Plan Review Notes
Plan Review Notes For Permit 20060203
Permit Number 20060203
Review Stop B
Sequence Number 1
Notes
Date Text
2020-06-17 15:44:12FLOORING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED -
  
 THE IIC TEST REPORT NEEDS TO BE 50 OR HIGHER =
 FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING
 UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC OR
 SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN IMPACT
 INSULATION CLASS (IIC) RATING OF NOT LESS THAN 50 (45
 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E
 492. THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 ALSO NEED THE UNDERLAYMENT FLAME SPREAD RATING =
 FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723. PROVIDE A COPY OF THE TEST REPORT.