Plan Review Notes
Plan Review Notes For Permit 20060456
Permit Number 20060456
Review Stop P
Sequence Number 3
Notes
Date Text
2020-10-23 13:32:113RD REVIEW FBC-2017 PLUMBING
 PERMIT- 20060456
 10/23/2020
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
 COMMENTS FROM THE 1ST REVIEW WILL BE MARKED AS PASSED
 OR FAILED. I HAVE ADDED NOTES TO FAILED COMMENTS FOR
 FUTHER CLARIFICATION.
  
 1) PASSED. SHEET P1: THE SINK FIXTURE DRAIN MUST
 CONNECT TO THE 3" BUILDING DRAIN DOWNSTREAM OF THE WC
 AND LAVATORY PER SECTIONS 912.1 AND 912.2.1 FBC P.
  
 2) FAILED P1: PROVIDE A WATER RISER DRAWING SHOWING
 PIPE SIZES, LOCATIONS OF SHUTOFF VALVES, WATER HAMMER
 ARRESTORS, MIXING VALVES ETC.- SECTION 107.3.5.1.3 WPB
 AMENDMENTS TO THE FBC.
 A) FULL OPEN SHUT OFF VALVES ARE REQUIRED AT THE BASES
 OF THE WATER RISERS UP TO THE SECOND FLOOR- SECTION
 606.1(4) FBC P.
 B) IT APPEARS THAT THE DISTANCE FROM THE WATER HEATER
 TO THE MOST REMOTE FIXTURE BEING SUPPLIED WITH HOT
 WATER EXCEEDS THE MAXIMUM 50 FT DISTANCE. PLEASE VERIFY
 COMPLIANCE WITH SECTION 607.2
  
 3) FAILED. P1: PROVIDE A PLUMBING FIXTURE AND DEVICE
 SCHEDULE- SECTION 107.2.1 WPB & SECTION 405.9 FBC P.
 SCHEDULES NOT PROVIDED. PLEASE NOTE THAT THE SPEC
 SHEETS SUBMITTED ARE FOR NON- ADA COMPLIANT FIXTURES
 EXCEPT FOR THE LAVATORY FAUCET WHICH MEETS THE
 STANDARDS. THE SUBMITTALS FOR FIXTURES AND DEVICES MAY
 BE DEFERRED AND BE ONSITE IF PREFERRED, HOWEVER IT
 WOULD BE HELPFUL TO PROVIDE A LIST OF DEFERRED
 SUBMITTALS ON THE PLANS.
  
 4) FAILED P1: PROVIDE PLUMBING FIXTURE CALCULATIONS FOR
 THE PROPOSED ALTERATIONS PER TABLE 403.3 FBC P. PROVIDE
 A SCHEDULE INDICATING THE REQUIRED AND PROVIDED
 PLUMBING FIXTURES. PLEASE NOTE THAT THE PLAN DOES NOT
 INDICATE DRINKING FOUNTAINS, OR A SERVICE SINK ARE
 EITHER EXISTING OR PROPOSED. REFER TO SECTION 211.1-
 211.3 FBC ACC FOR ACCESSIBLE DRINKING FOUNTAIN
 REQUIREMENTS. REVISE THE PLANS TO SHOW COMPLIANCE.
 A) BUSINESS OCCUPANCIES ARE CALCULATED AT 100 GROSS PER
 SQ. FT. NOT 150- TABLE 1004.1.2 FBC B. THE CALCULATION
 RESULTS IN 27 OCCUPANTS.
 B) EXCEPTION #4 UNDER SECTION 403.2 DOES NOT EXIST.
 ACCORDING TO SECTION 403.2 EXCEPTION #2- SEPARATE
 FACILITIES ARE NOT REQUIRED IN STRUCTURES AND TENANT
 SPACES WITH A TOTAL OCCUPANT LOAD OF 15 OR FEWER,
 THEREFORE SEPARATE FACILITIES ARE REQUIRED FOR MALE AND
 FEMALE USE. THE CODE DOES ALLOW THE ROOMS TO BE
 DESIGNATED AS UNISEX- SECTION 403.2.1. CORRECT THE
 SCHEDULE TO SHOW 2 WATER CLOSET AND 2 LAVATORIES ARE
 REQUIRED. PLEASE NOTE THAT EACH OF THESE TOILET ROOMS
 THAT ARE BEING CONSTRUCTED OR ALTERED SHALL BE DESIGNED
 AS ACCESSIBLE- SECTION 213.1 FBC ACC.
  
