2020-07-08 10:59:59PLAN REVIEW - FUEL GAS
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE DETAIL OF GENERATOR GAS COMPONENTS. RISER,
 SHUTOFF, REGULATOR, DRIP LEG AND FLEX CONNECTOR.
  
 2. PROVIDE APPROPRIATE TABLE FOR 2 PSI P.E. PIPE FROM
 FBC RESIDENTIAL FUEL GAS TABLES.
  
 3. PROVIDE TOTAL SUPPLY BTU FROM UTILITY.
  