Plan Review Notes For Permit 20060478 |
Permit Number |
20060478 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-07-01 10:23:46 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE PREFAB GENERATOR PAD DRAWING IS REQUIRED TO HAVE | | THE ENGINEER'S DIGITAL SIGNATURE. FS 71 AND FAC 61G15 | | | | 2) THE PREFAB GENERATOR PAD DRAWING SPECIFIES THE WIND | | LOAD PRESSURE CAPACITY OF A SPECIFIC GENERATOR AND THE | | PAD. THE REQUIRED WIND LOAD PRESSURES FOR THE LOCATION | | IS NOT PROVIDED. THE ENGINEERING THAT WAS SUBMITTED | | REQUIRES SITE SPECIFIC ENGINEERING TO DETERMINE THE | | WIND LOAD PRESSURES REQUIRED AT THE LOCATION OF THE | | PROJECT. FBC 107 |
|