND 3 WHICH
 REQUIRE A HIGHER PRESSURE THAN THE MAXIMUM SHOWN ON THE
 PRODUCT APPROVAL (-60) - SEE NOTE NUMBER 4 ON THE
 PRODUCT APPROVAL. SIGNED AND SEALED DRAWINGS OR
 DOCUMENTS WILL NEED TO BE DIGITALLY SIGNED AND SEALED
 TO BE USED IN ELECTRONIC PLAN REVIEW. SHOW THE WIND
 DESIGN DATA USED PER 2017 FBC AND ASCE 7-10 - WIND
 SPEED - EXPOSURE - RISK CATEGORY - ETC.
 2) PLEASE PROVIDE THE FRONT PAGES FOR THE FLORIDA STATE
 PRODUCT APPROVAL (THE INSTALLATION INSTRUCTIONS ARE
 PROVIDED - FOR TARCO W-3)
  
  