2020-09-28 07:31:04 | 3RD REVIEW FBC-2017 MECHANICAL |
| PERMIT-20060389 |
| |
| CODES IN EFFECT: |
| |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) PLEASE SEE BUILDING B SQ. FT. SUMMARY ON SHEET A-1. |
| AFTER CARE ASSEMBLY AREA HAS AN OCCUPANT LOAD OF 72 |
| PEOPLE. PLEASE USE THIS OCCUPANT COUNT FOR THE OUTDOOR |
| AIR CALCULATIONS FOR THE AFTER CARE ROOM ON SHEET A-4. |
| WE MUST PROVIDE O.A. BASED ON THE OCCUPANT LOAD OF THE |
| SPACE. FBC M TABLE 403.3.1.1 |
| |
| 2) BASED ON FBC M TABLE 403.3.1.1: REQUIRED O.A. FOR |
| THIS BUILDING IS: AFTER CARE ROOM- 605 CFM; 4 |
| CLASSROOMS- 1007CFM. SHEET A-4- THE DRAWING SHOWS AN |
| O.A. DUCT FOR EXISTING AHU#1 BUT THE OUTDOOR AIR |
| CALCULATIONS DO NOT SHOW THE REQUIRED OUTDOOR AIR FOR |
| THIS ROOM. PLEASE SHOW THIS IN THE O.A. CALCULATIONS. |
| FBC M TABLE 403.3.1.1 |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| UPDATED. |
| |
| |