Plan Review Notes
Plan Review Notes For Permit 20060348
Permit Number 20060348
Review Stop E
Sequence Number 1
Notes
Date Text
2020-06-29 10:05:28CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) ELECTRICAL PERMIT REQUIRED.
  
 2) PAGE E-100 PROVE PROTECTION FOR SERVICE EQUIPMENT
 SPACE PROVIDED IS ONLY 2' 110.26 PROVIDE WORKING
 CLEARANCES AND PROTECTION OF EQUIPMENT.
  
 3) PAGES E-701 AND E-002 ) NOTE #3 TO SECTION LOW
 VOLTAGE ELECTRICAL POWER BOTH HAVE REFERENCES TO
 VOLTAGE DROP, WHICH DO PREFER TO USE, PAGE E-002
 CONFORMS TO ENREGY CODE.
  
 4) PAGE E-801 RISER DOES NOT SHOW WIRE SIZES FOR
 SERVICE EQUIPMENT OTHER THAN GROUNDING. 215.5
  
 5) PAGE E-801 PROVIDE AIC RATING AND CALCULATION
 REQUIRED PER 110.9, 10
  
 PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
  
 6) PAGE E-801 DRIP LOOP ON SERVICE WILL BE TO LOW TO
 MEET THE REQUIREMENTS OF 230.23(B)(2)