Plan Review Notes
Plan Review Notes For Permit 20060201
Permit Number 20060201
Review Stop FIRE
Sequence Number 4
Notes
Date Text
2020-07-13 10:48:15THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) THERE REMIANS NOT INDICATIONS IN WRITING NOR CLOUDS
 ON THE PALN SHEETS SHOWING WHAT AND WHERE CHANGES WERE
 MADE.
  
 PLACING A NOTE IN THE TITLE BLOCK STATING "REVISED PER
 FM COMMENTS" DOES NOT ADDRESS WHAT IS REQUIRED TO
 DOCUMENT THE CHANGES.
  
 PER NFPA 1
  
 1.14 PLAN REVIEW.
  
 1.14.5 WHEN REQUIRED BY THE AHJ, REVISED CONSTRUCTION
 DOCUMENTS OR SHOP DRAWINGS SHALL BE PREPARED AND
 SUBMITTED FOR REVIEW AND APPROVAL TO ILLUSTRATE
 CORRECTIONS OR MODIFICATIONS NECESSITATED BY FIELD
 CONDITIONS OR OTHER REVISIONS TO APPROVED PLANS.
  
  
 CONTACT ME DIRECTLY SO THAT WE CAN DISCUSS WHAT IS
 NEEDED.
  
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  