 5) PASSED P1: INDICATE HOW TEMPERED WATER WILL BE
 PROVIDED TO THE LAVATORY- SECTION 416.5 FBC P. REFER TO
 COMMENT #3 DEFERRED SUBMITTAL. IT WILL BE HELPFUL TO
 NOTE ON THE PLAN THE REQUIRED ASSE 1070 LISTING
 STANDARD FOR THE DEVICES-SSECTION 607.1.2.
  
 6) FAILED. A4: ACCESSIBILITY CORRECTIONS- FBC ACC:
 PLEASE NOTE THAT BOTH RESTROOMS 1 & 2 NEED TO MEET
 COMPLIANCE HOWEVER THE PLANS INDICATE ONLY RESTROOM 1
 IS BEING MADE ACCESSIBLE- SECTION 213.1 FBC ACC. ITEMS
 A- J BELOW PASSED FOR RESTROOM 1 ONLY.
  
 A) LENGTH OF THE LAVATORY CLEAR FLOOR SPACE NOT SHOWN-
 SECTION 606.2 AND 305.
 B) HEIGHT TO THE TOP OF THE WATER CLOSET SEAT FROM THE
 FINISHED FLOOR INDICATED AT 20"- SECTION 604.4
 C) THE SIDE GRAB BAR AT THE WATER CLOSET SHALL EXTEND
 MINIMUM 54" FROM THE REAR WALL- FIGURE 604.5.1.
 D) REAR GRAB BEHIND WATER CLOSET NOT CENTERED
 CORRECTLY- FIGURE 604.5.2.
 E) HEIGHTS OF GRABS SHOWN AT BOTH 33" AND 36" FROM
 FLOOR. GRAB BARS SHALL BE INSTALLED AT 33" MINIMUM AND
 36"MAXIMUM MEASURED FROM THE FINISHED FLOOR TO THE TOP
 OF THE GRIPPING SURFACE- SECTION 609.4.
 F) FLUSH CONTROL SHOWN ON THE WRONG SIDE OF THE WATER
 CLOSET- SECTION 604.6
 G) TOILET PAPER DISPENSER NOT LOCATED IN COMPLIANCE
 WITH- SECTION 604.7.
 H) HEIGHT OF THE MIRROR SHALL BE 40" FROM THE FINISHED
 FLOOR TO THE BOTTOM OF THE REFLECTIVE SURFACE SECTION
 603.3.
 I) KNEE AND TOE CLEARANCES FOR THE LAVATORY NOT SHOWN-
 SECTIONS 305 & 306.
  
 7) FAILED. A2, A3, & A4: NO ACCESSIBILITY DETAILS HAVE
 BEEN PROVIDED FOR THE ALTERED SECOND FLOOR BATHROOM.
 THE CONFIGURATION OF THE ROOM INDICATES NON-COMPLIANCE.
 PLEASE PROVIDE ENLARGED DRAWINGS AND DETAILS TO SHOW
 COMPLIANCE WITH THE FBC ACC. THE ACCESSIBILITY ALLOWS
 SOME EXCEPTIONS FOR PRIVATE BATHROOMS INCLUDING TOILET
 SEATS (SECTION 604.4), GRAB BARS FOR TOILETS AND
 SHOWERS (604.5 & 608.3), LAVATORY KNEE AND TOE
 CLEARANCES (606.2) & LAVATORY HEIGHT (606.3). IN LIEU
 OF THE GRAB BARS REINFORCEMENTS FOR FUTURE GRABS ARE
 REQUIRED TO BE INSTALLED. ALL OTHER COMPLIANCES LISTED
 BELOW SHALL BE MET AND SHOWN ON THE PLANS UNLESS MARKED
 AS NOT REQUIRED.
  
