2020-07-02 08:51:461ST REVIEW FBC-2017 PLUMBING
 PERMIT- 20060456
 7/2/2020
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P1: THE SINK FIXTURE DRAIN MUST CONNECT TO THE
 3" BUILDING DRAIN DOWNSTREAM OF THE WC AND LAVATORY PER
 SECTIONS 912.1 AND 912.2.1 FBC P.
  
 2) P1: PROVIDE A WATER RISER DRAWING SHOWING PIPE
 SIZES, LOCATIONS OF SHUTOFF VALVES, WATER HAMMER
 ARRESTORS, MIXING VALVES ETC.- SECTION 107.3.5.1.3 WPB
 AMENDMENTS TO THE FBC.
  
 3) P1: PROVIDE A PLUMBING FIXTURE AND DEVICE SCHEDULE-
 SECTION 107.2.1 WPB & SECTION 405.9 FBC P.
  
 4) P1: PROVIDE PLUMBING FIXTURE CALCULATIONS FOR THE
 PROPOSED ALTERATIONS PER TABLE 403.3 FBC P. PROVIDE A
 SCHEDULE INDICATING THE REQUIRED AND PROVIDED PLUMBING
 FIXTURES. PLEASE NOTE THAT THE PLAN DOES NOT INDICATE
 DRINKING FOUNTAINS, OR A SERVICE SINK ARE EITHER
 EXISTING OR PROPOSED. REFER TO SECTION 211.1- 211.3 FBC
 ACC FOR ACCESSIBLE DRINKING FOUNTAIN REQUIREMENTS.
 REVISE THE PLANS TO SHOW COMPLIANCE.
  
 5) P1: INDICATE HOW TEMPERED WATER WILL BE PROVIDED TO
 THE LAVATORY- SECTION 416.5 FBC P.
  
 6) A4: ACCESSIBILITY CORRECTIONS- FBC ACC:
 A) LENGTH OF THE LAVATORY CLEAR FLOOR SPACE NOT SHOWN-
 SECTION 606.2 AND 305.
 B) HEIGHT TO THE TOP OF THE WATER CLOSET SEAT FROM THE
 FINISHED FLOOR INDICATED AT 20"- SECTION 604.4
 C) THE SIDE GRAB BAR AT THE WATER CLOSET SHALL EXTEND
 MINIMUM 54" FROM THE REAR WALL- FIGURE 604.5.1.
 D) REAR GRAB BEHIND WATER CLOSET NOT CENTERED
 CORRECTLY- FIGURE 604.5.2.
 E) HEIGHTS OF GRABS SHOWN AT BOTH 33" AND 36" FROM
 FLOOR. GRAB BARS SHALL BE INSTALLED AT 33" MINIMUM AND
 36"MAXIMUM MEASURED FROM THE FINISHED FLOOR TO THE TOP
 OF THE GRIPPING SURFACE- SECTION 609.4.
 F) FLUSH CONTROL SHOWN ON THE WRONG SIDE OF THE WATER
 CLOSET- SECTION 604.6
 G) TOILET PAPER DISPENSER NOT LOCATED IN COMPLIANCE
 WITH- SECTION 604.7.
 H) HEIGHT OF THE MIRROR SHALL BE 40" FROM THE FINISHED
 FLOOR TO THE BOTTOM OF THE REFLECTIVE SURFACE SECTION
 603.3.
 I) KNEE AND TOE CLEARANCES FOR THE LAVATORY NOT SHOWN-
 SECTIONS 305 & 306.
  
 7) A2, A3, & A4: NO ACCESSIBILITY DETAILS HAVE BEEN
 PROVIDED FOR THE ALTERED SECOND FLOOR BATHROOM. THE
 CONFIGURATION OF THE ROOM INDICATES NON-COMPLIANCE.
 PLEASE PROVIDE ENLARGED DRAWINGS AND DETAILS TO SHOW
 COMPLIANCE WITH THE FBC ACC:
 A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 WATER CLOSET- SECTION 604.3.
 B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 LAVATORY- SECTION 606.2.
 C) DIAGRAMS AND DIMENSIONS FOR THE NEW SHOWER PER
 SECTION 608.2.1 AND FIGURE 608.2.1. THE SHOWER
 COMPARTMENT SHALL BE 36 INCHES BY 36 INCHES CLEAR
 INSIDE DIMENSIONS MEASURED AT THE CENTER POINTS OF
 OPPOSING SIDES AND SHALL HAVE A 36 INCH WIDE MINIMUM
 ENTRY ON THE FACE OF THE SHOWER COMPARTMENT. CLEARANCE
 OF 36 INCHES WIDE MINIMUM BY 48 INCHES LONG MINIMUM
 MEASURED FROM THE CONTROL WALL SHALL BE PROVIDED.
 D) BATHROOM ENTRY DOOR WIDTH, DOOR SWING, AND
 WHEELCHAIR APPROACHES- SECTION 604.8.1.2 & 604.8.1.3.
 E) TURNING SPACE DIAMETERS SECTION 304.3.
 F) CENTERLINE OF THE WATER CLOSET FROM THE SIDE WALL-
 SECTION 604.2.
 G) HEIGHT OF THE WATER CLOSET SEAT FROM THE FINISHED
 FLOOR- SECTION 604.4.
 H) HEIGHT OF THE FRONT RIM OF THE LAVATORY FROM THE
 FINISHED FLOOR- SECTION 606.3
 I) KNEE AND TOE CLEARANCES FOR THE LAVATORY- SECTION
 306.
 J) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS- SECTION 604.5
 K) LOCATION OF THE WATER CLOSET FLUSH CONTROL- SECTION
 604.6.
 L) LOCATION, CLEARANCE, AND MOUNTING HEIGHT FOR THE
 TOILET PAPER DISPENSER- SECTION 604.7.
 M) HEIGHT OF THE MIRROR FROM THE FINISHED FLOOR TO THE
 BOTTOM OF THE REFLECTIVE SURFACE- SECTION 603.3
 N) NEW SHOWER GRAB BAR AND SHOWER CONTROL LOCATIONS AND
 CLEARANCES PER SECTIONS AND FIGURES 608.3.1 & 608.5.1.
 O) LOCATION AND DETAILS FOR INSTALLATION OF THE
 REQUIRED SEAT IN THE SHOWER- SECTION 608.4 & 610.3.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER