2020-11-16 16:10:35 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT-20060456 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) PLEASE PROVIDE THE SPECIFICATIONS FOR THE BATH |
| EXHAUST FANS. FBC 107.2 |
| |
| 2) PLEASE PROVIDE CFM OF BATH EXHAUST FANS: FBC M TABLE |
| 403.3.1.1 NOTE E-RATES ARE PER WATER CLOSET OR URINAL. |
| THE HIGHER RATE SHALL BE PROVIDED WHERE THE EXHAUST |
| SYSTEM IS DESIGNED TO OPERATE INTERMITTENTLY. THE LOWER |
| RATE SHALL BE PERMITTED ONLY WHERE THE EXHAUST SYSTEM |
| IS DESIGNED TO OPERATE CONTINUOUSLY WHILE OCCUPIED. |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| UPDATED. |
| |
| MICHAEL EDWARDS |
| MECHANICAL EXAMINER |
| 401 CLEMATIS STREET |
| WEST PALM BEACH FL. 33401 |
| 561-805-6728 |
| [email protected] |
| |