Plan Review Notes
Plan Review Notes For Permit 20060393
Permit Number 20060393
Review Stop P
Sequence Number 3
Notes
Date Text
2020-11-04 06:18:57 
  
 1. IT APPEARS THAT SOME CHANGES MAY HAVE BEEN MADE TO
 THE PROJECT THAT WERE NOT PERMITTED. PROVIDE AN
 EXISTING FLOOR PLAN. THE FLOOR LAYOUT OF THE EXISTING
 PLAN IN CITY RECORDS DOES NOT MATCH THE LAYOUT OF THE
 SUBMITTED PLAN. THE RESPONSE IN THE RESPONSE NARRATIVE
 OF " THE OLD PERMIT PLANS MUST BE INACCURATE" DOES NOT
 SOLVE THIS ISSUE. WORK THAT WAS PREVIOUSLY DONE WITHOUT
 PERMITS MUST BE LEGALLY PERMITTED. WPB AMEND. TO FBC
 SEC. 107.3..5, 105.1.
 2. THE CENTERLINE OF THE WATER CLOSET SHALL BE 18
 INCHES MAXIMUM, NOT MINIMUM AS NOTED ON PLANS. SEE FBC
 ACC 604.2. THE CENTERLINE OF THE WATER CLOSET SHALL BE
 16 INCHES MINIMUM TO 18 INCHES MAXIMUM FROM THE SIDE
 WALL OR PARTITION.
 3)THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH
 FLOOR SHALL BE 17 INCHES MINIMUM AND 19 INCHES MAXIMUM
 MEASURED TO THE TOP OF THE SEAT. FBC ACC 604.4. PER WPB
 FBC 107.2.1, CORRECT DETAIL ON PLAN A-3.
 4) INDICATE THE ON THE PLAN THAT THE TEMPERED WATER TO
 THE SINK MAX 110 DEGREES BY AN APPROVED ASSE 1070
 DEVICE COMPLYING WITH FBC PL 607.1.2.
 5) THE 2017 ACCESSIBILITY CODE REQUIRES AT LEAST A HIGH
 & LOW DRINKING FOUNTAIN INCOMPLIANCE WITH 2017
 FBC-ACCESSIBILITY CODE. 211.2 MINIMUM NUMBER. NO FEWER
 THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED. ONE
 DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH 602.6
 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.7. THE
 WATER DISPENSER IS NOT ACCEPTABLE AS IT DOES NOT
 SATISFY THE DRINKING FOUNTAIN REQUIREMENTS.
 6) PROTRUDING OBJECTS 307.2 PROTRUSION LIMITS 307.2.
 OBJECTS WITH LEADING EDGES MORE THAN 27 INCHES AND NOT
 MORE THAN 80 INCHES ABOVE THE FLOOR SHALL NOT PROTRUDE
 MORE THAN 4 INCHES HORIZONTALLY INTO THE CIRCULATION
 PATH.
 7) SHT. A-1 - NOTE #8 CALLS OUT A UTILITY SINK BUT
 THERE IS NO UTILITY SINK SHOWN ON THE PLANS. CLARIFY.
 8) SHT. A-2 - ACCESSIBLE TOILETS FOR KIDS DETAILS - THE
 FRONT ELEVATION OF THE WATER CLOSET SHOWS THE
 CENTERLINE AT 12-15 INCHES AND THE WHEELCHAIR
 ACCESSIBLE WATER CLOOSET PLAN SHOWS 12-18 INCHES.
 CORRECT THE DETAIL.
 9) SHT. A-2 - THE WATER CLOSET ELEVATION DETAIL SHOWS
 THE GRAB BARS MEASURED TO THE CENTERLINE OF THE BAR.
 GRAB BARS SHALL BE MEASURE TO THE TOP OF THE GRIPPING
 SURFACE. FBC-ACCESS. SEC. 609.4.
 10) SHT. A-3 - PLUMBING FIXTURE MOUNTING HEIGHT DETAILS
 - THE DETAILS REFER TO THE 2007 FBC.THE 2017 FBC IS IN
 EFFECT. REVISE THE NOTE. ALSO, THE FIGURE NUMBERS
 LISTED ON THE DETAILS ARE NO LONGER IN THE CODE.
 11) THE WATER HEATER DETAIL ON THE MEP PLAN SHOWS A TOP
 FEED WATER HEATER BUT THE WATER HEATER SPECIFICATIONS
 SHOW THE WATER HEATER IS BOTTOM FED. A VACUUM RELIEF
 LINE IS REQUIRED ON THE COLD WATER LINE PER
 FBC-PLUMBING SEC.504.2.
 12) THE WATER HEATER PAN SHALL COMPLY WITH FBC-PLUMBING
 SEC.504.7 & 504.7.1.
 13) SHOW THE SIZE OF THE EXPANSION TANK ON THE WATER
 HEATER.
 14) SUBMIT DETAILS AS TO HOW THE WATER HEATER IS BEING
 SUPPORTED (TYPE AND SIZE OF HANGING RODS, TYPE AND
 LOCATION OF CONNECTIONS TO BAR JOISTS). WPB AMEND. TO
 FBC SEC. 107.2.1.
 15) ACCESS SHALL BE PROVIDED TO THE WATER HEATER IN THE
 CEILING PER FBC-PLUMBING SEC.502.5. A LEVEL WORKING
 SPACE NOT LESS THAN 30 INCHES IN LENGTH AND 30 INCHES
 IN WIDTH SHALL BE PROVIDED IN FRONT OF THE CONTROL SIDE
 TO SERVICE AN APPLIANCE.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  