Plan Review Notes For Permit 20060203 |
Permit Number |
20060203 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-06-17 15:44:12 | FLOORING | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | | | CORRECTIONS NEEDED - | | | | THE IIC TEST REPORT NEEDS TO BE 50 OR HIGHER = | | FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING | | UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC OR | | SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN IMPACT | | INSULATION CLASS (IIC) RATING OF NOT LESS THAN 50 (45 | | IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E | | 492. THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM | | CEILING. PROVIDE A COPY OF THE TEST REPORT. | | | | ALSO NEED THE UNDERLAYMENT FLAME SPREAD RATING = | | FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE | | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL | | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID | | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED | | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE | | 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 | | OR UL 723. PROVIDE A COPY OF THE TEST REPORT. |
|