Date |
Text |
2020-08-07 12:36:11 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| MANUAL REVISED 2017 |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| EDITION |
| FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| FAC= FLORIDA ADMINISTRATIVE CODE |
| FS = FLORIDA STATUTES |
| |
| 20060393 2405 MERCER AVE |
| |
| 2ND REVIEW |
| PLUMBING COMMENTS: DENIED |
| |
| 1. IT APPEARS THAT SOME CHANGES MAY HAVE BEEN MADE TO |
| THE PROJECT THAT WERE NOT PERMITTED. SEE COMMENTS 4.B) |
| AND 5. REFER TO PERMIT 14050704. PROVIDE EXISTING FLOOR |
| PLAN AS PER CITY RECORDS UNDER PERMIT # 14050704 |
| (UNLESS THERE IS A MORE RECENT RECORD WHICH NEEDS TO BE |
| PROVIDED) AND INSPECTORS PHOTOS AS THERE IS NOTICEABLE |
| CHANGE TO THE FLOOR PLAN. FBC 107.3.5. EXPOSE ALL WORK |
| REQUIRING INSPECTION. IT SHALL BE THE DUTY OF THE |
| PERMIT APPLICANT TO CAUSE THE WORK TO REMAIN ACCESSIBLE |
| AND EXPOSED FOR INSPECTION PURPOSES. WPB AMEND TO THE |
| FBC 110.1 |
| |
| 2. PER WPB FBC 107.2.1, SUBMIT A SLAB REPAIR DETAIL FOR |
| REVIEW AND ONCE APPROVED HAVE TWO COPIES AT THE JOB |
| SITE. SHOW THE WIDTH OF THE REPAIR, THE MINIMUM |
| THICKNESS OF THE CONCRETE TO BE REPLACED, AND THE PSI |
| OF THE CONCRETE. SHOW THE SIZE AND LENGTH OF THE |
| DOWELS, THE MINIMUM EMBEDMENT DEPTH INTO THE EXISTING |
| SLAB, THE ANCHORING MATERIAL FOR THE DOWELS AND THE |
| SPACING OF THE DOWELS ON CENTER. THE REPAIR SHALL ALSO |
| INCLUDE TERMITE TREATMENT OF THE SOIL AND THE REQUIRED |
| VAPOR BARRIER OVER WELL-COMPACTED SOIL. A COPY OF THE |
| TERMITE CERTIFICATE SHALL BE ONSITE FOR A FINAL |
| INSPECTION. |
| |
| 3. WATER CLOSET |
| THE CENTERLINE OF THE WATER CLOSET SHALL BE 18 INCHES |
| MAXIMUM, NOT MINIMUM AS NOTED ON PLANS. SEE FBC ACC |
| 604.2. ?THE CENTERLINE OF THE WATER CLOSET SHALL BE 16 |
| INCHES MINIMUM TO 18 INCHES MAXIMUM FROM THE SIDE WALL |
| OR PARTITION? |
| THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH |
| FLOOR SHALL BE 17 INCHES MINIMUM AND 19 INCHES MAXIMUM |
| MEASURED TO THE TOP OF THE SEAT. SEATS SHALL NOT BE |
| SPRUNG TO RETURN TO A LIFTED POSITION PER FBC ACC |
| 604.4. PER WPB FBC 107.2.1, CORRECT DETAIL ON PLAN A-3. |
| |
| 4.A) SECOND REQUEST: PROVIDE A WATER ISOMETRIC FOR THE |
| NEW ACCESSIBLE TOILET ROOM PER WPB FBC 107.3.5. |
| INDICATE THE ON THE PLAN THE TEMPERED WATER TO THE SINK |
| MAX 110 DEGREES BY AN APPROVED ASSE 1070 DEVICE |
| COMPLYING WITH FBC PL 607.1.2. |
| 4.B) ADDITIONALLY, REFER TO PERMIT 14050704. THERE WAS |
| A SINK ADJACENT TO THE PLUMBING WET WALL IN THE ROOM |
| WHERE THE NEW ACCESSIBLE TOILET ROOM IS BEING ADDED. |
| THE WET WALL FOR THE NEW BATHROOM IS OPPOSITE THE |
| EXISTING WET WALL, SO THE EXISTING HOT WATER SYSTEM IS |
| NOT REMAINING AS IS AS NOTED IN THE COMMENT RESPONSE. |
| |
| 5. THERE APPEARS TO HAVE BEEN AN EXISTING DRINKING |
| FOUNTAIN (SEE PERMIT # 14050704) HOWEVER IT WAS IN A |
| DIFFERENT LOCATION THAN WHERE IT IS NOW SHOWN. PER WPB |
