2020-10-27 11:57:102017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20060456
 ADD: 1101 N. OLIVE AVE.
 CONT: S. D. CHURCH & SONS
 TEL:1- 386-314-3001
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. AUGUST 25TH / 2020
 ACTION: DENIED
  
 1) COMPLIED. ACCESSIBLE PARKING AND ACCESS AISLE.
  
 2) COMPLIED. LIFE SAFETY PLAN 1ST FLOOR & 2ND FLOOR.
  
 3) COMPLIED/ VERTICAL ACCESSIBILITY/ DISPROPORTIONATE
 COST.
  
 4)SEMI- COMPLIED, ADDITIONAL COMMENTS. SPOKE WITH THE
 CONTRACTOR ABOUT THE REQUIRED 20% DISPROPORTIONATE COST
 LETTER ON THE COMPANY LETTER HEAD AND WHAT ITEMS CAN BE
 INCLUDED UNDER THE 20% DISPROPORTIONATE COST. THE FIRST
 FLOOR SHOWS VARIOUS AREAS WHERE ACCESSIBLE UPGRADES ARE
 GOING TO BE MADE BUT THE 2ND FLOOR DOES SHOW
 ALTERATIONS TO THE 2ND FLOOR. THE RESTROOM 2 AND THE
 PRIVATE BATHROOM AS WELL AS DOORS TO THE RESTROO#2 AND
 PRIVATE BATHROOM.
  
 WHEN YOU REMODEL A ELEMENT AS DOORS AND OR RESTROOMS
 AND OR BATHROOMS THEN THEY HAVE TO BE BROUGHT UP TO THE
 CURRENT CODE STANDARDS. 2017 EXISTING BUILDING CODE.
 801.3 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS,
 COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE
 REQUIREMENTS OF THE FLORIDA BUILDING CODE, BUILDING.
 UNDER THE EXISTING BUILDING CODE EACH PORTION OF THIS
 CODE LEVEL I, LEVEL 2 OR LEVEL 3 ALL REFER BACK TO THE
 ACCESSIBILITY CODE. IF ELEMENTS ARE NOT TOUCHED THEN
 THEY CAN STAY AS THEY ARE. THE DISPROPORTIONATE COST
 KICKS IN TRYING TO MAKE THE BUILDING OVER A SERIES OF
 SMALLER RENOVATIONS. YOU SHOW HOW YOU HAVE MET THE
 DISPROPORTIONATE COST FOR THE VERTICAL ACCESSIBILITY,
 BUT THAT DOES NOT RELIEVE YOU FROM UPGRADING THE 2ND
 FLOOR WHERE WORK IS SHOWN TO BE PREFORMED.
  
  
 DISPROPORTIONATE COST. PLEASE REVIEW HOW YOU ARE TO
 MEET DISPROPORTIONATE COST. EITHER THE CONTRACTOR OR
 THE DESIGNER OF RECORD ON THEIR LETTERHEAD NEED TO SHOW
 HOW THEY ARE GOING TO SPEND THE 20% DISPROPORTIONATE
 FUNDS LISTED FOR EACH ELEMENT WHERE THE FUNDS ARE BEING
 SPENT AND IN THE ORDER LISTED IN SECTION 202.4.1
 DISPROPORTIONATE COST OF THE 2017 ACCESSIBILITY CODE.
  
 5A-C) COMPLIED.
  
 5D)SEMI-COMPLIED. SHEET A-3 DOES NOT SHOW A HIGH- LOW
 DRINKING FOUNTAIN. THE 1ST AND 2ND FLOOR COMBINED
 OCCUPANT LOAD IS 27 OCCUPANTS REQUIRING DRINKING
 FOUNTAINS. THE FLOOR PLAN DOES SHOW A HIGH/ LOW
 DRINKING FOUNTAIN AND 30X 48 CLEAR FLOOR SPACE. SHEET
 A4 SHOWS ELEVATIONS FOR ELEMENTS WITHIN THE RESTROOMS
 BUT MISSING ELEVATIONS FOR THE DRINKING FOUNTAIN AND
 COMPLIANCE WITH:
  
 DRINKING FOUNTAINS.
 5D)(1) 2017 FBC-ACCESSIBILITY CODE. 211.2 MINIMUM
 NUMBER. NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE
 PROVIDED. ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1
 THROUGH 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY
 WITH 602.7. SHOW ELEVATION VIEW WITH SPOUT HEIGHTS.
  
 5D)(2) PROTRUDING OBJECTS 307.2 PROTRUSION LIMITS
 307.2. OBJECTS WITH LEADING EDGES MORE THAN 27 INCHES
 AND NOT MORE THAN 80 INCHES ABOVE THE FLOOR SHALL NOT
 PROTRUDE MORE THAN 4 INCHES HORIZONTALLY INTO THE
 CIRCULATION PATH. SHOW WITH ELEVATION VIEW, DOES THIS
 TYPE OF DRINKING FOUNTAIN THE BOTTOM OF THE SHROUD LESS
 THAN 27 INCHES OFF THE FLOOR FOR BOTH HIGH & LOW
 DRINKING FOUNTAINS?
  
 5D)(3) COMPLIED. 30X48 CLEAR FLOOR SPACE.
  
 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER