Plan Review Notes
Plan Review Notes For Permit 20060389
Permit Number 20060389
Review Stop P
Sequence Number 1
Notes
Date Text
2020-07-02 11:48:411ST REVIEW FBC-2017 PLUMBING
 PERMIT- 20060389
 7/2/2020
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A1: REFER TO SECTION 468.3.5.1 FBC B, AND
 TABLE 403.3 FBC P AND PROVIDE PLUMBING FIXTURE
 CALCULATIONS. PROVIDE A SCHEDULE ON THE PLAN INDICATING
 THE REQUIRED AND PROVIDED PLUMBING FIXTURE BASED ON THE
 E OCCUPANCY AND OCCUPANT LOAD OF 183. PLEASE NOTE THAT
 A MINIMUM OF TWO DRINKING FOUNTAINS ARE REQUIRED- REFER
 TO SECTION 211.1- 2113 FBC ACC PLEASE NOTE A THOROUGH
 REVIEW OF THE PLANS CANNOT BE ACCOMPLISHED UNTIL THE
 SCHEDULE IS PROVIDED- SECTION 107.2.1 WPB.
  
 2) A1, A2: IDENTIFY THE NEW TOILET ROOM AS EITHER MALE
 OR FEMALE- SECTION 403.2 FBC P.
  
 3) A3: PROVIDE ENLARGED TOILET ROOM DRAWINGS
 INDICATING:
 A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 WATER CLOSET- SECTION 604.3.
 B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 LAVATORY- SECTION 606.2.
 C) TURNING SPACE DIAMETER- SECTION 304.3.
 D) LOCATION OF THE WATER CLOSET FLUSH CONTROL- SECTION
 604.6.
 E) LOCATION, CLEARANCE, AND MOUNTING HEIGHT FOR THE
 TOILET PAPER DISPENSER- SECTION 604.7.
  
 4) A3: THE SINK FIXTURE DRAIN MUST CONNECT TO THE 3"
 BUILDING DRAIN DOWNSTREAM OF THE WC AND LAVATORY PER
 SECTIONS 912.1 AND 912.2.1 FBC P.
  
 5) A3: PROVIDE A WATER RISER DRAWING SHOWING PIPE
 SIZES, LOCATIONS OF SHUTOFF VALVES, WATER HAMMER
 ARRESTORS, MIXING VALVES ETC.- SECTION 107.3.5.1.3 WPB
 AMENDMENTS TO THE FBC.
  
 6) A3: PROVIDE PLUMBING FIXTURE AND DEVICE SCHEDULES ON
 THE PLAN- SECTION 107.2.1 WPB & SECTION 405.9 FBC P.
  
 7) A3: INDICATE HOW TEMPERED WATER WILL BE PROVIDED TO
 THE LAVATORY- SECTION 416.5 FBC P.
  
 8) A1 & A3: PROVIDE THE SCOPE OF WORK FOR THE REQUIRED
 WATER HEATER- SECTION 607.1 FBC P. CLARIFY IF THE
 APPLIANCE IS EXISTING OR TO BE REPLACED. SHOW THE
 LOCATION AND PROVIDE PLUMBING DETAILS IF APPLICABLE.
 PLEASE NOTE THAT THE DEVELOPED LENGTH OF HOT OR
 TEMPERED WATER PIPING, FROM THE SOURCE OF HOT WATER TO
 THE FIXTURES THAT REQUIRE HOT OR TEMPERED WATER, SHALL
 NOT EXCEED 50 FEET.
  
 9) A1 & A3: CONCERNING THE REQUIRED DRINKING FOUNTAINS
 PLEASE SEE SECTION 211.1.2 FBC ACC- NO FEWER THAN TWO
 DRINKING FOUNTAINS SHALL BE PROVIDED. ONE DRINKING
 FOUNTAIN SHALL COMPLY WITH SECTIONS 602.1 - 602.6, AND
 ONE SHALL COMPLY WITH 602.7. SECTION 602.7 REQUIRES
 THAT SPOUT OUTLETS FOR STANDING PERSONS SHALL BE 38
 INCHES MINIMUM AND 43 INCHES MAXIMUM FROM THE FINISHED
 FLOOR. SHOW THE LOCATIONS OF THE FOUNTAIN AND SHOW:
 A) THE CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR
 FORWARD WHEELCHAIR APPROACH- SECTION 602.2. FBC ACC.
 B) KNEE AND TOE CLEARANCES- SECTION 306.
 C) SPOUT HEIGHT AND SPOUT LOCATION- SECTION 602.4 AND
 602.5.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  