Plan Review Notes For Permit 20060393 |
Permit Number |
20060393 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-07-06 08:27:56 | PLUMBING 1ST REVIEW COMMENTS: | | | | 1) PROJECT VALUATION OF $5000 APPEARS LOW. PROVIDE A | | BONA FIDE SIGN CONTRACT. FBC 109.3 | | | | 2) SHEET A1 LIST 2014 FBC AND SHEET A3 UNDER DETAIL #6 | | LIST 2007. AS OF 12/31/2018 WE ARE UNDER THE 2017 FBC | | 6TH ED. PLEASE CORRECT. | | | | 3) NEW ADA TOILET ROOM IS SHOW @ 76?. MIN PERMITTED | | WITH MIN SIZED SINK OF 19? X 17 WOULD REQUIRE 85? BUT | | AS CALLED OUT ON SHEET A3 THE SINK IS SHOWN AS BEING | | MOUNTED @ 18? OFF SIDE WALL MAKING THE MIN 88? FOR THIS | | PROJECT. THESE ARE FINISHED MEASUREMENTS. FBC-ACC 603, | | 604 | | | | 4) PROVIDE A WATER ISOMETRIC. FBC 107.3.5 SHOWING | | TEMPERED WATER TO THE SINK MAX 110 DEGREES BY AN | | APPROVED ASSE 1070 DEVISE. FBC-PLB 607.1.2 | | | | 5) PROVIDE THE REQUIRED HI/ LOW DRINKING FOUNTAIN. | | UNABLE TO LOCATE ON PLAN. FBC-PLB 410.3 | | | | 6) SHEET A3 DETAIL 6 SHOW GRAB BARS AS BEING MOUNTED TO | | THE CENTER. ALL GRAB BAR MEASUREMENTS SHALL BE TO THE | | TOP OF THE GRIPPING SURFACE. FBC 609.4 | | | | 7) SHEET A3 DETAIL #6 MIRROR IS SHOWN AS MOUNTING TO | | THE BOTTOM. PLEASE SHOWN MAX 40? TO THE BOTTOM OF THE | | REFLECTIVE SURFACE. FBC-ACC 603.3 | | | | 8) PROVIDE THE REQUIRED CLEAR FLOOR SPACED FOR THE | | TOILET AND SINK IN THE NEW ADA TOILET ROOM. FBC-ACC 604 | | | | TIM HUNT | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | ( CAP GOVERNMENT ) | | [email protected] | | | | | 2020-07-01 16:37:27 | TIM HUNT |
|