Plan Review Notes
Plan Review Notes For Permit 20060298
Permit Number 20060298
Review Stop G
Sequence Number 1
Notes
Date Text
2020-07-10 11:33:12PLAN REVIEW - FUEL GAS GENERATOR
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
  
 1) GAS ISOMETRIC DRAWING:
 A) THE DRAWING IS INCOMPLETE AND MUST BE MODIFIED TO
 SHOW THE ENTIRE SYSTEM INCLUDING ALL BRANCH PIPES FROM
 THE METER TO THE MOST REMOTE OUTLET. THE BTUH LOAD OF
 EACH APPLIANCE AND THE LOCATIONS OF REGULATORS SHALL BE
 INDICATED ON THE DRAWING- SECTIONS G2412.3 & G2412.4
 FBC RES.
 B) PROVIDE THE TOTAL DEVELOPED LENGTH OF THE SYSTEM
 FROM THE METER TO THE MOST REMOTE OUTLET, AND BRANCH
 LENGTH SIZES- SECTIONS G2413.4.1, G2413.4.2 &
 G2413.4.3.
 B) PROVIDE DELIVERY PRESSURE TO THE GENERATOR FROM THE
 OUTLET OF THE REGULATOR- SECTION G2421.1
 C) CORRECT THE BTUH LOAD OF THE GENERATOR. THE
 SUBMITTED SPECS INDICATE 327,000 BTUH FULL LOAD-
 G2413.2 FBC RES.
  
  
  
  