2020-06-12 11:48:08 | RESIDENTIAL (R3) BUILDING REVIEW COMMENTS |
| CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| |
| NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK |
| SHALL COMPLY WITH THE MATERIALS AND METHODS |
| REQUIREMENTS IN THE FLORIDA BUILDING CODE. |
| |
| 1- ACCORDING TO SEC. R301.2.1.4 FBC-RESIDENTIAL THE |
| BUILDING EXPOSURE FOR THIS HOUSE IS EXPOSURE "D". BASED |
| ON TABLE R301.2(4) FBC-RESIDENTIAL THE DESIGN PRESSURES |
| ARE -45.86 PSF AND +40.572 PSF. FLORIDA PRODUCT |
| APPROVAL FL16107-R10 SUBMITTED IS FOR A GARAGE DOOR |
| WITH THE DESIGN PRESSURES OF -44.0 PSF AND +38.0 PSF. |
| NEED TO PROVIDE ANOTHER PRODUCT APPROVAL THAT MEETS THE |
| DESIGN PRESSURES CALCULATED FROM TABLE R301.2(4) |
| FBC-RESIDENTIAL OR PROVIDE SIGNED AND SEALED |
| CALCULATIONS SHOWING THAT THE GARAGE DOOR PRODUCT |
| APPROVAL SUBMITTED MEETS THE DESIGN PRESSURES FOR A |
| BUILDING IN EXPOSURE "D". |
| |
| 2- CONTRACT SUBMITTED INDICATES THAT THE CUSTOMER NEEDS |
| TO INSTALL CODE APPROVED OUTLET. AN ELECTRICAL |
| SUBPERMIT IS REQUIRED IF THIS IS A NEW INSTALLATION. |
| SEC. 105.1 CITY AMENDMENTS. |
| |
| PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| QUESTIONS REGARDING THESE COMMENTS, |