2020-06-19 10:52:54 | PLAN REVIEW - FUEL GAS |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| PLANS EXAMINER BUILDING - PX3169 |
| PLANS EXAMINER 1&2 FAMILY - SFP306 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| CODES IN EFFECT: |
| 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| |
| 1ST REVIEW |
| |
| RESULTS: DENIED |
| |
| YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| BELOW. |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| 1. THE GAS PLAN AND ISO DRAWINGS FOR PERMIT 18090327 |
| NEW SFR ONLY SHOWS AN OUTDOOR GRILL AND RANGE. |
| |
| 2. A SEPERATE GAS PERMIT 19071618 WAS SUBMITTED FOR THE |
| INSTALLATION OF A TANKLESS WATER HEATER THW. THIS |
| SUBMITTAL HAS BEEN DENIED TWICE. COMMENTS ARE INCLUDED |
| FOR YOUR REVIEW. |
| |
| 3. THE GAS PLAN AND ISO DRAWINGS FOR REVISION 20060326 |
| SHOWS THE OUTDOOR GRILL AND RANGE BUT ALSO INCLUDES A |
| FIRE PIT, A TWH, A POOL HEATER AND A GENERATOR. |
| |
| NOTE: IF THE TWH IS TO BE INCLUDED IN REVISION 20060326 |
| THEN GAS PERMIT 19071618 CAN BE REVOKED. PLEASE ADVISE. |
| |
| COMMENTS FROM GAS PERMIT 19071618 FOR YOUR REFERENCE: |
| |
| PERMIT 19071618 TWH - LC |
| 1. UNDER THE AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| 6TH EDITION (2017), CHAPTER 1, ADMINISTRATION OF THE |
| CITY WEST PALM BEACH SECTION 107.3.5.3 RESIDENTIAL ITEM |
| 13 (ONE AND TWO-FAMILY). PLEASE SUBMIT AN GAS ISOMETRIC |
| DRAWING THAT CLEARLY SHOWS THE LENGTH OF ALL CUT |
| SECTIONS OF PIPE, WHERE YOUR METER IS LOCATED, HOW FAR |
| THE DISTANCE, IS IT A 2LBS OR .05 LBS SYSTEM, LIST THE |
| BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON |
| THE SYSTEM, SHOWER UNION AND REGULATOR PER 2017 FBC |
| FUEL GAS RES SECS. G2413.4.1, G2413.4.2. |
| 2. SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS |
| PER THE 2017 FBC FUEL GAS RES. SEC. G2420.4. |
| 3. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS |
| METER / MP REGULATOR) TO THE MOST REMOTE OUTLET IN THE |
| BUILDING AND/OR SYSTEM, LISTED SHUTOFF VALVES PER THE |
| 2017 FBC FUEL GAS RES. SEC. G2413.4.1. |
| 4. THE PLANS INDICATE AN EXISTING GAS METER. THE BTU |
| LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO THE |
| TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING |
| SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE EXISTING |
| SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING |
| SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS |
| THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH |
| APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH |
| APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF |
| PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE |
| OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE |
| EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE |
| SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE |
| REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES |
| 2017 FBC FUEL GAS RES. SECS.G2412.4, G2412.8, G2413.1, |
| G2413.2, G2413.3. |
| 5. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| PRESSURE REGULATORS. REGULATORS INSTALLED ON THE |
| EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR |
| INSTALLATION. 2017 FBC FUEL GAS SEC.410.1 OR 2017 FBC |
| FUEL GAS RES. SEC. G2421.1. |
