Plan Review Notes For Permit 20060547 |
Permit Number |
20060547 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-06-17 11:01:52 | ROOFING | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | 1) ROOFING SYSTEM TO BE USED ON THE PROVIDED PRODUCT | | APPROVAL REQUIRES ADDITIONAL SIGNED AND SEALED | | ATTACHMENT DETAILS FROM AN ARCHITECT OR ENGINEER FOR | | ROOF WIND ZONES 2 AND 3 WHICH REQUIRE A HIGHER PRESSURE | | THAN THE MAXIMUM SHOWN ON THE PRODUCT APPROVAL (-60) - | | SEE GEMERAL LIMITATION NOTE NUMBER 7 ON THE PRODUCT | | APPROVAL. SIGNED AND SEALED DRAWINGS OR DOCUMENTS WILL | | NEED TO BE DIGITALLY SIGNED AND SEALED TO BE USED IN | | ELECTRONIC PLAN REVIEW. SHOW THE WIND DESIGN DATA USED | | PER 2017 FBC AND ASCE 7-10 - WIND SPEED - EXPOSURE - | | RISK CATEGORY - ETC. | | | | FYI = ENGINEER CANNOT SELF-CERTIFY THE DIGITAL | | SIGNATURE | | 668.003(2) AND (3), F.S. | | (2) A PROFESSIONAL ENGINEER UTILIZING A DIGITAL | | SIGNATURE TO ELECTRONICALLY SIGN AND SEAL ENGINEERING | | PLANS, | | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS SHALL HAVE | | THEIR IDENTITY AUTHENTICATED BY A CERTIFICATION | | AUTHORITY. | | |
|