2020-06-14 15:39:482017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20060389
 ADD: 2401 MERCER AVE.
 CONT: BUTLER CONSTRUCTION
 TEL: 561-832-9700
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SUN. JUNE 14TH/ 2020
 ACTION: DENIED
  
 1) THE SUBMITTED PERMIT APPLICATION STATES THAT IT IS
 FOR THE RENOVATION OF AN EXISTING RESTROOM FOR A VALUE
 OF $5,000.00 DOLLARS. THE PERMIT APPLICATION DOES NOT
 STATE IF THE WORK TO BE PERFORMED UNDER THIS PERMIT IS
 IN BUILDING A OR BUILDING B? TO FURTHER CONFUSE THE
 JOBSITE LOCATION IN THE TITLEBLOCK THE LOCATION STATES
 2401 MERCER BUILDING B. THE LIFE SAFETY SHEET A-1 UNDER
 THE FLOOR PLAN STATES BUILDING A, WHICH IS IT? THE
 LOCATION OF WHERE THIS PROJECT IS TO TAKE PLACE IS IN
 QUESTION?
 2017 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED.
  
 2) SHEET A-1 CODE REFERENCES LIST THE 2014 FBC AS THE
 CODE IN AFFECT. PLEASE UPDATE THE CODE REFERENCE TO THE
 2017 FBC. THE 2017 FAMILY OF THE 6TH EDITION FLORIDA
 BUILDING CODE HAS BEEN ADOPTED STATEWIDE SINCE
 12/31/2017.
  
 3) SHEET A-2 DOES MAKE REFERENCE TO THIS FACILITY IS A
 PUBLIC CHARTER SCHOOL GRADES K-8TH GRADE. PLEASE BE
 AWARE OF THE 2017 FBC-EXISTING BUILDING CODE SCOPING
 REQUIREMENTS AND THE EXCEPTION FOUND UNDER SECTION
 101.2. EXCEPTION: FOR THE PURPOSE OF PUBLIC EDUCATIONAL
 FACILITIES AND STATE LICENSED FACILITIES, SEE CHAPTER
 4, SPECIAL OCCUPANCIES, OF THE FLORIDA BUILDING CODE,
 BUILDING.
 SECTION 453 DEALS WITH STATE REQUIREMENTS FOR
 EDUCATIONAL FACILITIES. NOT THE LOCAL BUILDING
 DEPARTMENT CONCERN UNLESS THE SCHOOL BOARD SUBMITS
 PLANS FOR PUBLIC SCHOOLS.
  
 3A) SECTION 468.1 IS FOR FLORIDA?S PUBLIC AND PRIVATE
 SCHOOLS, COLLEGES AND UNIVERSITIES. THERE IS NO
 EXISTING BUILDING CODE TO GO BY UNDER SPECIAL
 OCCUPANCIES FOUND IN CHAPTER 4. THERE IS NOT ENOUGH
 INFORMATION ON THE PLAN TO DETERMINE CODE COMPLIANCE
 FOR CODE COMPLIANCE FOR THE REQUIRED NUMBER OF FIXTURES
 REQUIRED UNDER THE 2017 FBC-B TABLE 2902.1 FOR
 EDUCATION.
  
 3B) 2017 FBC-B 468.3.5.1 STANDARDS. EDUCATIONAL AND
 ANCILLARY FACILITIES SHALL BE PROVIDED WITH TOILETS,
 HAND WASHING FACILITIES AND DRINKING FOUNTAINS FOR ALL
 OCCUPANTS IN RATIOS AND ACCESSIBLE AS REQUIRED BY THE
 FLORIDA BUILDING CODE, FLORIDA LAW AND FEDERAL
 REGULATIONS. SHEET A-1 SHOWS A SINGLE DRINKING FOUNTAIN
 NOT A HIGH-LOW DRINKING FOUNTAIN AS REQUIRED BY:
 2017 FBC-ACCESSIBILITY CODE. 211.2 MINIMUM NUMBER. NO
 FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED.
 ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH
 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH
 602.7.
 DRINKING FOUNTAINS TO SHOW COMPLIANCE WITH 307.2
 PROTRUSION LIMITS. OBJECTS WITH LEADING EDGES MORE THAN
 27 INCHES AND NOT MORE THAN 80 INCHES ABOVE THE FINISH
 FLOOR SHALL PROTRUDE 4 INCHES OR LESS MAXIMUM
 HORIZONTALLY INTO THE CIRCULATION PATH. SKIRTS MAYBE
 REQUIRED TO BE APPLIED TO THE BOTTOM OF THE DRINKING
 FOUNTAIN.
  
 4) SHEET A-3 HAS RESTROOM DETAILS, THE GRAB BARS THAT
 SURROUND THE WATER CLOSET NEED TO BE UPDATED TO THE
 2017 FBC-ACCESSIBILITY CODE. 2017 FBC-ACCESSIBILITY
 CODE SECTION 609.4 POSITION OF GRAB BARS. GRAB BARS
 SHALL BE INSTALLED IN A HORIZONTAL POSITION, 33 INCHES
 MINIMUM AND 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR
 MEASURED TO THE TOP OF THE GRIPPING SURFACE, NOT
 CENTERLINE.
  
 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER