Plan Review Notes
Plan Review Notes For Permit 20060389
Permit Number 20060389
Review Stop P
Sequence Number 2
Notes
Date Text
2020-08-04 17:36:492ND REVIEW FBC-2017 PLUMBING
 PERMIT- 20060389
 8/4/2020
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A3: REMOVE THE REFERENCES TO THE FBC 2007
 SHOWN IN DETAIL 6. THE ACCESSIBLE TOILET ROOM SHALL BE
 DESIGNED IN ACCORDANCE WITH THE FLORIDA ACCESSIBILITY
 CODE- 2017 SIXTH EDITION.
  
 A) DETAIL 6 GRAB BARS: REFER TO FIGURE 604.5.2 FBC ACC
 AND CORRECT THE REAR WALL GRAB BAR DETAIL.
  
 B) 2ND REQUEST FOR LOCATION, MOUNTING HEIGHT AND
 CLEARANCE FOR THE TOILET PAPER DISPENSER- SECTION
 604.7.
  
 C) REFER TO FIGURES 306.2 AND 306.3 AND CORRECT THE
 KNEE AND TOE CLEARANCES FOR THE LAVATORY. TOE
 CLEARANCES SHALL BE MINIMUM 9" IN HEIGHT, AND KNEE
 CLEARANCE SHALL BE 11" DEEP MINIMUM AT 9" ABOVE THE
 FINISHED FLOOR- SECTION 306.3.3.
  
 2) COMMENTS #5,6,7, & 8 FROM THE 1ST REVIEW LISTED
 BELOW HAVE NOT BEEN ADDRESSED- PLEASE COMPLY.
 5) A3: PROVIDE A WATER RISER DRAWING SHOWING PIPE
 SIZES, LOCATIONS OF SHUTOFF VALVES, WATER HAMMER
 ARRESTORS, MIXING VALVES ETC.- SECTION 107.3.5.1.3 WPB
 AMENDMENTS TO THE FBC. NOT PROVIDED.
  
 6) A3: PROVIDE PLUMBING FIXTURE AND DEVICE SCHEDULES ON
 THE PLAN- SECTION 107.2.1 WPB & SECTION 405.9. NOT
 PROVIDED.
  
 7) A3: INDICATE HOW TEMPERED WATER WILL BE PROVIDED TO
 THE LAVATORY- SECTION 416.5 FBC P. NOT PROVIDED.
  
 8) A1 & A3: PROVIDE THE SCOPE OF WORK FOR THE REQUIRED
 WATER HEATER- SECTION 607.1 FBC P. CLARIFY IF THE
 APPLIANCE IS EXISTING OR TO BE REPLACED. SHOW THE
 LOCATION AND PROVIDE PLUMBING DETAILS IF APPLICABLE.
 PLEASE NOTE THAT THE DEVELOPED LENGTH OF HOT OR
 TEMPERED WATER PIPING, FROM THE SOURCE OF HOT WATER TO
 THE FIXTURES THAT REQUIRE HOT OR TEMPERED WATER, SHALL
 NOT EXCEED 50 FEET.
 THE WATER HEATER DETAIL ON A3 DOES NOT SPECIFY A MAKE
 AND MODEL, GALLON SIZE, OR EFFICIENCY RATING.
 NOTE-7 SPECIFIES A MIXING VALVE BUT INCORRECT LISTING-
 ASSE 1070 CONFORMANCE REQUIRED- SECTION 607.1.2 FBC P.
 NOTE-8 INDICATES MIXING VALVE TEMPERATURE SETTING AT
 140 DEGREES. TEMPERED WATER SHALL HAVE A TEMPERATURE
 RANGE 0F 85 TO 110 DEGREES FAHRENHEIT.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  