| 6. REGULATORS INSTALLED OUTDOORS SHALL BE DESIGNED, |
| INSTALLED OR PROTECTED SO THEIR OPERATION WILL NOT BE |
| AFFECTED BY THE ELEMENTS. PROVIDE DOCUMENTATION FROM |
| THE MANUFACTURER THAT THE REGULATORS ARE APPROVED FOR |
| EXTERIOR USE. NFPA 58-11 SEC. 6.8.1.5. |
| 7. SUBMIT TWO COPIES OF THE SIZING TABLE USED IN THE |
| DESIGN FOR THE GAS SYSTEM OR PLACE A NOTE ON BOTH SETS |
| OF PLANS LISTING THE SIZING TABLES FROM GAS CODES OR |
| ANOTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS |
| SYSTEM 2017 FBC FUEL GAS RES. SEC. G2413.3. |
| 8. THERE IS A FIRE PIT, SECOND TANKLESS AND POOL |
| HEATER ON THE LAYOUT SUBMITTED AND NO SPECIFICATIONS OR |
| INSTALLATION INSTRUCTION. AS NOTED IN ITEM 4 THERE IS A |
| GAS METER ON THE MAIN HOUSE AND PERMIT 18090327 SHOW A |
| RANGE, OUTDOOR GRILL AND 199 BTU?S TANKLESS WHICH IS |
| NOT ADDED TO THE SYSTEM, PLEASE CLARIFY AND MAKE |
| CORRECTION PER THE WPB AMENDMENTS TO THE FBC SEC. |
| 105.1. |
| 9. A SUB ELECTRICAL PERMIT IS REQUIRED FOR THE SOURCE |
| OF IGNITION IF NOT THERE AT TIME OF INSTALLATION, WPB |
| AMENDMENTS TO THE FBC SEC. 105.1. |
| |
| NEW REVIEW COMMENTS FOR REVISION 20060326 ARE AS |
| FOLLOWS: |
| |
| EFFECTIVE IMMEDIATELY THE FOLLOWING INFORMATION SHALL |
| BE SHOWN ON ALL GAS DRAWINGS SUBMITTED FOR PERMITTING |
| IN THE CITY OF WEST PALM BEACH: |
| |
| 1. SUBMIT TWO COPIES OF AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS THE LENGTH OF ALL CUT SECTIONS OF PIPE |
| PER 2017 FBC-R SEC. G2413.4.1, G2413.4.2. |
| |
| 2. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL |
| PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE |
| CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR |
| EACH PIPE SIZE. WPB AMENDMENTS TO FBC SEC.107.2.1. |
| |
| 3. TYPE OF GAS (LP OR NATURAL).WPB AMEND. TO FBC SEC. |
| 107.2.1. |
| |
| 4. LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL |
| BTU LOAD ON THE SYSTEM. REFER TO THE 2017 FBC-RES. SEC. |
| G2413.3, G2413.4 AND TABLES G2413.4 (1 ) THROUGH |
| G2413.4 (21). CONTRACTOR TO STATE WHICH TABLES ARE |
| USED. |
| |
| 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS |
| METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND / OR SYSTEM PER THE 2017 |
| FBC-RES. SEC. G 2413.4.1, G2413.4.2. |
| |
| 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2017 |
| FBC-RES. SEC.G 2407.1 AND G2439.4 (CLOTHES DRYERS). |
| |
| 7. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM |
| ON THE PLAN PER 2017 FBC RES. SEC. G2413.2, G2413.4.3. |
| |
| 8. SUBMIT TWO COPIES OF A DETAIL SHOWING THE TYPE OF |
| VENT, LOCATION, SIZE, TERMINATION POINT, HEIGHT ABOVE |
| THE ROOF AND ANCHORING DETAILS OF THE GAS VENT(S) PER |
| 2017 FBC-RES. SEC.G2426 THROUGH G2439. |
| |
| 9. SUBMIT TWO COPIES OF THE MANUFACTURER?S |
| SPECIFICATION SHEETS / INSTALLATION MANUAL FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54, |
| NFPA 58, AND FBC-2017 FUEL GAS CODE SEC. 402.2, AND |
| 301.3 OR 2017 FBC-RES. SEC. G2404.3. GAS APPLIANCES |
| SHALL BE LISTED AND LABELED. THE INSTALLATION MANUALS |
| FOR ALL GAS APPLIANCES / EQUIPMENT SHALL BE ONSITE AT |
| THE TIME OF INSPECTION. FBC-RES. SEC.G2408.1. |
| |
| WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| REVIEWED SHEETS DETACHED. |
| |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| |
| |