2020-07-22 15:59:06ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) NEED TO SIZE THE OCP DEVICES FOR POOL PUMP,
 CHLORINATOR, AND LIGHT YOU JUST SHOW WIRE SIZES.
  
 2) VALUE OF PERMIT INCLUDES DECK AND POOL (28000)
 PLEASE SUBMIT A SIGNED CONTRACT FOR POOL AND DECK.