2020-11-04 06:18:57 | |
| |
| 1. IT APPEARS THAT SOME CHANGES MAY HAVE BEEN MADE TO |
| THE PROJECT THAT WERE NOT PERMITTED. PROVIDE AN |
| EXISTING FLOOR PLAN. THE FLOOR LAYOUT OF THE EXISTING |
| PLAN IN CITY RECORDS DOES NOT MATCH THE LAYOUT OF THE |
| SUBMITTED PLAN. THE RESPONSE IN THE RESPONSE NARRATIVE |
| OF " THE OLD PERMIT PLANS MUST BE INACCURATE" DOES NOT |
| SOLVE THIS ISSUE. WORK THAT WAS PREVIOUSLY DONE WITHOUT |
| PERMITS MUST BE LEGALLY PERMITTED. WPB AMEND. TO FBC |
| SEC. 107.3..5, 105.1. |
| 2. THE CENTERLINE OF THE WATER CLOSET SHALL BE 18 |
| INCHES MAXIMUM, NOT MINIMUM AS NOTED ON PLANS. SEE FBC |
| ACC 604.2. THE CENTERLINE OF THE WATER CLOSET SHALL BE |
| 16 INCHES MINIMUM TO 18 INCHES MAXIMUM FROM THE SIDE |
| WALL OR PARTITION. |
| 3)THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH |
| FLOOR SHALL BE 17 INCHES MINIMUM AND 19 INCHES MAXIMUM |
| MEASURED TO THE TOP OF THE SEAT. FBC ACC 604.4. PER WPB |
| FBC 107.2.1, CORRECT DETAIL ON PLAN A-3. |
| 4) INDICATE THE ON THE PLAN THAT THE TEMPERED WATER TO |
| THE SINK MAX 110 DEGREES BY AN APPROVED ASSE 1070 |
| DEVICE COMPLYING WITH FBC PL 607.1.2. |
| 5) THE 2017 ACCESSIBILITY CODE REQUIRES AT LEAST A HIGH |
| & LOW DRINKING FOUNTAIN INCOMPLIANCE WITH 2017 |
| FBC-ACCESSIBILITY CODE. 211.2 MINIMUM NUMBER. NO FEWER |
| THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED. ONE |
| DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH 602.6 |
| AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.7. THE |
| WATER DISPENSER IS NOT ACCEPTABLE AS IT DOES NOT |
| SATISFY THE DRINKING FOUNTAIN REQUIREMENTS. |
| 6) PROTRUDING OBJECTS 307.2 PROTRUSION LIMITS 307.2. |
| OBJECTS WITH LEADING EDGES MORE THAN 27 INCHES AND NOT |
| MORE THAN 80 INCHES ABOVE THE FLOOR SHALL NOT PROTRUDE |
| MORE THAN 4 INCHES HORIZONTALLY INTO THE CIRCULATION |
| PATH. |
| 7) SHT. A-1 - NOTE #8 CALLS OUT A UTILITY SINK BUT |
| THERE IS NO UTILITY SINK SHOWN ON THE PLANS. CLARIFY. |
| 8) SHT. A-2 - ACCESSIBLE TOILETS FOR KIDS DETAILS - THE |
| FRONT ELEVATION OF THE WATER CLOSET SHOWS THE |
| CENTERLINE AT 12-15 INCHES AND THE WHEELCHAIR |
| ACCESSIBLE WATER CLOOSET PLAN SHOWS 12-18 INCHES. |
| CORRECT THE DETAIL. |
| 9) SHT. A-2 - THE WATER CLOSET ELEVATION DETAIL SHOWS |
| THE GRAB BARS MEASURED TO THE CENTERLINE OF THE BAR. |
| GRAB BARS SHALL BE MEASURE TO THE TOP OF THE GRIPPING |
| SURFACE. FBC-ACCESS. SEC. 609.4. |
| 10) SHT. A-3 - PLUMBING FIXTURE MOUNTING HEIGHT DETAILS |
| - THE DETAILS REFER TO THE 2007 FBC.THE 2017 FBC IS IN |
| EFFECT. REVISE THE NOTE. ALSO, THE FIGURE NUMBERS |
| LISTED ON THE DETAILS ARE NO LONGER IN THE CODE. |
| 11) THE WATER HEATER DETAIL ON THE MEP PLAN SHOWS A TOP |
| FEED WATER HEATER BUT THE WATER HEATER SPECIFICATIONS |
| SHOW THE WATER HEATER IS BOTTOM FED. A VACUUM RELIEF |
| LINE IS REQUIRED ON THE COLD WATER LINE PER |
| FBC-PLUMBING SEC.504.2. |
| 12) THE WATER HEATER PAN SHALL COMPLY WITH FBC-PLUMBING |
| SEC.504.7 & 504.7.1. |
| 13) SHOW THE SIZE OF THE EXPANSION TANK ON THE WATER |
| HEATER. |
| 14) SUBMIT DETAILS AS TO HOW THE WATER HEATER IS BEING |
| SUPPORTED (TYPE AND SIZE OF HANGING RODS, TYPE AND |
| LOCATION OF CONNECTIONS TO BAR JOISTS). WPB AMEND. TO |
| FBC SEC. 107.2.1. |
| 15) ACCESS SHALL BE PROVIDED TO THE WATER HEATER IN THE |
| CEILING PER FBC-PLUMBING SEC.502.5. A LEVEL WORKING |
| SPACE NOT LESS THAN 30 INCHES IN LENGTH AND 30 INCHES |
| IN WIDTH SHALL BE PROVIDED IN FRONT OF THE CONTROL SIDE |
| TO SERVICE AN APPLIANCE. |
| |
| TIM LARGE |
| CHIEF PLUMBING INSPECTOR |
| PLUMBING PLAN REVIEW |