| FBC 107.2.1, PROVIDE A SANITARY AND WATER RISER DIAGRAM |
| FOR THE DRINKING FOUNTAIN. INCLUDE CONNECTION TO |
| EXISTING SERVICES. |
| |
| 6. SECOND REQUEST: PROVIDE THE REQUIRED CLEAR FLOOR |
| SPACED FOR THE TOILET AND SINK IN THE NEW ADA TOILET |
| ROOM. |
| CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES |
| MINIMUM MEASURED PERPENDICULAR FROM THE SIDE WALL AND |
| 56 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE REAR |
| WALL PER FBC ACC 604.3.1 |
| THE CLEAR FLOOR OR GROUND SPACE FOR LAVATORY SHALL BE |
| 30 INCHES MINIMUM BY 48 INCHES MINIMUM PER FBC ACC |
| 305.3 |
| |
| 7. SEE BUILDING REVIEW REMARKS BELOW |
| 4A)THERE IS NOT ENOUGH INFORMATION ON THE PLAN TO |
| DETERMINE CODE COMPLIANCE FOR THE REQUIRED NUMBER OF |
| FIXTURES REQUIRED UNDER THE 2017 FBC-B TABLE 2902.1 FOR |
| EDUCATION. THE SUBMITTED TABLE GIVES A OVERALL COUNT |
| BUT NOT BY AGE GROUP SEE THE 2017 ACCESSIBILITY CODE |
| 604.9 AGES 5-8 AGES 9-12 FOR WATER CLOSET CENTERLINE, |
| TOILET SEAT HEIGHT, GRAB BAR HEIGHT AND DISPENSER |
| HEIGHT. |
| 4B) 2ND REQUEST ACCESS. CODE TABLE 604.9.THE 2017 FBC-B |
| 468.3.5.1 STANDARDS. EDUCATIONAL AND ANCILLARY |
| FACILITIES SHALL BE PROVIDE WITH TOLIETS, HAND WASHING |
| AND DRINKING FOUNTAINS FOR ALL OCCUPANTS IN RATIOS AND |
| ACCESSIBLE AS REQUIRED BY THE FLORIDA BUILDING CODE, |
| FLORIDA LAWS AND FEDERAL REGULATIONS. SHEET A-1 & A2 |
| SHOWS A SINGLE DRINKING FOUNTAIN, PLEASE SHOW A DOUBLE |
| HIGH/ LOW, PLEASE SEE IN THE 2017 FBC-ACCESSIBILITY |
| CODE REQUIREMENTS FOR DRINKING FOUNTAINS. SHEET A-3 |
| SHOWS COMPLIANCE WITH : |
| NOT SHOWN IN COMPLIANCE. PROTRUDING OBJECTS 307.2 |
| PROTRUSION LIMITS 307.2. OBJECTS WITH LEADING EDGES |
| MORE THAN 27 INCHES AND NOT MORE THAN 80 INCHES ABOVE |
| THE FLOOR SHALL NOT PROTRUDE MORE THAN 4 INCHES |
| HORIZONTALLY IN TO THE CIRCULATION PATH. |
| |
| END OF COMMENTS. |
| |
| A COMPREHENSIVE REVIEW COULD NOT BE ACCOMPLISHED AT |
| THIS TIME. PLEASE RESUBMIT CLEARLY LEGIBLE PLANS AND A |
| RESPONSE NARRATIVE ADDRESSING THE PLUMBING COMMENTS |
| FROM THE FIRST REVIEW. |
| |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| FYI = SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO |
| BE DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR |
| ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. - OR - |
| IF YOUR ENGINEER OR ARCHITECT DOES NOT HAVE AN |
| ELECTRONIC OR DIGITAL SIGNATURE - PLEASE DROP OFF (CITY |
| HALL DROP BOX) THE ORIGINAL SIGNED AND SEALED |
| DRAWINGS/DOCUMENTS ALONG WITH A "PLAN REVIEW REQUEST |
| FORM" EXPLAINING THE REASON FOR SUBMITTING THE DOCUMENT |
| OR DRAWINGS. PLAN REVIEW REQUEST FORM CAN BE OBTAINED |
| BY E MAILING [email protected] AND ASKING FOR THE FORM |
| |
| |
| |
| |
| JERALD SMITH |
| PLUMBING PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| EMAIL [email protected] |
| PHONE 561-246-0882 MOBILE |
| |
| 20060393 2405 MERCER AVE |
| |
| |
| |
| |