 A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 WATER CLOSET- SECTION 604.3.
 B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 LAVATORY- SECTION 606.2.
 C) DIAGRAMS AND DIMENSIONS FOR THE NEW SHOWER PER
 SECTION 608.2.1 AND FIGURE 608.2.1. THE SHOWER
 COMPARTMENT SHALL BE 36 INCHES BY 36 INCHES CLEAR
 INSIDE DIMENSIONS MEASURED AT THE CENTER POINTS OF
 OPPOSING SIDES AND SHALL HAVE A 36 INCH WIDE MINIMUM
 ENTRY ON THE FACE OF THE SHOWER COMPARTMENT. CLEARANCE
 OF 36 INCHES WIDE MINIMUM BY 48 INCHES LONG MINIMUM
 MEASURED FROM THE CONTROL WALL SHALL BE PROVIDED.
 D) BATHROOM ENTRY DOOR WIDTH, DOOR SWING, AND
 WHEELCHAIR APPROACHES- SECTION 604.8.1.2 & 604.8.1.3.
 PLEASE SEE SECTION 403.5- 36 IN. WALKING CLEAR WIDTH,
 AND 404.2.3- 32 IN. DOOR CLEAR WIDTH REQUIRED.
 E) TURNING SPACE DIAMETERS SECTION 304.3.
 F) CENTERLINE OF THE WATER CLOSET FROM THE SIDE WALL-
 SECTION 604.2.
 G) NOT REQUIRED. HEIGHT OF THE WATER CLOSET SEAT FROM
 THE FINISHED FLOOR- SECTION 604.4.
 H) NOT REQUIRED. HEIGHT OF THE FRONT RIM OF THE
 LAVATORY FROM THE FINISHED FLOOR- SECTION 606.3
 I) NOT REQUIRED. KNEE AND TOE CLEARANCES FOR THE
 LAVATORY- SECTION 306.
 J) REINFORCEMENTS REQUIRED. LOCATIONS, LENGTHS, AND
 MOUNTING HEIGHTS OF GRAB BARS- SECTION 604.5
 K) LOCATION OF THE WATER CLOSET FLUSH CONTROL- SECTION
 604.6.
 L) LOCATION, CLEARANCE, AND MOUNTING HEIGHT FOR THE
 TOILET PAPER DISPENSER- SECTION 604.7.
 M) HEIGHT OF THE MIRROR FROM THE FINISHED FLOOR TO THE
 BOTTOM OF THE REFLECTIVE SURFACE- SECTION 603.3
 N) REINFORCEMENTS REQUIRED. NEW SHOWER GRAB BAR AND
 SHOWER CONTROL LOCATIONS AND CLEARANCES PER SECTIONS
 AND FIGURES 608.3.1 & 608.5.1.
 O) REINFORCEMENTS REQUIRED. LOCATION AND DETAILS FOR
 INSTALLATION OF THE REQUIRED SEAT IN THE SHOWER-
 SECTION 608.4 & 610.3.
  
 NEW COMMENT BASED ON RESUBMITTED PLANS AND DOCUMENTS.
  
 1) CONCERNING THE DISPROPORTIONATE ITEMIZED COSTS
 SHEET, PLEASE REFER TO SECTION 202.4.2 FBC ACC:
 PRIORITY SHALL BE GIVEN TO THOSE ELEMENTS THAT WILL
 PROVIDE THE GREATEST ACCESS BEGINNING WITH THE
 ACCESSIBLE ENTRANCE AND FOLLOWED BY ACCESSIBLE ROUTE TO
 THE ALTERED AREA. YOU ARE SHOWING THE COSTS ASSOCIATED
 WITH THE ENTRANCE, BUT THE COSTS ASSOCIATED WITH THE
 ACCESSIBLE ROUTE DO NOT INCLUDE THE ESTIMATED COSTS TO
 PROVIDE VERTICAL ACCESSIBILITY TO THE 2ND FLOOR. THOSE
 COSTS TAKE PRIORITY OVER RESTROOMS, KITCHENS AND
 DRINKING FOUNTAIN COSTS. GIVEN THE NUMBERS SHOWN IT
 APPEARS COSTS ASSOCIATED WITH THE ENTRANCE AND
 ACCESSIBLE ROUTE ARE AT 18 % OF THE TOTAL COSTS.
  
 2) REFER TO SECTIONS 306, 307, AND 602 FBC ACC AND
 PROVIDE DRINKING FOUNTAIN INSTALLATION DETAILS AND
 ELEVATION VIEWS SHOWING KNEE AND TOE CLEARANCES, SPOUT
 LOCATIONS AND HEIGHTS. THE FOUNTAINS SHALL BE INSTALLED
 TO MEET COMPLIANCE WITH SECTION 307.2 PROTRUDING
 OBJECTS. PLEASE SHOW HOW COMPLIANCE IS BEING MET.
  
 3) PROVIDE A SLAB REPAIR DETAIL FOR THE SLAB CUTS MADE
 TO INSTALL PLUMBING PIPES- SECTION 107.2.1 WPB.
  
 4) SHEET P-2: PROVIDE HOT WATER PIPE INSUILATION
 SPECIFICATIONS TO THE NOTES- TABLE C403.2.10 FBC EC.
  
 5) P-2: SHOW THE REQUIRED 1/4 IN. PER FT. SHOWER PAN
 SLOPE- SECTION 417.5.2 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  