2020-07-06 08:27:56PLUMBING 1ST REVIEW COMMENTS:
  
 1) PROJECT VALUATION OF $5000 APPEARS LOW. PROVIDE A
 BONA FIDE SIGN CONTRACT. FBC 109.3
  
 2) SHEET A1 LIST 2014 FBC AND SHEET A3 UNDER DETAIL #6
 LIST 2007. AS OF 12/31/2018 WE ARE UNDER THE 2017 FBC
 6TH ED. PLEASE CORRECT.
  
 3) NEW ADA TOILET ROOM IS SHOW @ 76?. MIN PERMITTED
 WITH MIN SIZED SINK OF 19? X 17 WOULD REQUIRE 85? BUT
 AS CALLED OUT ON SHEET A3 THE SINK IS SHOWN AS BEING
 MOUNTED @ 18? OFF SIDE WALL MAKING THE MIN 88? FOR THIS
 PROJECT. THESE ARE FINISHED MEASUREMENTS. FBC-ACC 603,
 604
  
 4) PROVIDE A WATER ISOMETRIC. FBC 107.3.5 SHOWING
 TEMPERED WATER TO THE SINK MAX 110 DEGREES BY AN
 APPROVED ASSE 1070 DEVISE. FBC-PLB 607.1.2
  
 5) PROVIDE THE REQUIRED HI/ LOW DRINKING FOUNTAIN.
 UNABLE TO LOCATE ON PLAN. FBC-PLB 410.3
  
 6) SHEET A3 DETAIL 6 SHOW GRAB BARS AS BEING MOUNTED TO
 THE CENTER. ALL GRAB BAR MEASUREMENTS SHALL BE TO THE
 TOP OF THE GRIPPING SURFACE. FBC 609.4
  
 7) SHEET A3 DETAIL #6 MIRROR IS SHOWN AS MOUNTING TO
 THE BOTTOM. PLEASE SHOWN MAX 40? TO THE BOTTOM OF THE
 REFLECTIVE SURFACE. FBC-ACC 603.3
  
 8) PROVIDE THE REQUIRED CLEAR FLOOR SPACED FOR THE
 TOILET AND SINK IN THE NEW ADA TOILET ROOM. FBC-ACC 604
  
 TIM HUNT
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 ( CAP GOVERNMENT )
 [email protected]
  
  